2    RLD-H10G Product/Technical Bulletin

A

pplication Overview

Growing concern over the effects of certain
refrigerants on the atmosphere has generated a strong
motive to eliminate system leaks and to develop safer
refrigerants.  With the RLD-H10G, you can be
confident that your instrument will provide the
sensitivity and capabilities to meet your service needs
today and for the years to come.

The RLD-H10G is intended principally as a service
technician’s tool.  This detector has the capability to
detect small amounts of halogenated gases, including
chlorine and fluorine based refrigerants and blends.

T

heory of Operation

The leak detector consists of a control unit with a
manual balancing circuit, a probe with a 4.5 ft cable,
and a 6 ft power cord.  The sensor uses positive ion
emission technology, which is based on the ionization
characteristics of alkali metals.  The alkali metals act
as the cathode of a diode, and the anode is heated by
a DC voltage.  Air from the area being leak checked is
pumped from the probe and into the space between
the cathode and anode.  If halogen gas is present, it
creates an ionized current between the cathode and
the anode, which is amplified to sound a speaker and
light a neon lamp in the probe.  Sensitivity can be
controlled by adjusting the current (temperature)
through the sensor.

D

imensions

rld h1 0g

5 .0

1 27

2 .8

7 1

8.8

2 2 4

Figure 2:  RLD-H10G Dimensions (in/mm)

A

ccessories

Figure 3:  RLD-H10-100--14 in. Flexible Probe

Extension

Figure 4:  RLD-H10-600R--Tune-up Kit; includes

sensor, 100 filters, 4 airflow indicator balls,

3 rubber probe tips, and leak vial

Figure 5:  RLD-H10-601R--Replacement Sensor

Figure 6:  RLD-H10-602R--Maintenance Kit; includes

100 filters, 4 airflow indicator balls,

3 rubber probe tips

Figure 7:  RLD-H10-603R--Replacement Leak Vial

Содержание RLD-H10G

Страница 1: ...mission Heated Diode Sensor Provides the most sensitivity available today while still detecting all halogenated refrigerant gases Halogen Selective Sensing Eliminates many sources of possible false alarms due to background contamination High Quality Air Pump Supplies constant air flow to sensor so it responds quickly to leaks also helps sensor recover quickly after exposure to refrigerant so leak ...

Страница 2: ...on technology which is based on the ionization characteristics of alkali metals The alkali metals act as the cathode of a diode and the anode is heated by a DC voltage Air from the area being leak checked is pumped from the probe and into the space between the cathode and anode If halogen gas is present it creates an ionized current between the cathode and the anode which is amplified to sound a s...

Страница 3: ...ch to on position See Figure 8 3 Slide range switch to small SM leak position See Figure 8 4 Check for sufficient airflow by pointing the probe tip toward the floor and observing the airflow ball in the probe See Figure 9 If the airflow is sufficient the ball will rise and float a small distance above the tip of the probe If the ball does not rise tap the probe lightly to make sure it is not stick...

Страница 4: ...nd to the leak vial make sure there is liquid in the bottle If the unit still does not respond to the leak increase the sensor heat slightly by turning the sensor heat control knob on the bottom of the unit 1 16th of a turn clockwise 5 Allow a minute for the sensor to heat then repeat the calibration procedure Tips for Finding Leaks Use the black rubber probe tip whenever possible and hold the pro...

Страница 5: ...emove the old airflow indicator ball 3 Insert the new airflow indicator ball into the probe 4 Reattach the probe end to the hose Figure 10 Replacing the Filter and Airflow Indicator Replacing the Sensor The sensor is a plug in unit that is thrown away when expended It needs replacement when the RLD H10G no longer responds to the leak vial even with the sensor heat control turned fully clockwise Ma...

Страница 6: ...r RLD H10 602R Heat control set too low Increase the sensor heat slightly by turning the sensor heat knob on the bottom of the unit 1 16th of a turn clockwise Allow a minute for the sensor to heat then repeat calibration Audio normal probe lamp does not flash Burned out or damaged probe lamp Return unit to your Johnson Controls PENN representative Responds continuously in all leak positions Dirt i...

Страница 7: ... Should it become necessary to repair your RLD H10G please contact your Johnson Controls PENN representative Warranty Repairs Units under warranty will be shipped to Johnson Controls PENN for repairs The repairs will be completed within 24 hours after receipt by the repair center and the unit will be returned to your Johnson Controls PENN representative at the same priority of shipment with which ...

Страница 8: ...racy Meets SAE J1627 test requirements Probe Length Approximately 4 5 ft 1 4 m Ambient Operating Conditions 32 to 113 F 0 to 45 C 5 90 RH non condensing Ambient Storage Conditions 14 to 140 F 10 to 60 C 5 90 RH non condensing Case Vinyl Dimensions H x W x D 2 8 x 8 8 x 5 0 in 71 x 224 x 127 mm Shipping Weight 3 2 lb 1 4 kg Agency Listings UL Listed File SA9717 The performance specifications are no...