Setup and adjustments

Adjusting the temperature setpoint

1.  To view the current setpoint value, press the 

Up

 or 

Down 

icon once.

2.  To increase or decrease the temperature setpoint by 0.5 degrees Fahrenheit or Celsius, press the 

Up

 or 

Down 

icon again.

3.  To save the new settings, press the 

Menu 

icon once to return to the home screen or wait for ten seconds for the screen to 

return to the home screen automatically.

4. 

Optional: 

Press and hold the 

Up

 or 

Down

 icon to continuously increase or decrease the temperature setpoint.

Adjusting the fan speed

1.  To view the current fan speed, press the 

Fan

 icon once.

2.  To adjust the fan speed, continue to press the 

Fan

 icon to cycle through the automtic, off, low, medium or

high fan speed settings.

3.  To save the new settings, press the 

Menu 

icon once to return to the home screen or wait for ten seconds for the screen to 

return to the home screen automatically.

Viewing the SA bus sensor address and the firmware version

1.  Press the 

Menu

 icon once to view the SA bus sensor address. See Table 2 for setting the SA bus sensor address

2.  Press the 

Menu

 icon a second time to view the firmware version.

3.  Press the 

Menu

 icon a third time to return to the home screen or wait for ten seconds for the screen to return to the

home screen automatically.

Adjusting the temperature unit

To change the temperature units from Fahrenheit to Celsius or Celsius to Fahrenheit, complete the following steps:

1.  On the home screen, press and hold the 

Up

 and 

Down

 icons for five seconds until the middle display disappears and the 

Celsius and Fahrenheit indicator icons blink.

2.  To toggle between Fahrenheit and Celsius, press the 

Up

 or 

Down

 icon.

3.  To save the new settings, press the 

Menu 

icon six times to return to the home screen or wait for ten seconds for the screen to 

return to the home screen automatically.

Changing the home screen default value

Choose whether you want to display current temperature or the setpoint value in the middle of the home screen. To change which 

value displays in the middle of the home screen, complete the following steps:

1.  Press and hold the 

Up

 and 

Down

 icons for five seconds until the Fahrenheit and Celsius indicator icons start to blink. All icons 

are visible on the display.      

2.  Press the 

Menu

 icon once.

3.  To select and switch between current temperature or setpoint value, press the 

Up

 or 

Down

 icon.

4.  To save the new settings, press the 

Menu 

icon five times to return to the home screen or wait for ten seconds for the screen to 

return to the home screen automatically.

Selecting the setpoint display value

To change whether current or setpoint temperature displays in the upper-right corner, complete the following steps:

1.  Press and hold the 

Up

 and 

Down

 icons for five seconds until the Fahrenheit and Celsius indicator icons start to blink.

2.  Press the 

Menu 

icon twice.

3.  To select and switch between current temperature or setpoint value, press the 

Up

 or 

Down

 icon.

4.  To save the new settings, press the 

Menu 

icon four times to return to the home screen or wait for ten seconds for the screen to 

return to the home screen automatically.

Selecting the maximum fan speed settings

The fan speed is set to high speed by default. To change the value of the maximum fan speed that displays on the home screen, 

complete the following steps:

1.  Press and hold the 

Up

 and 

Down

 icons for five seconds until the Fahrenheit and Celsius indicator icons start to blink.

2.  Press the 

Menu 

icon three times.

3.  To increase or decrease the maximum fan speed, press the 

Up

 or 

Down

 icon.

4.  To save the new settings, press the 

Menu 

icon three times to return to the home screen or wait for ten seconds for the screen 

to return to the home screen automatically.

Changing the decimal separator

1.  Press and hold the 

Up

 and 

Down

 icons for five seconds until the Fahrenheit and Celsius indicator icons start to blink.

2.  Press the 

Menu 

icon four times.

3.  To switch between decimal point or decimal comma, press the 

Up

 or 

Down

 icon.

4.  To save the new settings, press the 

Menu 

icon twice to return to the home screen or wait for ten seconds for the screen to 

return to the home screen automatically.

Notes: 

• 

To activate the home screen when the backlight is off, touch the screen to turn the backlight back on for ten seconds.

• 

All icons are visible on the home screen during configuration.

Содержание NS Series

Страница 1: ...mpliance United States This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and us...

Страница 2: ...ence Height requirements may vary depending on the site Network sensors without CO2 sensing are shock and vibration resistant but not shock and vibration proof Be careful not to drop the unit or mount it where it could be exposed to excessive vibration Dropping a CO2 network sensor may result in readings outside of the specified accuracy tolerance Special tools only one type needed Johnson Control...

Страница 3: ...dhere to these wiring details causes the network sensor to function incorrectly You will not be able to connect to the system using the Bluetooth Wireless Comissioning Converter BTCVT Mobile Access Portal Gateway MAP or the handheld VAV balancing tool and you will not be able to expand the system with future offerings Notes IMPORTANT Do not connect the SA bus ground the modular phone jack GND or t...

Страница 4: ...Part No 24 11256 00007 Rev 4 NS8000 Series 5 2 1 4 15 VDC COM 15 VDC 1 2 5 6 4 3 COM SA SA SA SA COM 15 VDC 3 ...

Страница 5: ...r icon 6 Fahrenheit icon 7 Celsius icon 8 Percent relative humidity icon 9 Fan speed bars 10 Fan icon 11 Automatic fan speed icon 12 Up adjustment or navigation icon 13 SA bus online indicator 14 Down adjustment or navigation icon 15 Menu or enter icon 16 Occupancy indicator 17 Default display value setpoint zone temperature relative humidity 1 2 3 4 5 6 7 8 11 12 13 14 15 16 17 9 10 Table 1 Displ...

Страница 6: ...he home screen complete the following steps 1 Press and hold the Up and Down icons for five seconds until the Fahrenheit and Celsius indicator icons start to blink All icons are visible on the display 2 Press the Menu icon once 3 To select and switch between current temperature or setpoint value press the Up or Down icon 4 To save the new settings press the Menu icon five times to return to the ho...

Страница 7: ... it is the proper field to enter the hPa value found in Table 3 Refer to the Controller Tool Help LIT 12011147 for more details Note Enter the pressure value only in units of hPa The sensor reads the value entered as hPa The CO2 present value may require several minutes to settle after changing the offset value See Table 3 for local altitude values Network sensor addressing Table 2 Network sensor ...

Страница 8: ...earest customer service center or Johnson Controls representative Altitude above sea level Absolute pressure Feet Meters hPa 656 200 1 038 0 0 1 013 656 200 989 1 312 400 966 1 969 600 943 2 625 800 921 3 281 1 000 899 3 937 1 200 877 4 593 1 400 856 5 249 1 600 835 5 906 1 800 815 6 562 2 000 795 7 218 2 200 775 7 874 2 400 756 8 530 2 600 738 9 186 2 800 719 9 843 3 000 701 Table 3 CO2 altitude ...

Страница 9: ...H noncondensing 85 F 29 C maximum dew point Storage Display models 40 F to 122 F 40 C to 50 C 5 to 95 RH noncondensing Non display models 40 F to 185 F 40 C to 70 C 5 to 95 RH noncondensing Temperature resolution 0 5 F 0 5 C Temperature accuracy NS Series Network Zone Sensor 1 F 0 6 C Temperature element only 0 36 F 0 2 C at 70 F 21 C Humidity element accuracy NSB8BPN24x 0 models 2 RH for 20 to 80...

Страница 10: ...ulse voltage 330 V External power supply Intended for connection to Johnson Controls field controllers supporting the standard JCI SA Bus implementation CO2 sensor information The Model NSx8 Series Wall Mount sensors sense in part CO2 This functionality is intended to provide an input to equipment under normal operating conditions Where failure or malfunction of the transmitter could lead to perso...

Отзывы: