Basic Controls—System 350 P352AB Electronic Pressure Control Series Product/Technical Bulletin    

5

D352 Digital Pressure Display Module

The D352 Display Module receives power, sensor, and
setpoint information from the P352AB control. A
three digit Liquid Crystal Display (LCD) gives a
continuous readout of the sensed pressure. Pushing
the PRESS FOR SETPOINT button displays the
setpoint of the adjoining P352AB control. The button
must be pressed for approximately three seconds.
(Refer to the 

System 350

TM

 Display Modules

Product/Technical Bulletin, LIT-930070,

 for more

information.)

S352A Pressure Stage Modules

The S352A Stage Modules receive power, setpoint,
and sensor input from the P352AB controls. As many
as five S352A Stage Modules can plug into the
P352AB controls when powered by the Y350R Power
Module. When powered by an external transformer,
the P352AB controls can use up to nine S352A Stage
Modules. (Refer to the 

System 350

TM

 S350A

Temperature, S351A Humidity, and S352A Pressure
Stage Modules Product/Technical Bulletin,
LIT-930080,

 for more information.)

Note:

When using an external transformer, the
Y65 Series or other 40 VA Class 2
transformers are recommended.

!

 CAUTION: Verify that the jumpers are in the

proper position before powering
System 350 components. If the
jumpers on the P352AB control
or the S352A Stage Module are
in the wrong position, the device
will activate the relay in response
to the opposite signal. The
DA/RA relay will remain
energized until the error is
corrected.

A

djustments (S352A Stage Module)

Perform the following steps to adjust the S352A stage
module settings. (See Figure 4.) Refer to Figure 5 for
an illustration of the S352A Stage Modules in a typical
Direct Acting/Reverse Acting application.

!

 WARNING:

Risk of Electrical Shock.

Disconnect power supply to
avoid possible electrical shock or
equipment damage. More than
one disconnect may be required
to completely de-energize
equipment.

1.  Ensure all power to system is off.

Each stage module may be receiving separate
power sources. Make sure all power sources to
each stage module are off.

2.  Remove the stage module cover by loosening the

four captive cover screws.

3. 

Set the mode of operation

 by positioning the

jumpers (at Jumper Terminal J2) horizontally for
Direct Acting or vertically for Reverse Acting.

4. 

Adjust the differential

 using the potentiometer

marked DIFF to the desired setting.

5. 

Adjust the offset

 using the potentiometer marked

OFFSET to the desired pressure from the P352AB
control setpoint at which the stage relay will
de-energize (above setpoint with Direct Acting
mode selected or below setpoint with Reverse
Acting mode selected).

6.  Replace the S352A stage module cover and

tighten the captive cover screws.

7.  Restore power to system.

Module

Connector

Relay Energized

LED Indicator

Offset

Potentiometer

Differential

Potentiometer

Module

Connector

Jumper

Position at J2

Reverse Acting

Direct Acting

N.C.

Relay

N.O.

Terminals

COM

Output

Cover Screw

(One of Four)

Relay

Figure 4: Interior View and Typical Wiring

of the S352A Stage Module

Содержание System 350 P352AB Series

Страница 1: ... all System 350 products the P352AB control is housed in a NEMA 1 high impact thermoplastic enclosure The modular design provides easy snap together connections for quick installation and future expandability Figure 1 P352AB Electronic Pressure Control Features and Benefits Modular Design Provides the flexibility to add S352A Stage Modules D352 Display Module and Y350R Power Module Plug together C...

Страница 2: ...ontrol operates on 24 VAC and has an SPDT relay output A front panel LED lights to indicate when the relay is energized The P352AB controls are used with the P399 Electronic Pressure Transducers which are available in several pressure ranges and provide a ratiometric analog signal 0 5 to 4 5 VDC based on the sensed pressure IMPORTANT The P352AB controls use an input signal from the P399 Electronic...

Страница 3: ...ED illuminates Note The P352AB controls are configured for DA mode at the factory Refer to Figure 5 for an example of a typical Direct Acting Reverse Acting application Dimensions 1 3 16 2 3 8 61 7 16 11 1 1 2 40 1 8 4 DIN Rail Mount 7 8 22 Conduit Hole Mounting Slots For No 6 Screws 5 127 2 15 16 75 2 3 8 61 7 8 22 2 1 4 57 2 0 m 13 ft 4 0 m or Wiring Harness 6 1 2 ft P399 Transducer CONTROLS CON...

Страница 4: ...fter power is applied to the control a more accurate setting of the setpoint can be made by utilizing the D352A Pressure Display Module 6 Replace the cover on the control and fasten in place with screws 7 Restore power to system Module Connector Concealed Setpoint Adjustment Dial Differential Potentiometer N C Relay N O Terminals COM Output Relay Energized LED Indicator Jumper Position at J1 Rever...

Страница 5: ...te signal The DA RA relay will remain energized until the error is corrected Adjustments S352A Stage Module Perform the following steps to adjust the S352A stage module settings See Figure 4 Refer to Figure 5 for an illustration of the S352A Stage Modules in a typical Direct Acting Reverse Acting application WARNING Risk of Electrical Shock Disconnect power supply to avoid possible electrical shoc...

Страница 6: ...han one disconnect may be required to completely de energize equipment IMPORTANT Make all wiring connections in accordance with the National Electrical Code and all local regulations Use copper conductors only Do not exceed the control s electrical ratings Transducer Wiring The P352AB control supplies 5 VDC power to the P399 Electronic Pressure Transducer The transducer is wired to three of the fo...

Страница 7: ...te and tape Do not ground this end of cable shield 120 VAC Figure 6 System 350 Powered by an External Transformer Using 120 VAC Power Supply 120 VAC P352AB Y350R S352A S352A D352A S352A Load Load Load Load Isolate and tape Do not ground this end of cable shield P399 Transducer Wiring Harness White SEN Red VDC Black COM Wire Terminal Block 24V COM VDC SEN N O Terminals COM Output N C Relay Shield C...

Страница 8: ...and equipment check that all of the wiring is correct and all of the connections are tight b Apply power to the control c With the DVM check the voltage between the 24V and the COM terminals on the terminal block on the upper left side of the control If an external 24 VAC transformer powers the control select AC volts on the DVM The voltage must be between 20 and 30 VAC If a Y350R Power Module pow...

Страница 9: ...e Note Depending on the accuracy of the instrumentation used to measure the actual pressure at the transducer psiT and the transducer output voltage Vo the actual and calculated pressure may not exactly agree 10 90 50 Output Voltage of Power Supply 4 5 VDC 2 5 VDC 0 5 VDC 500 psi P352AB 3 P399B Pressure psi P352AB Model P399 Transducer 100 psi P352AB 2 P399A P 3 5 2 A B 2 P352AB 3 P352AB 4 Figure ...

Страница 10: ...what the On and Off setpoint pressure values are for each module f If a stage module LED and relay do not perform as expected adjust the differential and offset potentiometers to their minimum value and repeat the previous checks g If a stage module still does not perform properly replace the stage module 6 Check the display module for proper operation If there is no display module in the system s...

Страница 11: ...sure connection 0 to 500 psis 1 4 in SAE female flare pressure connection Electronic Pressure Transducers for the P352AB 4 P399CAA 1C P399CAC 1C 0 to 750 psis 1 8 in NPT male pressure connection 0 to 750 psis 1 4 in SAE female flare pressure connection Wiring Harness WHA P399 400C WHA P399 200C 13 1 ft 4 0 m length 6 6 ft 2 0 m length Display Module D352AA 2C Digital Pressure Display Module Stage ...

Страница 12: ...ty 125 VA at 24 240 VAC Ambient Temperature Operating 30 to 150 F 34 to 66 C Shipping 40 to 185 F 40 to 85 C Ambient Humidity 0 to 95 RH Non condensing Material Case Cover NEMA 1 High Impact Thermoplastic Agency Listing UL Listed CCN XAPX File E27734 UL Listed for Canada CCN XAPX7 File E27734 Only one voltage source may be used Add on Modules S352A Y350R D352 Relay Contacts SPDT 10 Amperes Non ind...

Отзывы: