background image

FANs 125, 121

Product/Technical Bulletin

RLD-H10G

Issue Date

0396

© 1996 Johnson Controls, Inc.

1

Part No. 24-7929-39, Rev. A
Code No. LIT-125602

The RLD-H10G is a professional grade leak detector
for use by refrigeration and air conditioning
technicians.  This detector senses all CFC, HCFC, and
HFC refrigerants and blends, such as R12, R502, R22,
R404a, R507, and R134a, among others.  The
RLD-H10G plugs into a 120 VAC outlet.  A full line of
accessories and maintenance kits is also available,
including replacement sensors, tune-up kits, probe
extensions, and leak vials.

Figure 1:  RLD-H10G Leak Detector

RLD-H10G Refrigerant Leak Detectors

Features and Benefits

Positive Ion Emission
Heated Diode Sensor

Provides the most sensitivity available today, while
still detecting all halogenated refrigerant gases

Halogen Selective Sensing

Eliminates many sources of possible false alarms
due to background contamination

High Quality Air Pump

Supplies constant air flow to sensor so it responds
quickly to leaks; also helps sensor recover quickly
after exposure to refrigerant so leak can be verified

Visual and Audible Signal

Facilitates sensing in noisy equipment rooms with
360° visibility and piercing tone;
Frequency of noise/light indicates magnitude of leak

Exceeds SAE J1627
Moving Probe Specification

Minimizes service time because the leak is found the
first time, is verifiable, and the fix can be confirmed

External Calibration Source

Indicates when the sensor is working properly and
serves as a reference point to judge leak size

Содержание RLD-H10G

Страница 1: ...mission Heated Diode Sensor Provides the most sensitivity available today while still detecting all halogenated refrigerant gases Halogen Selective Sensing Eliminates many sources of possible false alarms due to background contamination High Quality Air Pump Supplies constant air flow to sensor so it responds quickly to leaks also helps sensor recover quickly after exposure to refrigerant so leak ...

Страница 2: ...on technology which is based on the ionization characteristics of alkali metals The alkali metals act as the cathode of a diode and the anode is heated by a DC voltage Air from the area being leak checked is pumped from the probe and into the space between the cathode and anode If halogen gas is present it creates an ionized current between the cathode and the anode which is amplified to sound a s...

Страница 3: ...ch to on position See Figure 8 3 Slide range switch to small SM leak position See Figure 8 4 Check for sufficient airflow by pointing the probe tip toward the floor and observing the airflow ball in the probe See Figure 9 If the airflow is sufficient the ball will rise and float a small distance above the tip of the probe If the ball does not rise tap the probe lightly to make sure it is not stick...

Страница 4: ...nd to the leak vial make sure there is liquid in the bottle If the unit still does not respond to the leak increase the sensor heat slightly by turning the sensor heat control knob on the bottom of the unit 1 16th of a turn clockwise 5 Allow a minute for the sensor to heat then repeat the calibration procedure Tips for Finding Leaks Use the black rubber probe tip whenever possible and hold the pro...

Страница 5: ...emove the old airflow indicator ball 3 Insert the new airflow indicator ball into the probe 4 Reattach the probe end to the hose Figure 10 Replacing the Filter and Airflow Indicator Replacing the Sensor The sensor is a plug in unit that is thrown away when expended It needs replacement when the RLD H10G no longer responds to the leak vial even with the sensor heat control turned fully clockwise Ma...

Страница 6: ...r RLD H10 602R Heat control set too low Increase the sensor heat slightly by turning the sensor heat knob on the bottom of the unit 1 16th of a turn clockwise Allow a minute for the sensor to heat then repeat calibration Audio normal probe lamp does not flash Burned out or damaged probe lamp Return unit to your Johnson Controls PENN representative Responds continuously in all leak positions Dirt i...

Страница 7: ... Should it become necessary to repair your RLD H10G please contact your Johnson Controls PENN representative Warranty Repairs Units under warranty will be shipped to Johnson Controls PENN for repairs The repairs will be completed within 24 hours after receipt by the repair center and the unit will be returned to your Johnson Controls PENN representative at the same priority of shipment with which ...

Страница 8: ...racy Meets SAE J1627 test requirements Probe Length Approximately 4 5 ft 1 4 m Ambient Operating Conditions 32 to 113 F 0 to 45 C 5 90 RH non condensing Ambient Storage Conditions 14 to 140 F 10 to 60 C 5 90 RH non condensing Case Vinyl Dimensions H x W x D 2 8 x 8 8 x 5 0 in 71 x 224 x 127 mm Shipping Weight 3 2 lb 1 4 kg Agency Listings UL Listed File SA9717 The performance specifications are no...