Table 28: NAE55xx-3 (UL 916, Energy Management) and NAE5510-3U (UL 864, Smoke Control) technical

specifications

Data protection battery

Supports data protection on power failure. Rechargeable gel cell battery: 12 V, 1.2 Ah,

with a typical life of 3 to 5 years at 21°C (70°F); Product Code Number: MS-BAT1010-0

Clock battery

Maintains real-time clock through a power failure. Onboard cell; typical life 10 years at

21°C or 70°F

Processor

1.46 GHz Intel

®

 Atom

®

 Bay Trail E3815 processor for MS-NAE55xx-3 models

Memory

16 GB flash nonvolatile memory for operating system, configuration data, and

operations data storage and backup for MS-NAE55xx-3 models.

2 GB DDR3 SDRAM for operations data dynamic memory for all models

Operating system

NAE5510-3U (UL 864 UUKL 10th ed /S527 UUKL7 4th ed)

: OEM Version of Microsoft®

Windows® Embedded Standard 7 with SP1 (WES7)

NAE55xx-3: (UL 916)

: Wind River

®

 Linux LTS 17 (LTS=long-term support)

Network and serial interfaces • One Ethernet port; 10/100/1000 Mbps; 8-pin RJ-45 connector

• Two optically isolated RS-485 ports; 9.6k, 19.2k, 38.4k, or 76.8k baud; pluggable and

keyed 4 position terminal blocks, RS-485 terminal blocks available on NAE55 models

only

• Two RS-232-C serial ports, with standard 9-pin sub-D connectors, that support all

standard baud rates

• Two USB 2.0 serial ports; standard USB connectors support an optional, user-

supplied external modem, no longer supported at Release 10.0 or later

• One LonWorks port; FTT10 78 Kbps; pluggable, keyed 3-position terminal block.

LonWorks port available on NAE552x-x models only

Housing

Plastic housing with internal metal shield

Plastic material: ABS + polycarbonate; Protection: IP20 (IEC 60529)

Mounting

On a flat surface with screws on four mounting feet or on a dual 35 mm DIN rail

Dimensions

(Height x Width x Depth)

226 mm x 332 mm x 96.5 mm or 8.9 in. x 13.1 in. x 3.8 in. including mounting feet

Minimum space for mounting: 303 mm x 408 mm x 148 mm or 12.0 in. x 16.1 in. x 5.8

in.

Shipping weight

2.9 kg or 6.4 lb

Compliance

United States

: UL Listed, File E107041, CCN PAZX, UL 916, Energy Management

Equipment, FCC Compliant to CFR47, Part 15, Subpart B, Class A

UL Listed, File S4977, UL 864 UUKL/UUKLC 10th Edition Listed, Smoke Control Units

and Accessories for Fire Alarm Systems Equipment (MS-NAE5510-3U model only with

Release 8.1 software)

Canada

: UL Listed, File E107041, CCN PAZX7, CAN/CSA C22.2 No. 205, Signal Equipment,

Industry Canada Compliant, ICES-003

UL Listed, File S4977, UL 864 UUKL/ORD-C100-13 10th Edition Listed, Smoke Control

Units and Accessories for Fire Alarm Systems. MS-NAE5510-3U model only with Release

8.1 software

Europe

: CE Mark - Johnson Controls declares that this product is in compliance with the

essential requirements and other relevant provisions of the EMC Directive.

Australia and New Zealand

: RCM Mark, Australia/NZ Emissions Compliant

United Kingdom

: Johnson Controls declares that this product is in compliance

with Electromagnetic Compatibility Regulations, The Electrical Equipment (Safety)

Regulations, and Restriction of the Use of Certain Hazardous Substances in Electrical

and Electronic Equipment Regulations.

BACnet International:

 BTL 135-2020 Listed B-BC/B-BBMD, Protocol Revision 15

FIPS 140-2 Level 1

: Compliant with Federal Information Processing Standard. NAE55s

at Release 11.0 only

NAE55 Installation Guide

19

Содержание Metasys NAE55

Страница 1: ... NAE55 Installation Instructions Part No 24 10051 00132 Note At Metasys Release 10 0 and later modems internal and external and pagers are no longer supported on NAE55 engines that run the Linux operating system but are still supported on prior releases for engines that use a Windows Embedded operating system You can field upgrade a network engine at Release 9 0 that has an internal modem to Relea...

Страница 2: ...ation Figure 6 Mount the network engine on an even surface in wall mount applications whenever possible If you must mount the network engine on an uneven surface be careful not to crack the wall mount feet or housing when tightening the screws Use shims or washers to mount the unit securely on the mounting surface Mount the network engine in areas free of corrosive vapors and observe the environme...

Страница 3: ... the network engine on the screws with the upper two mount feet Figure 6 5 Insert the screws into the lower two wall mount feet and holes and carefully tighten all of the screws Important Do not overtighten the mounting screws Overtightening the screws can crack the network engine wall mount feet or housing Mounting the Network Engine for DIN rail mount applications To mount the network engine on ...

Страница 4: ...not connected to any earth ground connection The FC A and FC B terminal blocks are not interchangeable LonWorks network terminal block The LonWorks TP FT 10 network connection available only on the network engine LonWorks model is a 3 wire removable keyed terminal block The Shield connection on the LonWorks network terminal block is an isolated terminal and is not connected in the network engine U...

Страница 5: ...s may result in permanent damage to the equipment Do not apply 24 VAC power to the network engine before installing the data protection battery See the Installing the data protection battery section in this document Use copper conductors only Make all wiring in accordance with local national and regional regulations The network engine is a low voltage 30 VAC device Do not exceed the network engine...

Страница 6: ...ed shield connection terminal 3 Set each FC EOL switch to their proper positions See the note in Setting the end of line switches Connecting LonWorks devices About this task To connect LonWorks devices complete the following steps 1 Connect the 2 wire cable from the LonWorks trunk to the removable 3 terminal blue plug labeled LON Figure 3 The LonWorks network trunk is available on the MS NAE5520 3...

Страница 7: ...converter s A terminal to the device s or A terminal b Connect the converter s B terminal to the device s or B terminal Figure 11 Connection between converter and device 4 To add additional vendor devices wire from one device to the next in a daisy chain configuration The completed wiring should look similar to Figure 12 Figure 12 Modbus RTU wiring detail overview Connecting M Bus devices About th...

Страница 8: ...D receive data PIN 3 on RJ12 7 GND ground PIN 5 on RJ12 4 To network engine RS 232C port Connecting KNX devices About this task The network engine connects to a KNX network device by using the KNX IP interface router After installation and wiring are complete refer to the Network Engine Commissioning for KNX Vendor Integration Application Note LIT 12013148 for additional information 1 Connect an E...

Страница 9: ...e removable power terminal connector on the network engine Figure 15 The connections are HOT and COM common Do not apply power yet Figure 15 Supply power wiring 24 VAC transformer Table 8 Power supply wiring Callout Description 1 NAE power terminal block 2 NAE power terminal block plug 3 Terminating wire for 24 VAC orange 4 Terminating wire for Common brown 5 Terminating wires from 24 VAC Class 2 ...

Страница 10: ...ly 3 minutes to start up and become operational See the LED test sequence at startup section Startup is complete and the network engine is operational when the green RUN LED is On steady and the red GEN FAULT LED is Off See Figure 18 for LED locations Disconnecting power from the Network Engine Important The data protection battery must be installed and charged before disconnecting the 24 VAC supp...

Страница 11: ...lished at 100 Mbps On Steady Yellow Ethernet connection is established at 1 000 Mbps FC A Green Flicker On Steady Controllers are defined to FC A FC Bus 1 or N2 Trunk 1 in the network engine but none are communicating network engine transmitting only Flicker Normal communications FC A port is transmitting and receiving data Flickers are generally in sync with data transmission but should not be us...

Страница 12: ...tegory Rules and Maximums General Star topology with network switches Number of Devices Maximum of 1 000 devices permitted at one site in the Metasys network 2 000 m 6 600 ft for plastic glass fiber optic with external adapter Line Length and Type 10 BaseT 100 m 330 ft Cat5 or Cat6 cable 100 BaseT 100 m 330 ft Cat5 or Cat6 cable 1000 BaseT 100 m 330 ft Cat5E or Cat6 cable Terminations For 10 100 1...

Страница 13: ...imally Required Termination Configuration At least one N2 device with an EOL switch in the ON position somewhere on each N2 Bus segment Table 14 Modbus RTU rules Category Rules and Maximums General One direct Modbus RTU RS 232 connection to either RS232C port is supported connection requires an RS 232 RS 485 converter to the RS232C serial port One direct Modbus RTU RS 485 connection to either FC B...

Страница 14: ... 2 x 0 8 mm 20 AWG shielded resistance 30 Ohms 64 350 m 1 148 ft 4 000 m 13 123 ft 2 x 0 8 mm 20 AWG shielded resistance 30 Ohms 9 600 250 350 m 1 148 ft 1 000 m 3 281 ft 2 x 0 8 mm 20 AWG shielded resistance 30 Ohms 38 400 64 350 m 1 148 ft 1 000 m 3 281 ft 2 x 0 8 mm 20 AWG shielded resistance 30 Ohms Line Length and Type Cable Twisted pair cable shielding optional Termination No termination 1 U...

Страница 15: ... 700 m 8 850 ft 2 200 m 7 200 ft Belden 8471 Cable 2 700 m 8 850 ft 2 200 m 7 200 ft Level IV 22 AWG 1 400 m 4 600 ft 1 150 m 3 770 ft JY St Y 2 x 2 x 0 8 900 m 2 950 ft 750 m 2 460 ft Note For the bus topology the maximum length stub cable is 3 m 10 ft and the stub lengths must be calculated into the overall segment length 1 FTT Free Topology Twisted Pair Transceiver LPT Link Power Twisted Pair T...

Страница 16: ...g mode Repair information If you replace a network engine for any reason or add a new network engine to a site you must update the site registration to ensure that the new network engine is recognized and able to communicate on the Metasys system site For details refer to the Replacing an NAE section in the NAE Commissioning Guide LIT 1201519 Except for replacing the data protection battery the ne...

Страница 17: ... a LonWorks trunk two third party trunks Modbus RTU or TCP M Bus or KNX or two N2 trunks BACnet MS TP RS 485 trunks or one N2 trunk and one BACnet MS TP trunk Supports up to 255 devices on the LonWorks trunk Supports up to 100 devices on each N2 or BACnet MS TP trunk Supports a BACnet IP or BACnet SC network This model is a BACnet BTL Listed controller at protocol revision 15 PR15 Table 23 Network...

Страница 18: ... IP router to connect KNX line through Ethernet to a network engine including line or area coupler functionality Note Order these accessories in AOMS from the European Distribution Center Note When you use the GRIPIN01 S KNX for NAE integration use a non secure mode Set Metasys driver N ROUTING MODE and in ETS set Secure mode to deactivated Table 27 Modbus training tool ordering information Course...

Страница 19: ...c housing with internal metal shield Plastic material ABS polycarbonate Protection IP20 IEC 60529 Mounting On a flat surface with screws on four mounting feet or on a dual 35 mm DIN rail Dimensions Height x Width x Depth 226 mm x 332 mm x 96 5 mm or 8 9 in x 13 1 in x 3 8 in including mounting feet Minimum space for mounting 303 mm x 408 mm x 148 mm or 12 0 in x 16 1 in x 5 8 in Shipping weight 2 ...

Страница 20: ...s all the requirements of the Canadian Interference Causing Equipment Regulations Cet appareil numérique de la Classe A respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada Industry Canada Statement s This device complies with Industry Canada licence exempt RSS standard s Operation is subject to the following two conditions 1 This device may not cause interference and 2 ...

Отзывы: