background image

Part No. 24-11256-00007, Rev. —

7

NS8000 Series

4

2

1

On

Off

DIP switch SA bus address

Switch 4

Switch 2

Switch 1

199

Off

Off

Off

200

Off

Off

On

201

Off

On

Off

202

Off

On

On

203

On

Off

Off

204

On

Off

On

205

On

On

Off

206

On

On

On

CO

2

 altitude compensation 

The Johnson Controls® NS Series CO

2

 Network Sensors ship from the factory calibrated for an altitude range of 0 ft to 2,000 ft

(0 m to 600 m) without compensation.

For altitudes above 2,000 ft (600 m) where optimum accuracy of the CO

2

 concentration measurement is essential, modify the 

offset property of the NS Series CO

2

 Network Sensors (Zone Quality [ZN-Q] Analog Input [AI]). The offset represents the local 

atmospheric pressure in hectopascals (hPa). Set the offset to the known local pressure or use the local altitude value listed in

Table 3. The factory default value is 978 hPa.

As of Release 5.3 of the Controller Configuration Tool (CCT) and Facility Explorer® Programmable Controller Tool (FX-PCT) 

software, the NS Series CO

2

 Network Sensors (Zone Quality [ZN-Q] Analog Input [AI]) automatically change the hPa value entered 

from Table 3

 into the correct offset value in the CCT and FX-PCT software. The offset value for the SA bus device is labeled ppm; 

however, it is the proper field to enter the hPa value found in 

Table 3. Refer to the 

Controller Tool Help (LIT-12011147)

 for more 

details.

Note: 

Enter the pressure value only in units of hPa. The sensor reads the value entered as hPa. The CO

2

 present value may 

require several minutes to settle after changing the offset value.

See Table 3 for local altitude values.

Network sensor addressing

Table 2: Network sensor addressing

Figure 1: Three-position switch

Hiding icons on the home screen

1.  Press and hold the 

Up

 and 

Down

 icons for five seconds until the Fahrenheit and Celsius indicator icons start to blink.

2.  Press the 

Menu 

icon five times.

3.  To go through each icon on the display, press the 

Down

 icon.

4.  When the icon you want to hide blinks, press the 

Up

 icon to hide it.

5.  To save the new settings, press the 

Menu 

icon five times to return to the home screen or wait for ten seconds for the screen to 

return to the home screen automatically.

Activating and deactivating the screen lockout

Lock the screen to prevent users from making setpoint changes or entering the commissioning mode. To activate and deactivate 

the screen lockout, complete the following steps:

1.  Press and hold the 

Menu

 icon for ten seconds until the 

Up

 and 

Down

 icons vanish on the display

to activate the screen lockout.

2.  Press and hold the 

Menu

 icon for ten seconds until the 

Up

Down

 and

 Fan

 icons reappear to deactivate the screen lockout.

Содержание NS Series

Страница 1: ...mpliance United States This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and us...

Страница 2: ...ence Height requirements may vary depending on the site Network sensors without CO2 sensing are shock and vibration resistant but not shock and vibration proof Be careful not to drop the unit or mount it where it could be exposed to excessive vibration Dropping a CO2 network sensor may result in readings outside of the specified accuracy tolerance Special tools only one type needed Johnson Control...

Страница 3: ...dhere to these wiring details causes the network sensor to function incorrectly You will not be able to connect to the system using the Bluetooth Wireless Comissioning Converter BTCVT Mobile Access Portal Gateway MAP or the handheld VAV balancing tool and you will not be able to expand the system with future offerings Notes IMPORTANT Do not connect the SA bus ground the modular phone jack GND or t...

Страница 4: ...Part No 24 11256 00007 Rev 4 NS8000 Series 5 2 1 4 15 VDC COM 15 VDC 1 2 5 6 4 3 COM SA SA SA SA COM 15 VDC 3 ...

Страница 5: ...r icon 6 Fahrenheit icon 7 Celsius icon 8 Percent relative humidity icon 9 Fan speed bars 10 Fan icon 11 Automatic fan speed icon 12 Up adjustment or navigation icon 13 SA bus online indicator 14 Down adjustment or navigation icon 15 Menu or enter icon 16 Occupancy indicator 17 Default display value setpoint zone temperature relative humidity 1 2 3 4 5 6 7 8 11 12 13 14 15 16 17 9 10 Table 1 Displ...

Страница 6: ...he home screen complete the following steps 1 Press and hold the Up and Down icons for five seconds until the Fahrenheit and Celsius indicator icons start to blink All icons are visible on the display 2 Press the Menu icon once 3 To select and switch between current temperature or setpoint value press the Up or Down icon 4 To save the new settings press the Menu icon five times to return to the ho...

Страница 7: ... it is the proper field to enter the hPa value found in Table 3 Refer to the Controller Tool Help LIT 12011147 for more details Note Enter the pressure value only in units of hPa The sensor reads the value entered as hPa The CO2 present value may require several minutes to settle after changing the offset value See Table 3 for local altitude values Network sensor addressing Table 2 Network sensor ...

Страница 8: ...earest customer service center or Johnson Controls representative Altitude above sea level Absolute pressure Feet Meters hPa 656 200 1 038 0 0 1 013 656 200 989 1 312 400 966 1 969 600 943 2 625 800 921 3 281 1 000 899 3 937 1 200 877 4 593 1 400 856 5 249 1 600 835 5 906 1 800 815 6 562 2 000 795 7 218 2 200 775 7 874 2 400 756 8 530 2 600 738 9 186 2 800 719 9 843 3 000 701 Table 3 CO2 altitude ...

Страница 9: ...H noncondensing 85 F 29 C maximum dew point Storage Display models 40 F to 122 F 40 C to 50 C 5 to 95 RH noncondensing Non display models 40 F to 185 F 40 C to 70 C 5 to 95 RH noncondensing Temperature resolution 0 5 F 0 5 C Temperature accuracy NS Series Network Zone Sensor 1 F 0 6 C Temperature element only 0 36 F 0 2 C at 70 F 21 C Humidity element accuracy NSB8BPN24x 0 models 2 RH for 20 to 80...

Страница 10: ...ulse voltage 330 V External power supply Intended for connection to Johnson Controls field controllers supporting the standard JCI SA Bus implementation CO2 sensor information The Model NSx8 Series Wall Mount sensors sense in part CO2 This functionality is intended to provide an input to equipment under normal operating conditions Where failure or malfunction of the transmitter could lead to perso...

Отзывы: