SENTRY Carbon Dioxide Hand Portable Fire Extinguishers 

Operation, Inspection, Service and Maintenance,  

and Recharge Manual (Part No. 429425)

2018-OCT-11    REV. 05    PAGE 3

OPERATION

OPERATION

!

  

WARNING

Carbon dioxide extinguishers contain a suppressing agent 

that will not support life when used in sufficient concentration 

to suppress a fire. The use of this type of extinguisher in an 

unventilated space can dilute the oxygen supply. Prolonged 

occupancy of such spaces can result in loss of consciousness 

and possible death due to oxygen deficiency.

  1.  Remove extinguisher from its hanger.
  2.   Use handle to carry extinguisher to fire. Walk at a rapid 

pace. DO NOT RUN.

  3.   Proceed to upwind side of fire. Stay well clear of flames. 

From this position, air currents help carry agent into fire, 

assure maximum visibility, provide protection from heat, 

and lessen exposure to possible harmful vapors.

  4.   Start back from fire a distance recommended on 

extinguisher nameplate. Holding extinguisher by handle, 

grasp ring pin and pull straight out, breaking visual seal.

 5.  

5 lb Extinguisher: 

Position tube/horn assembly and 

squeeze handle lever to discharge agent.

    

10, 15, or 20 lb Extinguishers:

 Hold the nozzle with one 

hand and squeeze handle lever to discharge agent.

NOTICE

For additional information on proper use 

and applications of SENTRY Carbon 

Dioxide Extinguishers, Johnson Controls 

maintains a comprehensive library of 

training aids and offers hands-on fire 

fighting training at our fire school. Contact 

Johnson Controls, One Stanton Street, 

Marinette, WI 54143-2542, or your 

Authorized SENTRY Distributor.

 

Содержание SENTRY CD05-1

Страница 1: ...AND RECHARGE MANUAL One Stanton Street Marinette WI 54143 2542 USA 1 715 735 7411 www ansul com 2018 Johnson Controls All rights reserved All specifications and other information shown were current as...

Страница 2: ......

Страница 3: ...re abused in service or are not properly maintained they may not perform reliably These extinguishers are pressure vessels that must be treated with respect and handled with care Only genuine SENTRY r...

Страница 4: ...NING Indicates a hazardous situation in which a person could experience serious personal injury or death if the situation is not avoided CAUTION Indicates a hazardous situation in which a person could...

Страница 5: ...guishers Operation Inspection Service and Maintenance and Recharge Manual Part No 429425 TABLE OF CONTENTS 2018 OCT 11 REV 05 PAGE TOC 1 SECTION PAGE Introduction 1 2 Operation 3 Inspection 5 Maintena...

Страница 6: ...SENTRY Carbon Dioxide Hand Portable Fire Extinguishers Operation Inspection Service and Maintenance and Recharge Manual Part No 429425 PAGE TOC 2 REV 05 2018 OCT 11 TABLE OF CONTENTS NOTES...

Страница 7: ...frequency will vary from hourly to monthly based on the needs of the situation MAINTENANCE Extinguishers shall be maintained at regular intervals not more than one year apart or when specifically ind...

Страница 8: ...REFERENCES REFERENCES IN THIS MANUAL AVAILABLE FROM NFPA 10 STANDARD FOR NFPA PORTABLE FIRE 1 Batterymarch Park EXTINGUISHERS Quincy MA 02169 7471 CGA C 1 METHODS FOR Compressed Gas HYDROSTATIC Assoc...

Страница 9: ...Stay well clear of flames From this position air currents help carry agent into fire assure maximum visibility provide protection from heat and lessen exposure to possible harmful vapors 4 Start back...

Страница 10: ...SENTRY Carbon Dioxide Hand Portable Fire Extinguishers Operation Inspection Service and Maintenance and Recharge Manual Part No 429425 PAGE 4 REV 05 2018 OCT 11 OPERATION NOTES...

Страница 11: ...d on the valve body and includes hose and horn assembly 4 Remove extinguisher from its wall hanger or bracket Examine extinguisher for evidence of physical damage corrosion or other impairments 5 Chec...

Страница 12: ...SENTRY Carbon Dioxide Hand Portable Fire Extinguishers Operation Inspection Service and Maintenance and Recharge Manual Part No 429425 PAGE 6 REV 05 2018 OCT 11 INSPECTION NOTES...

Страница 13: ...Extinguishers taken out of service for maintenance or recharge shall be replaced by spare extinguishers of the same type and at least equal rating 3 Clean extinguisher to remove dirt grease and forei...

Страница 14: ...04995 11 5 lb Extinguisher Only Assure nut attached to hex swivel rotates freely but not loosely 12 Check siphon tube by shaking entire extinguisher A metallic rattling noise indicates separation of s...

Страница 15: ...freezing if sprayed on bare skin or in the eyes NOTICE If charging multiple extinguishers keep the components for each extinguisher separate Valve assemblies and shells are not indexed and nameplates...

Страница 16: ...se spring clamp from operating lever when scale indicates correct amount of CO2 has been introduced into cylinder Close CO2 supply line valve and vent CO2 supply line to outside atmosphere 9 Install r...

Страница 17: ...p and gives sugges tions for corrective action For further information contact Johnson Controls WARNING Contents under high pressure Before removing or disassem bling valve make sure extinguisher is c...

Страница 18: ...ly Leak at cylinder valve joint Examine for cracks around perimeter of cylinder neck Discard if cracks are found If leaking at thread joint remove valve from cylinder Clean threads with stiff brush On...

Страница 19: ......