Engineering manual - SAB 193-233-283 S A-frame (including ATEX)
90/168
008831 en 2020.10
6.4
Minimum compressor flow at 3550 rpm
The minimum flow capacity for each compressor varies depending on its geometry and its operat-
ing conditions. Typical minimum flow for each of our compressor models is listed below. Table 22
represents minimum suction flow with the slide valve fully unloaded.
Unit
Minimum flow*
CFM
m
3
/h
SAB 193 S
71
121
SAB 193 L
95
161
SAB 233 S
125
212
SAB 233 L
157
267
SAB 233 E
365
621
SAB 283 S
224
380
SAB 283 L
282
479
SAB 283 E
650
1104
SAB 283 X
478
812
Table 22: Minimum suction flow
* at 3550 rpm
Содержание Sabroe SAB 193 L
Страница 1: ...SAB 193 233 283 S A frame including ATEX Screw compressor units Engineering manual en ...
Страница 2: ......
Страница 169: ......