Johnson Controls PREMIUM EFFICIENCY VPCS Series Скачать руководство пользователя страница 42

42

FORM 145.18-IOM2 

ISSUE DATE: 06/17/2020

SECTION 2 - OPERATION

TABLE 8 -

 ECM BLOWER PERFORMANCE (CONT'D)

UNIT SIZE

MOT

OR 

SPEED

EXTERNAL

 

ST

ATIC 

OPTION

ECM T

AP#

RA

TED 

COOLING 

(CFM)

RA

TED 

HEA

TING 

(CFM)

EXTERNAL STATIC PRESSURE (IWG)

0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 0.6

30

OPTIONAL 

FAN ONLY

N/A

1

1075

1075

870 850 830 810 790 770 750 725 700 680 660

-

-

LOW

LOW

2

940 920 900 885 870 855 840 820 800 775 750

-

-

HIGH

3

1160 1125 1090 1075 1060 1050 1040 1035 1010 995 980 960 930

LOW

HIGH

4

1070 1055 1040 1020 1000 980 960 940 920 900 880 860 840

HIGH

5

1330 1315 1300 1285 1270 1250 1230 1205 1160 1130 1080 1070 1060

36

OPTIONAL 

FAN ONLY

N/A

1

1100

1250

870 850 830 810 790 770 750 725 700 680 660

-

-

LOW

LOW

2

1070 1055 1040 1020 1000 980 960 940 920 900 880

-

-

HIGH

3

1200 1185 1170 1155 1140 1120 1100 1085 1070 1055 1040 995 950

LOW

HIGH

4

1160 1125 1090 1075 1060 1050 1040 1035 1010 995 980 960 930

HIGH

5

1460 1430 1400 1370 1340 1295 1250 1210 1175 1145 1090 1080 1070

NOTES

All airflow ratings are at the lowest voltage rating of dual rating (for example, 208 volt). 
Airflow ratings include the resistance of wet coil and clean air filters.

UNIT CONTROLS

The control system microprocessor board is specifi-

cally designed for water source heat pump operation. 

The control system interfaces with a conventional type 

thermostat.

•  The unit is complete with a self-contained low-

voltage control circuit. 

•  The unit incorporates a lockout circuit that pro-

vides reset capability from a hard lockout at the 

space thermostat or base unit if any of the follow-

ing standard safety devices trip and shut off the 

compressor:

•  Low pressure limit switch (loss of charge)
•  High pressure limit switch 
•  Freeze protection switch (unit shutdown on 

low water temperature) 

•  Condensate overflow switch

•  The unit operates with conventional thermostat 

designs and has a low voltage terminal strip for 

easy hook-up. 

•  Unit control board has on-board diagnostics and 

fault code display. 

•  Standard controls include anti-short cycle and low 

voltage protection.

•  The control board monitors each refrigerant safe-

ty switch independently. 

•  The control board has a random start feature.
• 

The control board retains the last five fault codes 

in nonvolatile memory that cannot be lost in the 

event of a power loss.

Sequence of Operation

The room thermostat makes a circuit between R and Y 

for cooling.
The call passes to the unit microprocessor control that 

determines whether the requested operation is avail-

able and if so, which components to energize.
For heating, the room thermostat makes a circuit be-

tween R and W. The microprocessor control energizes 

the compressor and fan, enabling the unit to run in 

heating mode. 

Содержание PREMIUM EFFICIENCY VPCS Series

Страница 1: ...IUM EFFICIENCY VPCS SERIES VERTICAL STACKED WATER SOURCE HEAT PUMP CABINET MODEL VPB VPM VPS VPT09 36 AND CHASSIS MODEL VPCS09 36 INDOOR PACKAGED EQUIPMENT Installation Operation and Maintenance Super...

Страница 2: ...y with all applicable industry and governmental standards and regulations pertaining to the task in question SAFETY SYMBOLS The following symbols are used in this document to alert the reader to speci...

Страница 3: ...on the equipment ASSOCIATED LITERATURE MANUAL DESCRIPTION FORM NUMBER Vertical Stacked Heat Pump Start Up and Performance Checklist 145 18 CL1 Vertical Stacked Water Source Heat Pump Heating and Cool...

Страница 4: ...D K P V Z 80 inches with 8 inch Stand F 2 4 6 8 SUPPLY AIR CONFIGURATION 1H Single Horizontal Supply 2T Double Horizontal Supply Top 2H Double Horizontal Supply 3H Triple Horizontal Supply 3T Triple H...

Страница 5: ...M J 4 5 USGPM K 5 0 USGPM L 6 0 USGPM M 7 0 USGPM N 8 0 USGPM P 9 0 USGPM AIRSIDE OPTIONS A Standard Airside Coil C Dipped Electrofin Coating WATERSIDE OPTIONS C Standard Water Coil N Cupro Nickel Wat...

Страница 6: ...l 21 Supply Air SA Ductwork 25 Horizontal Supply Air 25 Top Discharge Supply Air 25 Top Mounted Fresh Air Intake 28 Top Mounted Fresh Air Intake with Motorized Damper 28 Removing the Actuator 28 Syste...

Страница 7: ...lied JIC Hose Kits and Risers 18 FIGURE 8 Optional Field Supplied Risers with Factory Supplied JIC Hose Kits and Shut Off Valves 18 FIGURE 9 Field Wiring Diagram 19 FIGURE 10 Remote Thermostat Wiring...

Страница 8: ...pply Face Velocity FPM 27 TABLE 7 Operating Limits 40 TABLE 8 EC Motor ECM Blower Performance 41 TABLE 9 Flash Codes 45 TABLE 10 Premium Series Pressure Drop 51 LIST OF FIGURES CONT D FIGURE 26 Tilt t...

Страница 9: ...ges may require that the NRTL or testing facility review and re approve the product by means of a field or site inspection and certification Modifications may invalidate product certifications or viol...

Страница 10: ...ify the model number on the unit nameplate with the ordering and shipping information to en sure the correct unit has been shipped Carefully inspect each unit before delivery to the installation site...

Страница 11: ...ER INSTALLATION Do NOT use the risers to lift or move the cabinets Refer to Figure 3 on page 14 which shows the correct location of the cabinet in relation to the floor sleeve and risers Risers are no...

Страница 12: ...ate drainage 6 When building construction codes or safety laws require securing the cabinets in order to prevent accidental tipping the field must order and install factory isolated anchor kits P N VB...

Страница 13: ...0 Compressor Type Rotary Scroll Refrigerant Charge oz 33 39 45 47 51 52 58 Air Coil Type Enhanced Copper Tubes Enhanced Aluminum Fins Face Area sq ft 1 83 1 83 2 72 2 72 3 14 3 38 3 38 Rows FPI 2 14...

Страница 14: ...PENING 8 50 A 2 36 CONDENSATE RISER OPENING VSHP Cabinet Drain Pan Do not penetrate this area with drills or screws 1 50 4 75 Top Supply Opening Optional 7 8 inch OD Control Entrance Front Supply Open...

Страница 15: ...y and Return Risers 36 inches 6 inches P Trap Allow for 2 inch Insertion into Swage End Supply and Return Riser Max 120 inches Condensate Riser Max 120 inches As Req d As Req d Reduce Up Riser Max 120...

Страница 16: ...are to be field sweat connected to risers see Figure 6 on page 17 and Figure 8 on page 18 HOSES Ensure the correct hose set is matched with the com patible unit size see Table 2 on page 16 Instal the...

Страница 17: ...TE National Pipe Straight Hose NPSH connection LD18126 Figure 5 STANDARD FACTORY SUPPLIED NPSH HOSE KITS AND RISERS LD18127 NOTE National Pipe Straight Hose NPSH connection 1 2 INCH MALE NPSH 1 2 INCH...

Страница 18: ...CONNECTION BALL VALVE LD19518 Figure 7 STANDARD FACTORY SUPPLIED JIC HOSE KITS AND RISERS LD19519 1 2 INCH OR 3 4 INCH JIC FLARE CONNECTION 1 2 INCH OR 3 4 INCH FLEXIBLE CONNECTOR HOSE 24 INCHES LONG...

Страница 19: ...ch power entrance knock out Connect to the line side of the factory installed termi nal block Unit terminals are not designed to accept other types of conductors Failure to use copper con ductors may...

Страница 20: ...ptional ADA Door Mounted Thermostat For units ordered with the Americans with Disabilities Act ADA thermostat option to meet ADA require ments the thermostat is located on the RA panel door at a heigh...

Страница 21: ...rain pan electrical box and discharge ple num after cutting out the supply returns openings To prevent electrical shorts and drain pan leaks DO NOT penetrate unit compo nents when driving screws near...

Страница 22: ...EL OPENING D ROUGH IN WIDTH E UNIT WIDTH F UNIT DEPTH G NO OA OPTION G OA OPTION NO DAMPER G OA OPTION WITH DAMPER 09 12 15 18 25 75 19 19 25 23 75 0 125 20 20 23 25 MIN 23 50 MAX 24 75 MIN 25 00 MAX...

Страница 23: ...D 52 50 Mounting Holes x 6 54 50 54 3 4 ROUGH IN WALL OPENING 50 25 Magnetic Catches x 2 1 2 Insulation 1 92 inches 0 28 inches B C Mounting Holes x 6 52 5 inches 56 75 inches D A 50 25 inches 54 5 i...

Страница 24: ...25 Thermostat mounting location Cut out for routing ADA thermostat harness LEFT HAND OPENING SHOWN 1 50 LD19320 NOTES 1 Powder coated in appliance white 2 Inside panel lined with 0 5 inch acoustical...

Страница 25: ...inch neoprene tape field supplied around the perimeter of the volume damper prior to inserting it into the supply opening See Figure 17 on page 25 for an example This assists in reducing noise transmi...

Страница 26: ...lled with Volume Damper Wall Stud Factory Supplied 1 inch Duct Flange Detail A Optional Framing Studs for Supply Opening 2 25 inch Minimum Unit Supply Duct Flange to 0 5 inch Drywall Face B C Vertical...

Страница 27: ...bined with any other discharge arrangement it is included in determining horizontal opening grille size 6 Openings marked Not Available result in face velocities outside the recommended 300 500 FPM ra...

Страница 28: ...ply plaster flange Top Mounted Fresh Air Intake with Motorized Damper This include the same features as the top mounted fresh air intake option with the addition of a motorized damp er assembly inside...

Страница 29: ...iser shut off valves are closed at each unit 2 Fill the water circulation system with clean wa ter from the make up water supply Ensure the air vents are open during initial filling Do not allow the s...

Страница 30: ...tem start up It is recommended that a professional wa ter treatment company perform ongoing maintenance of the water loop including chemical analysis and flushing if neces sary The water loop testing...

Страница 31: ...All Three Sides Front Supply Optional Optional 24V Molex Connection for Surface Mount Remote Mounted Thermostat Unit Switch Plate ADA Molex Connection Optional B CABINET DIMENSIONS INCHES MODEL A B C...

Страница 32: ...Entrance 7 8 inch Control Entrance Riser Opening All Three Sides 3 25 inches 4 inch Fresh Air Intake C Optional Top Supply 4 25 inches B A C A 61 875 inches 36 inches CABINET DIMENSIONS INCHES MODEL A...

Страница 33: ...either NPSH or JIC fittings Refer to Riser Loop on page 16 for more information For Units with NPSH and JIC Valve Connection and Hose Sets NPSH JIC flexible connection hoses do not re quire any pipe...

Страница 34: ...ssis with the opening of the cabinet Tilt the chassis sufficiently for the base of the chassis to clear the mounting rails on the cabinet drain pan see Figure 26 on page 34 4 Insert the chassis midway...

Страница 35: ...8 Without touching the flanges on either side en sure the chassis alignment in the cabinet is cen tered in the cabinet opening see Figure 30 on page 35 9 Complete the electrical connections to the ch...

Страница 36: ...ge control wiring correct per the unit wir ing diagram C PHYSICAL INSPECTION Removed the inner service panel and manually checked the blower wheel for free rotation Removed the chassis refrigeration a...

Страница 37: ..._______________________VOLTS B AIRSIDE NOTE CFM measurements should be within the param eters listed in the associated tables in the IOM HEATING COOLING Coil Inlet Dry Bulb F F Coil Outlet Dry Bulb F...

Страница 38: ...38 FORM 145 18 IOM2 ISSUE DATE 06 17 2020 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 39: ...rain riser and the drain pan stub INITIAL UNIT START UP During installation testing servicing and troubleshooting of this product it may be necessary to work with live electri cal components Failure t...

Страница 40: ...T 50 0 F 30 0 F 50 0 F 20 0 F MAXIMUM EWT 110 0 F 90 0 F NOTE Geothermal operation antifreeze mixture FAN SPEED ADJUSTMENT Multi speed EC motors ECMs are used in all units as standard ECMs have five s...

Страница 41: ...95 380 360 HIGH 5 590 570 550 535 525 510 490 470 450 430 405 380 350 15 OPTIONAL FAN ONLY N A 1 520 580 415 405 395 350 320 275 245 LOW LOW 2 480 460 440 415 390 370 350 HIGH 3 570 545 520 505 490 47...

Страница 42: ...r source heat pump operation The control system interfaces with a conventional type thermostat The unit is complete with a self contained low voltage control circuit The unit incorporates a lockout ci...

Страница 43: ...or AUTO The lockout circuit can also be reset by opening and closing the unit mounted disconnect switch If the unit must be reset more than twice on consecutive operating cycles check the unit for a d...

Страница 44: ...s at 37 0 F and resets at 49 0 F 2 A high pressure limit switch to protect against ex cessive discharge pressures opens at 625 psig 25 psig 3 A low pressure limit switch to protect against loss of ref...

Страница 45: ...d on the microprocessor control LED Last Error When this button is pressed and released one time within 5 seconds it flashes the last five fault codes on the board s LED The most recent alarm is shown...

Страница 46: ...46 FORM 145 18 IOM2 ISSUE DATE 06 17 2020 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 47: ...ew odors 4 Annually check the fan motor and blower assem bly All units employ permanently lubricated fan motors DO NOT OIL FAN MOTORS Vacuum any accumulation of dirt from the motor ventila tion slots...

Страница 48: ...48 FORM 145 18 IOM2 ISSUE DATE 06 17 2020 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 49: ...49 Appendix FORM 145 18 IOM2 ISSUE DATE 06 17 2020 A VPB SERIES WIRING DIAGRAMS APPENDIX Figure 31 EC MOTOR ECM 2 SPEED FAN WIRING DIAGRAM LD27623...

Страница 50: ...50 FORM 145 18 IOM2 ISSUE DATE 06 17 2020 Appendix Figure 32 EC MOTOR ECM 3 SPEED FAN WIRING DIAGRAM LD28382...

Страница 51: ...0 1 6 1 2 0 7 2 8 4 4 4 0 3 6 3 1 2 7 3 8 6 8 6 4 6 0 5 6 5 1 VPCS15 2 5 3 4 3 1 2 8 2 4 2 1 3 8 6 9 6 3 5 6 5 0 4 3 5 11 1 10 1 9 0 8 0 6 9 VPCS18 3 4 4 6 4 2 3 9 3 5 3 1 5 13 2 12 1 11 0 9 9 8 8 6...

Страница 52: ...IT HAVE AN INTERNAL PUMP YES NO ____ SUPPLY AIRFLOW MEASUREMENT CFM _________ Please attach a sketch of the duct s run with this form when returned to the Applied Ducted Systems PTS team JOB _________...

Страница 53: ...e Coaxial Coil Reversing Valve Internal Pump Voltage L1 L2 Internal Pump Amp Draw L1 L2 If installed Fan Amp Draw L1 L2 May only need L1 and L2 lines L3 Fan Voltage L1 L2 L3 Fan Motor Speed F Liquid L...

Страница 54: ...ompressor is not covered by this warranty LABOR AND COST NOT COVERED This Limited Warranty provides only replacement parts or credits and does not provide for or cover any labor shipping handling or o...

Страница 55: ...at least 700 psig high side and 180 psig low side with a 550 psig retard All hoses must have a service pressure rating of 800 psig Leak detectors must be designed to detect HFC refrigerants Systems m...

Страница 56: ...2020 Johnson Controls 100 JCI Way York Pennsylvania USA 17406 8469 www johnsoncontrols com Subject to change without notice Form 145 18 IOM2 620 Supersedes 145 18 IOM2 719 All rights reserved...

Отзывы: