
Table 7: KNX/IP Interface Router connection
detail
Callout
Description
1
To power supply
2
To KNX devices
3
To Ethernet network
3. For a single KNX line, wire from the red and black
terminals on the gateway to the devices. For
multiple KNX lines, wire from the red and black
terminals on each gateway to the devices on the
same KNX line.
Note:
Specific cabling can vary depending
on the topology and site. See
considerations and guidelines for network
.
4. Wire each KNX gateway to its own dedicated power
supply on the KNX line.
Connecting other third-party devices
About this task:
Network engine models support several other third-
party devices. Refer to the following documents for
information about how to connect the network engine to
these devices:
•
C•CURE-victor:
Network Engine Commissioning for
C•CURE-victor Integration Application Note (LIT-12013151)
•
Simplex FACU:
Network Engine Commissioning for
Simplex Fire System Integration (LIT-12013060)
•
Cree SmartCast Lighting Control:
Metasys System
Commissioning for Cree Digital Lighting Systems
Integration (LIT-12013152)
•
Molex Lighting Control:
Metasys System Commissioning
for Molex Digital Lighting Systems Integration
(LIT-12013153)
•
Zettler Fire Panel:
Network Engine Commissioning for
Zettler MX Speak 6.0 Vendor Integration (LIT-12013269)
•
OPC UA Servers:
Network Engine Commissioning for OPC
UA Client Vendor Integration (LIT-12013545)
Connecting the power source
About this task:
Connect the 24 VAC supply power wires from the
transformer to the removable power terminal connector
on the network engine (Figure 15). The connections are
HOT
and
COM
(common).
Do
not
apply power yet.
Figure 15: Supply power wiring (24 VAC transformer)
Table 8: Power supply wiring
Callout Description
1
NAE power terminal block
2
NAE power terminal block plug
3
Terminating wire for 24 VAC (orange)
4
Terminating wire for Common (brown)
5
Terminating wires from 24 VAC Class 2 power
transformer
Note:
Power supply wire colors may be different on
transformers not manufactured by Johnson Controls.
Follow the transformer manufacturer’s instructions
and the project installation drawings.
Setup and adjustments
Installing the data protection battery
Important:
Do not apply 24 VAC power to the
network engine before installing the data protection
battery.
To install the data protection battery:
1. Remove the battery from its packaging. Remove the
battery cover on the network engine to expose the
battery compartment (Figure 3).
2. Carefully plug the network engine battery connector
from the battery compartment into the connector on
the battery cable (Figure 16).
3. Place the battery into the compartment (Figure 16).
4. Slide one end of the battery strap into the hole on
the opposite side of the strap (Figure 16), and loop
the strap tightly around the battery to minimize
battery movement.
5. Replace the cover of the battery compartment.
Important:
The data protection battery must
maintain a small residual charge. The battery ships
from the factory with a small residual charge.
You should connect 24 VAC power to the network
engine immediately after connecting the battery to
ensure that the battery does not completely loose its
charge, which may damage the battery.
NAE55 Installation Guide
9