Operating manual - HeatPAC with reciprocating compressor
46/62
009332 en 2021.07
6. Maintenance instructions
6.1
Maintenance of heat pump units
Read chapter
carefully before performing any maintenance on the heat pump unit.
To ensure that the heat pump unit operates without problems throughout a long service life, the system
of maintenance presented in the following instructions must be followed.
Daily maintenance is normally performed by operating personnel. Other maintenance and service tasks,
which require the refrigeration system to be opened, must be performed by competent personnel.
Maintenance can be divided into:
1.
Daily maintenance
(minimum twice a week)
Daily maintenance consists of visual inspections.
•
Inspect the heat pump unit, and check that both noise and vibrations are normal.
•
To observe trends, it is recommended to enter the observed operating data into a log-
book, see subsection
. Check that all operating values are
within the permissible ranges. Compare them with previous values to detect trends.
•
Check the oil level.
•
Check the refrigerant charge.
•
Observe for leaks of refrigerant (smell of ammonia), oil, glycol or water.
•
Check mechanical seal oil draining bottle.
•
Check the control system for alarms/shutdowns.
2.
Half yearly/yearly/major maintenance
•
Normally, only the compressor needs to be maintained. However, it is recommended to
check that the heat pump is running properly: check for fouling of heat exchangers, dirt
in filters, etc.
Maintenance intervals are described in detail in the compressor manual.