Johnson Controls MS-VMA1615-0U Скачать руководство пользователя страница 21

Table 10: VMA1615/1630 Controllers

United States:

UL Listed, File E107041, CCN PAZX, UL 916, Energy Management Equipment;

FCC Compliant to CFR47, Part 15, Subpart B, Class A

UL Listed, File S4977, UL 864 UUKL/UUKLC 10th Edition Listed, Smoke Control Units and
Accessories for Fire Alarm Systems Equipment

Compliance

Canada:

UL Listed, File E107041, CCN PAZX7 CAN/CSA C22.2 No.205, Signal Equipment; Industry

Canada Compliant, ICES-003

UL Listed, File S4977, UL 864 UUKL/ORD-C100-13 10th Edition Listed, Smoke Control Units and
Accessories for Fire Alarm Systems

Europe:

CE Mark – Johnson Controls declares that this product is in compliance with the essential
requirements and other relevant provisions of the EMC Directive.

Australia and New Zealand:

RCM Mark, Australia/NZ Emissions Compliant.

BACnet International

BACnet Testing Laboratories (BTL) Protocol Revision 12 Listed BACnet Advanced Application
Controller (B-AAC)

1

For more information, refer to the

MSTP Communications Bus Technical Bulletin (LIT-12011034).

2

Combined error due to offset, non-linearity, and temperature variation.

3

Includes error due to non-linearity.

The performance specifications are nominal and conform to acceptable industry standard. For application at conditions
beyond these specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for
damages resulting from misapplication or misuse of its products.

APAC Single Point of Contact:

NA/SA Single Point of Contact:

European Single Point of Contact:

JOHNSON CONTROLS

C/O CONTROLS PRODUCT MANAGEMENT

NO. 22 BLOCK D NEW DISTRICT

WUXI JIANGSU PROVINCE 214142

CHINA

JOHNSON CONTROLS

507 E MICHIGAN ST

MILWAUKEE WI 53202

USA

JOHNSON CONTROLS

WESTENDHOF 3

45143 ESSEN

GERMANY

Building Technologies & Solutions

507 E. Michigan Street, Milwaukee, WI 53202

Johnson Controls

®

is a registered trademark of Johnson Controls.

All other marks herein are the marks of their respective owners.

©

2018 Johnson Controls

www.johnsoncontrols.com

Published in U.S.A.

21

VMA1615 and VMA1630 Variable Air Volume Controllers Installation Instructions

Содержание MS-VMA1615-0U

Страница 1: ...amily Controllers and network sensors communicate using either the standard BACnet protocol based on the ANSI ASHRAE 135 2004 or the BACnet IP protocol The BACnet protocol is a standard for ANSI ASHRAE and the International Standards Organization ISO for building controls FEC VMA and most IOM field controllers are BTL listed as BACnet Application Specific Controllers B ASCs FAC field controllers a...

Страница 2: ...to tighten the square coupler bolt several shims or washers to mount the VMA power screwdriver 100 mm 4 in extension socket punch drill and 3 5 mm 9 64 in drill bits to mount the VMA pliers to open and close the damper required length of 3 97 mm 5 32 in ID pneumatic tubing and barbed fittings Mounting Observe these guidelines when mounting a VMA Important When the air supply to the VAV box is belo...

Страница 3: ...oses CW rotate the coupler to the CW mechanical limit The open end stop is automatically set for 90 boxes For 45 and 60 boxes hard stops must be provided at both full closed and full open damper positions By installing the VMA controller at the full open position the VMA controller provides the open stop for 45 and 60 boxes The closed damper seal provides the full closed stop 8 All models are comp...

Страница 4: ...Figure 2 VMA1615 1630 Controller Wiring Terminations and Physical Features VMA1630 Shown 4 VMA1615 and VMA1630 Variable Air Volume Controllers Installation Instructions ...

Страница 5: ...iversal Input Voltage Analog Input 0 10 VDC Resistive Analog Inputs 0 600k ohm see Table 3 0 2k Potentiometer RTD 1k Nickel 1k Platinum or A99B SI NTC 10K Type L 10K Johnson Controls Type II is equivalent to Type L or 2 252K Type II Dry Contact Binary Input 9 FC Bus Terminal Block May also be used for N2 connections See FC Bus Terminal Block Or N2 Protocol As Required 10 EOL End of Line Switch see...

Страница 6: ...input and output terminal and bus port locations on the VMA1615 1630 controllers Observe the following guidelines when wiring a VMA controller Input and Output Terminals The input spade terminals are located on the side of the VMA near the FC Bus terminal block The output spade terminals are located on the opposite side of the controller near the power supply terminal block See Table 3 for more in...

Страница 7: ... grounding the secondary of the 24 VAC transformer is required only one connection to ground should be made near the transformer See the following figure Figure 7 Transformer Grounding Risk of Property Damage Do not apply power to the system before checking all wiring connections Improper wiring of this terminal may cause a short circuit across the 24 VAC power supply on VMA models A short circuit...

Страница 8: ...ables but is recommended for input and output cables that are exposed to high electromagnetic or radio frequency noise Cable runs of less than 30 m 100 ft typically do not require an offset in the input output software setup Cable runs over 30 m 100 ft may require an offset in the input output software setup Maximum Cable Length versus Load Current Use Figure 8 to estimate the maximum cable length...

Страница 9: ...licable termination diagrams Table 2 Termination Details Termination Diagrams Type of Input Output Type of Field Device UI Voltage Input External Source UI Voltage Input Internal Source UI Voltage Input Self Powered UI Temperature Sensor UI Dry Contact CO 0 10 VDC Output to Actuator External Source 9 VMA1615 and VMA1630 Variable Air Volume Controllers Installation Instructions ...

Страница 10: ...Switch Low External Source Note Applies to CO4 and CO5 CO Incremental Control to Actuator Switch Low External Source CO Analog Output Voltage Note Applies to BO3 for VMA 1630 only BO1 and BO2 BO Incremental Control to Actuator Switch Low Internally Sourced BO 24 VAC Binary Output Switch Low Internally Sourced 10 VMA1615 and VMA1630 Variable Air Volume Controllers Installation Instructions ...

Страница 11: ... Output Type of Field Device SA Bus Network Stat with Phone Jack Fixed Address 199 SA Bus Network Stat with Terminals Addressable SA Bus Network Stat with Terminals Fixed Address 199 11 VMA1615 and VMA1630 Variable Air Volume Controllers Installation Instructions ...

Страница 12: ...ature Sensor Negative Temperature Coefficient NTC Sensor 10K Type L 10K Johnson Controls Type II is equivalent to Type L or 2 252K Type II See Guideline A in Table 4 Binary Input Dry Contact Maintained Mode 1 second minimum pulse width Internal 12 V 15k ohm pull up Same as Universal INn Universal Input Common for all Universal IN terminals Note All Universal ICOMn terminals are isolated from all o...

Страница 13: ...lines for Recommended Wire Sizes Assumptions Maximum Cable Length and Type Wire Size Gauge and Type Guideline 100 mV maximum voltage drop Depending on the cable length and the connected input or output device you may have to define an offset in the setup software for the input or output point 457 m 1 500 ft twisted wire 1 0 mm 18 AWG stranded copper A 297 m 975 ft twisted wire 0 8 mm 20 AWG strand...

Страница 14: ... wire 2 twisted pairs shielded cable recommended Note The and wires are one twisted pair and the COM and SA PWR wires are the second twisted pair SA Bus Communications SA BUS 2 SA Bus Signal Reference and 15 VDC Common COM 15 VDC Supply Power for Devices on the SA Bus SA PWR 24 AWG 3 pair CAT 3 Cable 30 5m 100 ft RJ 12 6 Position Modular Port provides FC Bus Communications FC BUS FC BUS 2 24 AWG 3...

Страница 15: ... 64 through 1 are device address switches Switch 128 is a mode switch that enables a field controller to operate on a ZFR ZFR Pro Series Wireless Field Bus Set switch 128 to OFF for all hard wired SA and FC Bus applications Figure 9 Device Address Switches Set to 21 Note Metasys field controllers ship with Switch 128 ON and the remaining address switches OFF This renders the controllers wired slav...

Страница 16: ...oller 3 Set the address switch set to the desired N2 address 4 Set the address switch segment labeled 128 to OFF 5 Reconnect the 24 VAC supply to the controller 6 Using an SA bus connection download the firmware and controller application file The download process asks to confirm switching the communication protocol to N2 7 Click OK 8 After the download is finished disconnect the 24 VAC supply to ...

Страница 17: ... controller fails to operate within its specifications contact the Johnson Controls Repair Center in Louisville Kentucky at 1 502 671 7312 Troubleshooting Table 8 provides LED status indicator information for troubleshooting the VMA1615 1630 controller Table 7 provides some additional troubleshooting information for possible problems Note If you experience short circuits in the 24 VAC power supply...

Страница 18: ...en multiple pieces of equipment 3 Verify the short circuit has been resolved with an ohm meter 4 Reset the breaker fuse or replace the transformer Note When replacing the transformer it is recommended to replace with a model that utilizes a resettable circuit breaker A circuit breaker makes solving wiring problems easier Ensure polarities of 24 V COM OCOM match and that the connected end device us...

Страница 19: ...9 to order accessories Table 9 VMA1615 1630 Controller Accessories Order Separately Description Product Code Number Transformer 120 24 VAC 96 VA with circuit breaker and 120 VAC outlet approved for Smoke Control PAN PWRSP U Refer to the NS Series Network Sensors Product Bulletin LIT 12011574 for specific sensor model descriptions NS Series Network Sensors Technical Specifications Table 10 VMA1615 ...

Страница 20: ...the supervisory controller and field controller SA Bus 0 6 mm 22 AWG stranded 4 wire 2 twisted pairs shielded cable recommended from the VMA controller for network sensors and other sensor actuator devices includes a terminal to source 15 VDC supply power from VMA to SA Bus devices 1 Communications Bus 1 RX630 32 bit Renesas microcontroller Processor 1 MB flash memory and 512 KB RAM Memory UI Anal...

Страница 21: ...r to the MSTP Communications Bus Technical Bulletin LIT 12011034 2 Combined error due to offset non linearity and temperature variation 3 Includes error due to non linearity The performance specifications are nominal and conform to acceptable industry standard For application at conditions beyond these specifications consult the local Johnson Controls office Johnson Controls shall not be liable fo...

Отзывы: