Johnson Controls Metasys NAE55 Скачать руководство пользователя страница 4

Power supply

Important: 

Install the data protection battery

before applying 24 VAC power to the network

engine. See the 

Installing the data protection battery

section.

In North America, use a Class 2, 24 VAC power supply with

a 50 VA minimum output. Outside North America, use a

24 VAC SELV transformer at the appropriate rating. The

minimum input voltage for the network engine to operate

properly is 20 VAC. See the 

Technical specifications

section.
Use a dedicated power supply to the network engine

only. Do not connect any other loads to the power supply.

Additional loads may cause noise interference.

Ethernet port

The Ethernet port, labeled

 ETHERNET

, is an 8-pin RJ-45

network port for connecting the network engine to

Ethernet IP networks. Network engine can connect to

Ethernet networks at 10 Mbps, 100 Mbps, or 1 Gbps.

This Ethernet port provides IP communications over

the building network and to any third-party integration

that uses Ethernet communication. The devices that you

integrate through the 

ETHERNET

 port on the network

engine include the following:
• BACnet/IP

• BACnet/SC devices utilize the ethernet port

• Ethernet TCP/IP

• Modbus TCP/IP

• KNX

• Tyco C•CURE 9000 and Tyco victor Video Management

• Simplex FACU

• Cree SmartCast Lighting Control

• Molex Lighting Control

• OPC Unified Architecture (UA)

FC Bus terminal block

The two Field Controller (FC) Bus connections on a

network engine are 4-pin removable, keyed terminal

blocks labeled 

FC-A

 and 

FC-B

. The FC bus connections are

optically isolated RS-485 ports that communicate at 9600,

19,200, 38,400, or 76,800 baud. You can use the FC Bus

port to integrate the following field controller networks

into the Metasys system:
• BACnet MS/TP FC Bus

• N2 Bus

• Modbus RTU

• M-Bus

Note: 

Each field controller integration has different

protocols and network requirements. Do not

intermix N2, MS/TP, Modbus, or M-Bus devices on

the same FC Bus port.

The SHD connections on the FC terminal blocks are not

connected to any earth ground connection. The FC A and

FC B terminal blocks are not interchangeable.

LonWorks network terminal block

The LonWorks TP/FT-10 network connection, available

only on the network engine LonWorks model, is a 3-wire

removable, keyed terminal block. The Shield connection

on the LonWorks network terminal block is an isolated

terminal and is not connected in the network engine.

Use the LonWorks terminal block to connect LonWorks

networks to the network engine.

Computer serial ports

The network engine has two RS-232-C serial ports labeled

RS232C A 

and 

RS232C B

 (Figure 3). Use either port to

connect a Modbus RTU or Zettler MXSpeak third-party

integration. For more information on how to use the

serial port for third-party vendor integration, refer to the

application note for the particular vendor integration you

are installing. Lastly, these RS-232-C serial ports do not

support external modems.

Universal Serial Bus (USB) ports

The two USB ports labeled 

USB A

 and 

USB B

 are

independent of each other. At Release 10.0 or later, the

use of a USB port to connect an optional external modem

is no longer supported.

Optional Internal Modem

MS-NAE55x1-x models with Release 9.0 have an internal

modem and a 6-pin RJ-12 modular jack labeled 

MODEM

.

Connect a standard phone line into the MODEM jack to

use the internal modem.

Note: 

Modem functionality is no longer available for

NAE55s upgraded to Release 10.0 or later.

For information on commissioning an internal modem

on older models, refer to the 

NAE Commissioning Guide

(LIT-1201519)

.

Wiring the Network Engine

Mount the network engine securely before wiring it. For

details, see 

Mounting

.

 CAUTION

Risk of Property Damage.

Do not apply power to the system before checking

all wiring connections. Short circuited or improperly

connected wires may result in permanent damage to

the equipment.

 Attention

Risque de dégâts matériels.

Ne pas mettre le système sous tension avant

d'avoir vérifié tous les raccords de câblage. Des

fils formant un court-circuit ou connectés de façon

incorrecte risquent d'endommager irrémédiablement

l'équipement.

NAE55 Installation Guide

4

Содержание Metasys NAE55

Страница 1: ... NAE55 Installation Instructions Part No 24 10051 00132 Note At Metasys Release 10 0 and later modems internal and external and pagers are no longer supported on NAE55 engines that run the Linux operating system but are still supported on prior releases for engines that use a Windows Embedded operating system You can field upgrade a network engine at Release 9 0 that has an internal modem to Relea...

Страница 2: ...ation Figure 6 Mount the network engine on an even surface in wall mount applications whenever possible If you must mount the network engine on an uneven surface be careful not to crack the wall mount feet or housing when tightening the screws Use shims or washers to mount the unit securely on the mounting surface Mount the network engine in areas free of corrosive vapors and observe the environme...

Страница 3: ... the network engine on the screws with the upper two mount feet Figure 6 5 Insert the screws into the lower two wall mount feet and holes and carefully tighten all of the screws Important Do not overtighten the mounting screws Overtightening the screws can crack the network engine wall mount feet or housing Mounting the Network Engine for DIN rail mount applications To mount the network engine on ...

Страница 4: ...not connected to any earth ground connection The FC A and FC B terminal blocks are not interchangeable LonWorks network terminal block The LonWorks TP FT 10 network connection available only on the network engine LonWorks model is a 3 wire removable keyed terminal block The Shield connection on the LonWorks network terminal block is an isolated terminal and is not connected in the network engine U...

Страница 5: ...s may result in permanent damage to the equipment Do not apply 24 VAC power to the network engine before installing the data protection battery See the Installing the data protection battery section in this document Use copper conductors only Make all wiring in accordance with local national and regional regulations The network engine is a low voltage 30 VAC device Do not exceed the network engine...

Страница 6: ...ed shield connection terminal 3 Set each FC EOL switch to their proper positions See the note in Setting the end of line switches Connecting LonWorks devices About this task To connect LonWorks devices complete the following steps 1 Connect the 2 wire cable from the LonWorks trunk to the removable 3 terminal blue plug labeled LON Figure 3 The LonWorks network trunk is available on the MS NAE5520 3...

Страница 7: ...converter s A terminal to the device s or A terminal b Connect the converter s B terminal to the device s or B terminal Figure 11 Connection between converter and device 4 To add additional vendor devices wire from one device to the next in a daisy chain configuration The completed wiring should look similar to Figure 12 Figure 12 Modbus RTU wiring detail overview Connecting M Bus devices About th...

Страница 8: ...D receive data PIN 3 on RJ12 7 GND ground PIN 5 on RJ12 4 To network engine RS 232C port Connecting KNX devices About this task The network engine connects to a KNX network device by using the KNX IP interface router After installation and wiring are complete refer to the Network Engine Commissioning for KNX Vendor Integration Application Note LIT 12013148 for additional information 1 Connect an E...

Страница 9: ...e removable power terminal connector on the network engine Figure 15 The connections are HOT and COM common Do not apply power yet Figure 15 Supply power wiring 24 VAC transformer Table 8 Power supply wiring Callout Description 1 NAE power terminal block 2 NAE power terminal block plug 3 Terminating wire for 24 VAC orange 4 Terminating wire for Common brown 5 Terminating wires from 24 VAC Class 2 ...

Страница 10: ...ly 3 minutes to start up and become operational See the LED test sequence at startup section Startup is complete and the network engine is operational when the green RUN LED is On steady and the red GEN FAULT LED is Off See Figure 18 for LED locations Disconnecting power from the Network Engine Important The data protection battery must be installed and charged before disconnecting the 24 VAC supp...

Страница 11: ...lished at 100 Mbps On Steady Yellow Ethernet connection is established at 1 000 Mbps FC A Green Flicker On Steady Controllers are defined to FC A FC Bus 1 or N2 Trunk 1 in the network engine but none are communicating network engine transmitting only Flicker Normal communications FC A port is transmitting and receiving data Flickers are generally in sync with data transmission but should not be us...

Страница 12: ...tegory Rules and Maximums General Star topology with network switches Number of Devices Maximum of 1 000 devices permitted at one site in the Metasys network 2 000 m 6 600 ft for plastic glass fiber optic with external adapter Line Length and Type 10 BaseT 100 m 330 ft Cat5 or Cat6 cable 100 BaseT 100 m 330 ft Cat5 or Cat6 cable 1000 BaseT 100 m 330 ft Cat5E or Cat6 cable Terminations For 10 100 1...

Страница 13: ...imally Required Termination Configuration At least one N2 device with an EOL switch in the ON position somewhere on each N2 Bus segment Table 14 Modbus RTU rules Category Rules and Maximums General One direct Modbus RTU RS 232 connection to either RS232C port is supported connection requires an RS 232 RS 485 converter to the RS232C serial port One direct Modbus RTU RS 485 connection to either FC B...

Страница 14: ... 2 x 0 8 mm 20 AWG shielded resistance 30 Ohms 64 350 m 1 148 ft 4 000 m 13 123 ft 2 x 0 8 mm 20 AWG shielded resistance 30 Ohms 9 600 250 350 m 1 148 ft 1 000 m 3 281 ft 2 x 0 8 mm 20 AWG shielded resistance 30 Ohms 38 400 64 350 m 1 148 ft 1 000 m 3 281 ft 2 x 0 8 mm 20 AWG shielded resistance 30 Ohms Line Length and Type Cable Twisted pair cable shielding optional Termination No termination 1 U...

Страница 15: ... 700 m 8 850 ft 2 200 m 7 200 ft Belden 8471 Cable 2 700 m 8 850 ft 2 200 m 7 200 ft Level IV 22 AWG 1 400 m 4 600 ft 1 150 m 3 770 ft JY St Y 2 x 2 x 0 8 900 m 2 950 ft 750 m 2 460 ft Note For the bus topology the maximum length stub cable is 3 m 10 ft and the stub lengths must be calculated into the overall segment length 1 FTT Free Topology Twisted Pair Transceiver LPT Link Power Twisted Pair T...

Страница 16: ...g mode Repair information If you replace a network engine for any reason or add a new network engine to a site you must update the site registration to ensure that the new network engine is recognized and able to communicate on the Metasys system site For details refer to the Replacing an NAE section in the NAE Commissioning Guide LIT 1201519 Except for replacing the data protection battery the ne...

Страница 17: ... a LonWorks trunk two third party trunks Modbus RTU or TCP M Bus or KNX or two N2 trunks BACnet MS TP RS 485 trunks or one N2 trunk and one BACnet MS TP trunk Supports up to 255 devices on the LonWorks trunk Supports up to 100 devices on each N2 or BACnet MS TP trunk Supports a BACnet IP or BACnet SC network This model is a BACnet BTL Listed controller at protocol revision 15 PR15 Table 23 Network...

Страница 18: ... IP router to connect KNX line through Ethernet to a network engine including line or area coupler functionality Note Order these accessories in AOMS from the European Distribution Center Note When you use the GRIPIN01 S KNX for NAE integration use a non secure mode Set Metasys driver N ROUTING MODE and in ETS set Secure mode to deactivated Table 27 Modbus training tool ordering information Course...

Страница 19: ...c housing with internal metal shield Plastic material ABS polycarbonate Protection IP20 IEC 60529 Mounting On a flat surface with screws on four mounting feet or on a dual 35 mm DIN rail Dimensions Height x Width x Depth 226 mm x 332 mm x 96 5 mm or 8 9 in x 13 1 in x 3 8 in including mounting feet Minimum space for mounting 303 mm x 408 mm x 148 mm or 12 0 in x 16 1 in x 5 8 in Shipping weight 2 ...

Страница 20: ...s all the requirements of the Canadian Interference Causing Equipment Regulations Cet appareil numérique de la Classe A respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada Industry Canada Statement s This device complies with Industry Canada licence exempt RSS standard s Operation is subject to the following two conditions 1 This device may not cause interference and 2 ...

Отзывы: