Table 8: VMA Controller Status LEDs
Descriptions of LED States
Normal State
LED Color
LED Label
Off Steady = No power
On Steady = Power is supplied by primary voltage
On Steady
Green
POWER
Blink - 2 Hz = Download or startup in progress, not ready for normal
operation, SA Bus devices offline (such as netsensors)
Rapid blink = SA Bus communications issue
Off Steady = No faults
On Steady = Device fault or no application loaded
Off Steady
Red
FAULT
Blink - 2 Hz = Data transmission (normal communication)
Off Steady = No data transmission (auto baud in progress)
On Steady = communication lost, waiting to join communication
ring
Blink - 2 Hz
Green
FC BUS
Blink - 2 Hz = Data transmission (normal communication)
Off Steady = No data transmission (N/A - auto baud not supported)
On Steady = Communication lost; waiting to join communication
ring
Blink - 2 Hz
Green
SA BUS
On Steady = EOL is active
Off Steady = EOL is not active
Off
Amber
EOL
Accessories
Use
to order accessories.
Table 9: VMA1615/1630 Controller Accessories (Order Separately)
Description
Product Code Number
Transformer, 120/24 VAC, 96 VA, with circuit breaker and 120 VAC outlet, approved for Smoke
Control
PAN-PWRSP-U
Refer to the
NS Series Network Sensors Product Bulletin (LIT-12011574)
for specific sensor model
descriptions.
NS Series Network Sensors
Technical Specifications
Table 10: VMA1615/1630 Controllers
MS-VMA1615-0U:
32-bit, Integrated VAV Controller/Actuator/Pressure Sensor - DPT, 3 UI and 2
BO, 24VAC, FC and SA Bus
MS-VMA1615-1U:
32-bit, Integrated VAV Controller/Actuator/Pressure Sensor - DPT, 3 UI and 2
BO, 24VAC, FC and SA Bus
MS-VMA1630-0U:
32-bit, Integrated VAV Controller/Actuator/Pressure Sensor - DPT; 3 UI, 3 BO,
and 2 CO; 24VAC; FC and SA Bus
MS-VMA1630-1U:
32-bit, Integrated VAV Controller/Actuator/Pressure Sensor - DPT; 3 UI, 3 BO,
and 2 CO; 24VAC; FC and SA Bus
Product Code Numbers
BACnet MSTP, N2
Communications
Protocol
24 VAC (nominal, 20 VAC minimum/30 VAC maximum), 50/60 Hz, Power Supply Class 2 (North
America)
Supply Voltage
19
VMA1615 and VMA1630 Variable Air Volume Controllers Installation Instructions