5.3.4
Restarting the heat pump after power interruption
When the power supply returns after a short power interruption, restarting depends on the UniSAB III
settings.
If UniSAB III is set in AUTO running mode, the heat pump will normally start up when needed by the au-
tomatic control and when the relevant timer/delay has expired.
If UniSAB III is set in MANUAL running mode, the operator must start up using the manual start key on
UniSAB III.
1.
Check variable set points
2.
UniSAB III should display: READY
3.
Follow the normal start-up procedure
Note:
A long stop requires a long-term stop procedure as described in the following.
5.3.5
Restarting the heat pump after alarm stop (shutdown)
1.
Check and correct the cause of the alarm.
2.
Reset the alarm.
3.
UniSAB III should display: READY.
4.
Follow the normal start-up procedure.
5.4
During operation
5.4.1
Checks to be performed during operation
1.
Choose a suitable picture from the UniSAB III display to view the data to be checked.
2.
Check that oil pressure is obtained and that the evaporating and condensing pressures are with-
in the permissible ranges.
3.
Check the other operating data.
4.
Check for abnormal noise and vibrations.
5.
Check the oil and refrigerant level.
6.
Make sure the heat pump is operating stably - not fluctuating.
5.4.2
Monitoring and logging of operation
It is recommended that the plant and the heat pump unit are monitored by a competent person at regular
intervals. The monitoring method and the interval may depend on local and national legislation.
Operating log
To ensure satisfactory operation, it is required that you enter certain routines in a logbook on a regular
basis. Please see subsection
for more details.
5.5
Stopping procedures
5.5.1
Stopping for a brief period
In automatic mode UniSAB III will occasionally stop the heat pump unit depending on the cooling re-
quirement. This is normal and does not require any action by the operator of the plant.
The heat pump unit can be stopped manually on UniSAB III at any capacity setting. However, under nor-
mal conditions it is recommended to reduce capacity to a minimum before stopping the compressor.