Smart Equipment Controls 

Installation, Operation and Maintenance Manual 

Form No. SECIOM.A 

Effective Date: 07/05/19 

Page 7 

states. The occupancy sensor can be 
a room occupancy sensor or another 
kind of occupancy detection (such as 
a duct pressure switch*). Without an 
occupancy sensor, the controller will 
always be in Occupied mode.  

occupancy sensor (wired to IN2 and 
ICOM2 on the controller) can be used 
to temporarily set the VAV box to 
Standby mode when occupancy is not 
sensed. 

*An optional factory provided occupancy pressure switch is available for standalone fan powered terminal units to
determine occupancy by measuring duct pressure to determine whether the air handler is on (zone is occupied) or off
(zone is unoccupied).

Control Sequences 

VAV boxes with Smart Equipment Controls will be factory mounted and wired according to the selected control sequence. 
Links to each individual control submittal are shown below: 

Table 2:    Control Sequences 

Smart Equipment Controls - Control Sequences

 

Description 

Single Duct 

Series Fan Powered  Parallel Fan Powered 

ZEC500  ZEC510 

ZEC500 

ZEC510 

ZEC500 

ZEC510 

Cooling Only 

6101 

7101 

6201 

7201 

6301 

7301 

1-Stage Electric Heat

6102 

7102 

6202 

7202 

6302 

7302 

2-Stage Electric Heat

6103 

7103 

6203 

7203 

6303 

7303 

3-Stage Electric Heat

6104 

7104 

6204 

7204 

6304 

7304 

Proportional Electric Heat 

6105 

7105 

6205 

7205 

6305 

7305 

On/Off Hot Water Heat 

6106 

7106 

6206 

7206 

6306 

7306 

Floating Hot Water Heat 

6107 

7107 

6207 

7207 

6307 

7307 

Proportional Hot Water Heat 

6108 

7108 

6208 

7208 

6308 

7308 

Supplemental Heat 

6109 

7109 

6209 

7209 

6309 

7309 

Controller Parameters 

Parameter Descriptions 

This section provides information on the SE-ZEC Controller Parameters. 

Static Parameters (All Applications) 

The list of available SE-ZEC Controller Parameters changes depending on the application type that is selected 
(Staged/Incremental/SCR). Table 2 shows the SE-ZEC Controller parameters that are available for every application 
(Staged/Incremental/SCR).  

Table 3:    Default SE-ZEC Controller Parameters 

Menu 1 

Menu 2 

Parameter Name  Parameter Description 

Parameter Values 

Home Page 

Setup 

Active Baud Rate 

Displays the active baud rate used for network 
communication. 

Read Only 

Содержание SE-ZEC500-1

Страница 1: ...ls Installation Operation and Maintenance Manual Form No SECIOM A Effective Date 07 05 19 Page 1 Smart Equipment Controls Installation Operation and Maintenance Manual Johnson Controls SE ZEC500 1 and SE ZEC510 1 Controllers ...

Страница 2: ...ancy Sensor 6 Control Sequences 7 Controller Parameters 7 Parameter Descriptions 7 Static Parameters All Applications 7 Application Specific Parameters 11 Factory Programmed Parameters 12 Default Parameters 12 Size Dependent Parameters 13 Sequence Dependent Parameters 14 Commissioning 16 Mobile Access Portal MAP Gateway 16 VAV Handheld Balancing Tool 17 Troubleshooting 17 Power Status LED 18 Commu...

Страница 3: ...drilling 10 screw through the captive spacer with a power screwdriver and 4 100 mm extension socket Otherwise use a punch to mark the position of the shoulder washer and then drill a hole into the VAV box using a 5 16 drill bit Insert the mounting screw and tighten against the spacer 7 Locate the damper position using the typical marking on the end of the damper shaft 8 Note the direction clockwis...

Страница 4: ...ise address DIP switch block at the top of the controller Device addresses 4 127 are the valid addresses for the SE ZEC controller SE ZEC Controllers ship with all address switches set to ON Set a valid and unique device address on the field controller before applying power to the controller on the Bus The DIP switch block has eight switches numbered 128 64 32 16 8 4 2 and 1 To set the device addr...

Страница 5: ...e is wired between terminals ICOM3 and IN3 on the SE ZEC Controller The sensor should be mounted in the inlet duct centered in the side of the ductwork Avoid installing the sensor near an elbow take off or transition Avoid blocking air to the primary airflow sensor Factory provided nickel 1k ohm temperature sensors have 4 long probes and stainless steel mounting flanges with 2 provided hex head se...

Страница 6: ... 66 F and Standby Cooling 77 F temperature setpoints as well as Unoccupied Heating and Unoccupied Cooling Airflow setpoints o For Series Fan Powered Terminals the Fan is always on o For Parallel Fan Powered Terminals the Fan is only on during a call for heating Unoccupied Mode o Uses Unoccupied Heating 55 F and Unoccupied Cooling 85 F temperature setpoints as well as Unoccupied Heating and Unoccup...

Страница 7: ...scription Single Duct Series Fan Powered Parallel Fan Powered ZEC500 ZEC510 ZEC500 ZEC510 ZEC500 ZEC510 Cooling Only 6101 7101 6201 7201 6301 7301 1 Stage Electric Heat 6102 7102 6202 7202 6302 7302 2 Stage Electric Heat 6103 7103 6203 7203 6303 7303 3 Stage Electric Heat 6104 7104 6204 7204 6304 7304 Proportional Electric Heat 6105 7105 6205 7205 6305 7305 On Off Hot Water Heat 6106 7106 6206 720...

Страница 8: ... CCW to close Reverse CW to close Adjustable Normal Reverse Home Page Setup Discharge Air Temperature Offset Used to calibrate the supply air temperature sensor Adjustable 5 F to 5 F Home Page Setup Fan Control Type Set the type of fan for the VAV Box Adjustable None Parallel Series Home Page Setup Heating Limit Enable Enables Disables the activation of re heat when the incoming air temperature ex...

Страница 9: ...This mode is intended to allow the controller to utilize unoccupied setpoints when there is no connection to a building automation system When Standalone Mode is enabled occupancy is determined by comparing the measured flow against the Occupancy Determination Flow Setpoint when Occupancy Sensor Enable if False or by using the Occupancy Sensor when Occupancy Sensor Enable is True Adjustable Off On...

Страница 10: ... Cooling Setpoint Defaults to 60 F Adjustable 45 F to 98 F Home Page Setpoints Warmer Cooler Adjust Range This is the range that the warmer cooler adjustment on the sensor can affect the setpoint Setting it to zero 0 means the user has no adjustment at the sensor Defaults to 5 F Adjustable 0 F to 5 F Home Page Setpoints Warmup Differential Sets the required differential between the supply air temp...

Страница 11: ...isplays temperature measured at zone sensor Ready Only Outputs Supply Air Damper Output Displays damper position 0 Fully Closed 100 Fully Open Read Only Outputs Supply Fan Command Displays fan status Read Only Parameters Factory Use Only Application Specific Parameters Table 3 below shows application specific parameters for the staged incremental and SCR applications Table 4 Application Specific S...

Страница 12: ...at Read Only Outputs Heating Output Displays the heat command 0 100 of the heat output to the proportional actuator or electric heat Read Only Outputs Heating Stage 1 Command Displays status of stage 1 heat Read Only Outputs Heating Stage 2 Command Displays status of stage 2 heat Read Only Outputs Heating Stage 3 Command Displays status of stage 3 heat Read Only Outputs Supplemental Heating Output...

Страница 13: ...196 0 267 0 349 0 442 0 545 0 785 1 069 1 396 0 738 2 667 Supply Airflow Pickup Gain 2 329 2 327 2 332 2 325 2 329 2 327 2 327 2 327 2 328 2 328 1 982 2 328 Cooling Maximum Flow Per Order Per Order Per Order Per Order Per Order Per Order Per Order Per Order Per Order Per Order Per Order Per Order Occupied Cooling Min Flow Per Order Per Order Per Order Per Order Per Order Per Order Per Order Per Or...

Страница 14: ...l Normal Normal Normal Normal Supplemental Heating Installed FALSE FALSE FALSE FALSE FALSE FALSE TRUE Box Heating Installed FALSE TRUE TRUE TRUE TRUE TRUE FALSE Box Heating Stroke Time N A N A N A N A N A 60 N A Box Heating Polarity N A N A N A N A N A Normal N A Staged Device Min Flow Per Size Table Per Size Table Per Size Table Per Size Table Per Size Table N A Per Size Table Occupancy Determina...

Страница 15: ...etpoint 0 0 0 0 0 0 0 Occupancy Polarity Close Close Close Close Close Close Close Occupancy Sensor Enable TRUE TRUE TRUE TRUE TRUE TRUE TRUE Standalone Mode TRUE FALSE TRUE FALSE TRUE FALSE TRUE FALSE TRUE FALSE TRUE FALSE TRUE FALSE TRUE FALSE TRUE FALSE Control Code 6301 7301 6302 7302 6306 7306 6303 7303 6304 7304 6305 7305 6308 7308 6307 7307 6309 7309 Heating Type Cooling Only Staged Staged ...

Страница 16: ... a browser A mobile application is not required to use the MAP Gateway with your mobile device The MAP Gateway can be used to see field bus devices on Metasys systems Facility Explorer systems and Smart Equipment rooftop units RTUs with unit control boards UCBs The MAP Gateway supports Johnson Controls branded Field Controllers including FEC FAC VMA PCA PCG and PCV Series devices MAP Gateway also ...

Страница 17: ...n Instructions LIT 24 10737 8 Catalog Page LIT 1900869 User s Guide LIT 12011999 Product Bulletin LIT 12011884 Technical Bulletin LIT 12012015 VAV Handheld Balancing Tool A Handheld Balancing Tool Part 15037701 can be used to aid in balancing units with SE ZEC Controllers 1 Connect the VAV Balancing Tool to the Network Zone Sensor associated with the controller you want to balance 2 Press and hold...

Страница 18: ...on problems and check if device address remains online at the MAP Gateway to determine if the device address remains online If the Bus communication problems are severe and no communication is present or you cannot determine where communication is unreliable partition disconnect and isolate a portion of the Bus for testing purposes and test the Bus portion connected to the Zone Coordinator Correct...

Страница 19: ...24 10143 01493 for more information on the SE ZEC Controllers Refer to Johnson Controls LIT 1900217 for more information on the TE 631GV 2 supply air or discharge air temperature sensors Refer to Johnson Controls LIT 1901099 for more information on NS8000 Series Network Sensors Refer to Johnson Controls LIT 12012362 for more information on networking the SE ZEC Controllers ...

Отзывы: