background image

Published in U.S.A.
www.johnsoncontrols.com

FEU16x0 Field Equipment Controller Installation Instructions

 14

Metasys® and Johnson Controls® are registered trademarks of Johnson Controls.

All other marks herein are the marks of their respective owners. © 2018 Johnson Controls.

Building Technologies & Solutions

507 E. Michigan Street, Milwaukee, WI  53202

Содержание Metasys MS-FEU1610-0U

Страница 1: ...the controller in the original container to minimize vibration and shock damage to the controller Verify that all parts shipped with the controller Do not drop the controller or subject it to physical shock Parts Included one MS FEU1610 0U Controller with removable Terminal Plugs one Installation Instructions sheet Materials and Special Tools Needed three fasteners appropriate for the mounting sur...

Страница 2: ...ock Universal Inputs Voltage Analog Input Current Analog Input Resistive Analog Inputs Dry Contact Binary Input can be defined as 0 10 VDC 4 20 mA 0 2k ohm RTD 1k Nickel 1k Platinum or A99B SI NTC 10k Type L or 2 225k Type 2 Binary Inputs Dry Contact Maintained Pulse Counter Mode can be defined as 100 Hz high speed Cover Screw Sensor Port RJ 12 6 Pin Modular Jack FIG FEC1610_term ON ADDRESS ADDRES...

Страница 3: ...where electromagnetic emissions from other devices or wiring can interfere with controller communication Observe these additional guidelines when mounting a controller in a panel or enclosure Mount the controller so that the enclosure walls do not obstruct cover removal or ventilation through the controller Mount the controller so that the power transformer and other devices do not radiate excessi...

Страница 4: ... the SA Bus daisy chain If multiple Input Output Modules IOMs are used set the End of Line EOL switch on the last IOM Risk of Electric Shock Disconnect the power supply before making electrical connections to avoid electric shock Mise En Garde Risque de décharge électrique Débrancher l alimentation avant de réaliser tout raccordement électrique afin d éviter tout risque de décharge électrique Risk...

Страница 5: ...The Sensor Bus port on the bottom right of the IOM is an RJ 12 6 position modular jack that provides a connection for an NS sensor See Table 1 for more information The Sensors Port pin assignment is shown in Figure 5 Device Address DIP Switches Ensure the device address DIP switches are set to the appropriate address in the range of 4 127 Ensure that DIP switch 128 is set to Off which disables wir...

Страница 6: ...r phasing is uniform across the devices Powering devices with uniform 24 VAC supply power phasing reduces noise interference and ground loop problems The FEC does not require an earth ground connection Figure 5 Pin Number Assignments for Sensor SA Bus and FC Bus Ports on FEC IOM and VMA16 Power 15 VDC SA or FC Bus SA or FC Bus Bus and Power Common Power 15 VDC Sensor SA Bus or FC Bus Port RJ 12 Mo...

Страница 7: ...able 2 Analog Input Resistive Mode Accepts 0 600k ohm input signal Internal 12 V 15k ohm Pullup RTD 1k Nickel Johnson Controls 1k Platinum A99B Silicon Temperature Sensor Negative Temperature Coefficient NTC Sensor 10k Type L 2 252k Type 2 0 6 mm 22 AWG stranded 2 wire twisted non shielded cable for runs of 30 m 90 ft See Row A in Table 2 Binary Input Dry Contact Maintained Mode 1 second minimum p...

Страница 8: ...OUT to OCOM when activated 30 VAC maximum output voltage 0 5 A maximum output current 1 3 A at 25 duty cycle Maximum 6 cycles per hour with M9220 BGx 3 40 mA minimum load current 0 6 mm 22 AWG stranded 2 wire twisted non shielded cable for runs of 30 m 90 ft See Row C in Table 2 OCOM n Analog Output The signal common for all analog CO terminals isolated from all other terminal commons excluding BI...

Страница 9: ...er to the MS TP Communications Bus Technical Bulletin LIT 12011034 Table 2 Wire Gauge and Length Guidelines Guideline Cable Size Maximum Length Assumptions A 1 0 mm 18 AWG 457 2 m 1 500 ft 100 mV maximum voltage drop 0 8 mm 20 AWG 297 2 m 975 ft 0 6 mm 22 AWG 182 9 m 600 ft 0 5 mm 24 AWG 106 7 m 350 ft B 1 0 mm 18 AWG 228 6 m 750 ft 100 mV maximum voltage drop 0 8 mm 20 AWG 137 1 m 450 ft 0 6 mm 2...

Страница 10: ...s DIP switch block should be set to Off Table 3 shows and describes the valid FC Bus and SA Bus devices addresses for FECs and IOMs on Johnson Controls MS TP communications bus applications Table 3 FC Bus Device Address Descriptions Device Address Description 0 Reserved for FC Bus supervisory controller 1 3 Reserved for peripheral devices 4 127 Available for FECs on the FC bus and IOMs on the SA o...

Страница 11: ...Figure 10 When set to the INT position the FEU16 is the power source for the Binary Output and both sides of the load can be wired directly to the OUTx and COMx terminals Setting the jumper to the EXT position isolates the Binary Outputs and power must come from one or more external sources Do not wire the load directly to the OUTx and COMx terminals Wire one side of the load to the source and the...

Страница 12: ...econnect power to the controller Table 4 Status LEDs Name Color Normal Descriptions Power PWR Green On Steady Off Steady No Power On Steady Power is supplied by Primary Voltage Fault FLT Red Off Steady Blink 2 Hz Download or Startup in progress not ready for normal operation Off Steady No Faults On Steady Device Fault no application loaded Main Code download required if controller is in Boot mode ...

Страница 13: ...r a single 35 mm DIN rail Housing Plastic housing Plastic material ABS and polycarbonate UL94 5VB Analog Input Analog Output Resolution and Accuracy Analog Input Points 15 bit resolution Analog Output Points 16 bit resolution 200 mV accuracy Dimensions Height x Width x Depth 144 x 127 x 58 mm 5 68 x 5 x 2 25 in Minimum space for mounting 174 x 350 x 110 mm 6 8 x 13 8 x 4 3 in Weight 0 5 kg 1 10 lb...

Страница 14: ...ntroller Installation Instructions 14 Metasys and Johnson Controls are registered trademarks of Johnson Controls All other marks herein are the marks of their respective owners 2018 Johnson Controls Building Technologies Solutions 507 E Michigan Street Milwaukee WI 53202 ...

Отзывы: