NS8000 Series

Technical specifications

Supply voltage

9.8 VDC to 16.5 VDC; 15 VDC nominal (from SA bus)

Current consumption

Base current draw (all models)

3 mA maximum (non-transmitting)

CO

2

 models

25 mA maximum additional current (during measurement)

Display models - backlight on

30 mA additional current

Note:

 SA bus applications are limited to a power load of 210 mA. The best practice when configuring 

an SA bus is to limit the total available operating power consumption to 120 mA or less. This power 

level allows you to connect a BTCVT Wireless Commissioning Converter temporarily or a DIS1710 

Local Controller Display to the bus for commissioning, adjusting, and monitoring.

Terminations

Modular jack and

 

screw terminal block

Network sensor addressing All models

DIP switch set from 199 to 206; factory set at 199

Wire size

Modular jack models

24 AWG or 26 AWG (0.5 mm or 0.4 mm diameter); three twisted 

pair (six conductors)

Screw terminal block models

18 AWG to 22 AWG (1 mm to 0.6 mm diameter); 22 AWG

(0.6 mm diameter)

Communication rate

Auto-detect: 9.6 kbps, 19.2 kbps, 38.4 kbps, or 76.8 kbps

Temperature measurement range

32.0°F/0°C to 104°F/40°C

Temperature sensor type

Digital temperature sensor

Humidity sensor type

Thin film capacitive sensor

Ambient conditions

Operating

32°F to 122°F (0°C to 50°C); 10% to 90% RH, noncondensing; 

85°F (29°C) maximum dew point

Storage Display models

-40°F to 122°F (-40°C to 50°C); 5% to 95% RH, noncondensing

Non-display models

-40°F to 185°F (-40°C to 70°C); 5% to 95% RH, noncondensing

Temperature resolution

±0.5°F/±0.5°C

Temperature accuracy

NS Series Network Zone 

Sensor

±1°F/±0.6°C

Temperature element only

±0.36°F/±0.2°C at 70°F/21°C

Humidity element accuracy NSB8BPN24x-0 models

±2% RH for 20% to 80% RH at 50°F to 95°F (10°C to 35°C)
±4% RH for 10% to 20% and 80% to 90% RH at 50°F to 95°F 

(10°C to 35°C)

NSB8BHxxxx-0 models

±3% RH for 20% to 80% RH at 50°F to 95°F (10°C to 35°C)
±6% RH for 10% to 20% and 80% to 90% RH at 50°F to 95°F 

(10°C to 35°C)

CO

2

 sensor accuracy

Accuracy

±30 ppm ±3% of CO

2

 reading at 77°F (25°C) and 978 hPa

(1,000 ft/300 m)

Temperature dependence

±1.4 ppm/°F (± 2.5 ppm/°C)

Pressure dependence

See Table 3 for CO

2

 altitude compensation.

Time constant

10 minutes nominal at 10 fpm airflow

Default temperature setpoint adjustment range

50°F/10°C to 86°F/30°C in 0.5° increments

CO

2

 sensor

Operating

32°F to 122°F (0°C to 50°C)

Compliance

United States

UL Listed, File E107041, CCN PAZX,

Under UL 60730-1, Energy Management Equipment
FCC Compliant to CFR 47, Part 15, Subpart B, Class B

Canada

cUL Listed, File E107041, CCN PAZX7,

Under CAN/CSA E60730-1, Signal Equipment
Industry Canada, ICES-003

Europe

CE Mark – Johnson Controls declares that this product is in 

compliance with the essential requirements and other relevant 

provisions of the EMC Directive and RoHS Directive.

Australia and New Zealand

RCM Mark, Australia/NZ Emissions Compliant

China

RoHS2

Содержание NS Series

Страница 1: ...mpliance United States This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and us...

Страница 2: ...ence Height requirements may vary depending on the site Network sensors without CO2 sensing are shock and vibration resistant but not shock and vibration proof Be careful not to drop the unit or mount it where it could be exposed to excessive vibration Dropping a CO2 network sensor may result in readings outside of the specified accuracy tolerance Special tools only one type needed Johnson Control...

Страница 3: ...dhere to these wiring details causes the network sensor to function incorrectly You will not be able to connect to the system using the Bluetooth Wireless Comissioning Converter BTCVT Mobile Access Portal Gateway MAP or the handheld VAV balancing tool and you will not be able to expand the system with future offerings Notes IMPORTANT Do not connect the SA bus ground the modular phone jack GND or t...

Страница 4: ...Part No 24 11256 00007 Rev 4 NS8000 Series 5 2 1 4 15 VDC COM 15 VDC 1 2 5 6 4 3 COM SA SA SA SA COM 15 VDC 3 ...

Страница 5: ...r icon 6 Fahrenheit icon 7 Celsius icon 8 Percent relative humidity icon 9 Fan speed bars 10 Fan icon 11 Automatic fan speed icon 12 Up adjustment or navigation icon 13 SA bus online indicator 14 Down adjustment or navigation icon 15 Menu or enter icon 16 Occupancy indicator 17 Default display value setpoint zone temperature relative humidity 1 2 3 4 5 6 7 8 11 12 13 14 15 16 17 9 10 Table 1 Displ...

Страница 6: ...he home screen complete the following steps 1 Press and hold the Up and Down icons for five seconds until the Fahrenheit and Celsius indicator icons start to blink All icons are visible on the display 2 Press the Menu icon once 3 To select and switch between current temperature or setpoint value press the Up or Down icon 4 To save the new settings press the Menu icon five times to return to the ho...

Страница 7: ... it is the proper field to enter the hPa value found in Table 3 Refer to the Controller Tool Help LIT 12011147 for more details Note Enter the pressure value only in units of hPa The sensor reads the value entered as hPa The CO2 present value may require several minutes to settle after changing the offset value See Table 3 for local altitude values Network sensor addressing Table 2 Network sensor ...

Страница 8: ...earest customer service center or Johnson Controls representative Altitude above sea level Absolute pressure Feet Meters hPa 656 200 1 038 0 0 1 013 656 200 989 1 312 400 966 1 969 600 943 2 625 800 921 3 281 1 000 899 3 937 1 200 877 4 593 1 400 856 5 249 1 600 835 5 906 1 800 815 6 562 2 000 795 7 218 2 200 775 7 874 2 400 756 8 530 2 600 738 9 186 2 800 719 9 843 3 000 701 Table 3 CO2 altitude ...

Страница 9: ...H noncondensing 85 F 29 C maximum dew point Storage Display models 40 F to 122 F 40 C to 50 C 5 to 95 RH noncondensing Non display models 40 F to 185 F 40 C to 70 C 5 to 95 RH noncondensing Temperature resolution 0 5 F 0 5 C Temperature accuracy NS Series Network Zone Sensor 1 F 0 6 C Temperature element only 0 36 F 0 2 C at 70 F 21 C Humidity element accuracy NSB8BPN24x 0 models 2 RH for 20 to 80...

Страница 10: ...ulse voltage 330 V External power supply Intended for connection to Johnson Controls field controllers supporting the standard JCI SA Bus implementation CO2 sensor information The Model NSx8 Series Wall Mount sensors sense in part CO2 This functionality is intended to provide an input to equipment under normal operating conditions Where failure or malfunction of the transmitter could lead to perso...

Отзывы: