SENTRY Carbon Dioxide Hand Portable Fire Extinguishers 

Operation, Inspection, Service and Maintenance,  

and Recharge Manual (Part No. 429425)

INTRODUCTION

2018-OCT-11    REV. 05    PAGE 1

INTRODUCTION

When utilized, the Occupational Safety and Health Act 

(OSHA) rules require that ‘‘the employer shall be responsible 

for the inspection, maintenance, and testing of all portable 

extinguishers in the work place.’’ Details are provided in the 

Code of Federal Regulations 29 CFR 1910.157(e) and in 

Appendixes A and B to Subpart L, referencing the provisions 

of NFPA 10 as guidelines. The latest edition of NFPA 10 

‘‘Standard for Portable Fire Extinguishers’’ is available from 

the National Fire Protection Association, visit www.nfpa.org.
The Compressed Gas Association Inc. CGA C-6 ‘‘Standards 

For Visual Inspection of Steel Compressed Gas Cylinders’’ 

and CGA C-6.1 ‘‘Standards For Visual Inspection of High 

Pressure Aluminum Compressed Gas Cylinders’’ provides 

information on determining unacceptable dents and corrosion. 

It is available from the Compressed Gas Association, Inc., visit 

www.cganet.com.

RESPONSIBILITY

The owner or occupant of a property in which fire extin-

guishers are located has an obligation for the care and use of 

these extinguishers at all times. By doing so, he/she is contrib-

uting to the protection of life and property. The nameplates 

and instruction manual should be read and thoroughly under-

stood by all personnel who may be expected to operate, 

recharge, inspect or maintain the extinguishers.

!

  

WARNING

When performing recharge, use only those materials specified 

on the extinguisher nameplate. The use of other recharging 

materials may reduce the efficiency, cause malfunction, or 

result in rupture of the extinguisher that could cause injury to 

the operator.

INSPECTION

Inspection is a ‘‘quick-check’’ to give reasonable assurance 

an extinguisher is fully charged and operable. It includes 

checking that an extinguisher is in its designated location, that 

it has not been actuated or tampered with, and that there is 

no obvious physical damage or condition to prevent operation. 

The value of an inspection lies in the frequency, regularity, 

and thoroughness with which it is conducted. The frequency 

will vary from hourly to monthly, based on the needs of the 

situation.

MAINTENANCE

Extinguishers shall be maintained at regular intervals, not 

more than one year apart, or when specifically indicated by 

an inspection. Maintenance is a ‘‘thorough check’’ to give 

maximum assurance the extinguisher will operate effec-

tively and safely. It includes a thorough examination and any 

necessary repair, recharge, or replacement. It will normally 

reveal if there is a need for hydrostatic testing.

RECHARGE

All extinguishers shall be recharged immediately after use, or 

when indicated by an inspection or maintenance examination. 

Recharge is the replacement or replenishment of the 

suppressing agent.

HYDROTEST

Extinguishers shall be hydrostatically tested at regular 

intervals as required in the latest edition of NFPA 10, 

‘‘Standard for Portable Fire Extinguishers,’’ or more frequently 

when inspection or maintenance dictates a specific need. 

Such tests are usually required on extinguisher shells and 

some hose assemblies. For further details, see SENTRY/

CLEANGUARD Fire Extinguisher Hydrostatic Test Instructions 

(Form No. T-2017001).

!

  

WARNING

For safety: If, at any time, an extinguisher shows evidence of 

corrosion or mechanical injury, it shall be subjected to a hydro-

static pressure test or replaced.

!

  

WARNING

Do not use air or gas for pressure testing. Failure to comply 

could result in severe personal injury or death if the shell 

ruptures.

RECORD KEEPING

Each extinguisher shall have a tag or label securely attached 

that indicates the month and year the maintenance was 

performed and shall identify the person performing the service. 

The same record tag or label shall indicate if recharging was 

also performed. The tag shall not be placed on the front of 

the extinguisher where it could obscure operating instructions. 

At least monthly, the date the inspection was performed and 

the initials of the person performing the inspection shall be 

recorded.
In addition to the required tag or label, a permanent file 

record should be kept for each extinguisher. The file record 

should also include the maintenance date and the name of 

the person or agency performing the maintenance; the date 

when last recharged and the name of the person performing 

the hydrostatic test; and a description of dents remaining after 

passing a hydrostatic test.
Parts of the above taken from NFPA Pamphlet 10.

Содержание SENTRY CD05-1

Страница 1: ...AND RECHARGE MANUAL One Stanton Street Marinette WI 54143 2542 USA 1 715 735 7411 www ansul com 2018 Johnson Controls All rights reserved All specifications and other information shown were current as...

Страница 2: ......

Страница 3: ...re abused in service or are not properly maintained they may not perform reliably These extinguishers are pressure vessels that must be treated with respect and handled with care Only genuine SENTRY r...

Страница 4: ...NING Indicates a hazardous situation in which a person could experience serious personal injury or death if the situation is not avoided CAUTION Indicates a hazardous situation in which a person could...

Страница 5: ...guishers Operation Inspection Service and Maintenance and Recharge Manual Part No 429425 TABLE OF CONTENTS 2018 OCT 11 REV 05 PAGE TOC 1 SECTION PAGE Introduction 1 2 Operation 3 Inspection 5 Maintena...

Страница 6: ...SENTRY Carbon Dioxide Hand Portable Fire Extinguishers Operation Inspection Service and Maintenance and Recharge Manual Part No 429425 PAGE TOC 2 REV 05 2018 OCT 11 TABLE OF CONTENTS NOTES...

Страница 7: ...frequency will vary from hourly to monthly based on the needs of the situation MAINTENANCE Extinguishers shall be maintained at regular intervals not more than one year apart or when specifically ind...

Страница 8: ...REFERENCES REFERENCES IN THIS MANUAL AVAILABLE FROM NFPA 10 STANDARD FOR NFPA PORTABLE FIRE 1 Batterymarch Park EXTINGUISHERS Quincy MA 02169 7471 CGA C 1 METHODS FOR Compressed Gas HYDROSTATIC Assoc...

Страница 9: ...Stay well clear of flames From this position air currents help carry agent into fire assure maximum visibility provide protection from heat and lessen exposure to possible harmful vapors 4 Start back...

Страница 10: ...SENTRY Carbon Dioxide Hand Portable Fire Extinguishers Operation Inspection Service and Maintenance and Recharge Manual Part No 429425 PAGE 4 REV 05 2018 OCT 11 OPERATION NOTES...

Страница 11: ...d on the valve body and includes hose and horn assembly 4 Remove extinguisher from its wall hanger or bracket Examine extinguisher for evidence of physical damage corrosion or other impairments 5 Chec...

Страница 12: ...SENTRY Carbon Dioxide Hand Portable Fire Extinguishers Operation Inspection Service and Maintenance and Recharge Manual Part No 429425 PAGE 6 REV 05 2018 OCT 11 INSPECTION NOTES...

Страница 13: ...Extinguishers taken out of service for maintenance or recharge shall be replaced by spare extinguishers of the same type and at least equal rating 3 Clean extinguisher to remove dirt grease and forei...

Страница 14: ...04995 11 5 lb Extinguisher Only Assure nut attached to hex swivel rotates freely but not loosely 12 Check siphon tube by shaking entire extinguisher A metallic rattling noise indicates separation of s...

Страница 15: ...freezing if sprayed on bare skin or in the eyes NOTICE If charging multiple extinguishers keep the components for each extinguisher separate Valve assemblies and shells are not indexed and nameplates...

Страница 16: ...se spring clamp from operating lever when scale indicates correct amount of CO2 has been introduced into cylinder Close CO2 supply line valve and vent CO2 supply line to outside atmosphere 9 Install r...

Страница 17: ...p and gives sugges tions for corrective action For further information contact Johnson Controls WARNING Contents under high pressure Before removing or disassem bling valve make sure extinguisher is c...

Страница 18: ...ly Leak at cylinder valve joint Examine for cracks around perimeter of cylinder neck Discard if cracks are found If leaking at thread joint remove valve from cylinder Clean threads with stiff brush On...

Страница 19: ......

Страница 20: ......

Отзывы:

Похожие инструкции для SENTRY CD05-1