FEU16x0 Field Equipment Controller Installation Instructions

8

Binary OUT
(Jumper set 
to External)

OUT 

n

Binary Output, 24 VAC Triac
Connects OUT to OCOM when activated
30 VAC maximum output voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
Maximum 6 cycles per hour with M9220-BGx-3
40 mA minimum load current

0.6 mm (22 AWG) stranded, 2-wire 
twisted, non-shielded cable for 
runs of <30 m (90 ft)

(See Row 

C

 in 

Table 2

.)

OCOM 

n

The signal common for Binary OUT terminals; isolated 
from all other terminal commons, including Binary Output 
terminal commons

Binary OUT
(Jumper Set 
to Internal)

OUT 

n

Sources 24 VAC Power (Hot)

0.6 mm (22 AWG) stranded, 2-wire 
twisted, non-shielded cable for 
runs of <30 m (90 ft)

(See Row 

C

 in 

Table 2

.)

OCOM 

n

Binary Output, 24 VAC Triac
Connects OCOM to 24 VAC Power (Com) when activated 
(low side switching).
30 VAC maximum output voltage
0.5 A maximum output current
40 mA minimum load current

Configurable 
OUT

OUT 

n

Analog Output, Voltage Mode
Sources 0-10 VDC
External 1k ohm minimum load required
10 VDC maximum output voltage
10 mA maximum output current

0.6 mm (22 AWG) stranded, 2-wire 
twisted, non-shielded cable for 
runs of <30 m (90 ft)

(See Row 

A

 in 

Table 2

.)

Binary Output, 24 VAC Triac mode
Connects OUT to OCOM when activated.
30 VAC maximum output voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
Maximum 6 cycles per hour with M9220-BGx-3
40 mA minimum load current

0.6 mm (22 AWG) stranded, 2-wire 
twisted, non-shielded cable for 
runs of <30 m (90 ft)

(See Row 

C

 in 

Table 2

.)

OCOM 

n

Analog Output:  The signal common for 

all

 analog CO 

terminals; isolated from all other terminal commons, 
excluding BI terminal commons
Binary Output:  The signal common for binary-configured 
CO terminals; isolated from 

all

 other terminal commons, 

including other CO terminal commons

0.6 mm (22 AWG) stranded, 2-wire 
twisted, non-shielded cable for 
runs of <30 m (90 ft)
(Same as OUT. See OUT cable 
type.)

Sensor

2,3

Sensor

Provides SA Bus communication network.
RJ-12 6-position modular connector

24 AWG 3-pair CAT 3 Cable 
<30.5 m (100 ft)

SA Bus

2

,

3

+
-

Provides SA Bus communication network.

0.6 mm (22 AWG) stranded, 4-wire 
twisted, shielded cable 
recommended

COM

Provides reference for network communication bus and 
15 VDC source power.

SA PWR

Sources 15 VDC power for devices on the SA Bus

FC Bus 
Terminal 

Block

3

+
-
COM

Provides FC Bus communication network.

0.6 mm (22 AWG) stranded, 3-wire 
twisted, shielded cable 
recommended

SHLD

Provides an optional shield connection.

Table 1:  FEC Terminal Blocks, Functions, Ratings, Requirements, and Cables (Part 2 of 3)

Terminal 
Block

Terminal 
Labels

Function and Electrical Ratings/Requirements

Recommended Cable Type 

and Length

1

Содержание Metasys MS-FEU1610-0U

Страница 1: ...the controller in the original container to minimize vibration and shock damage to the controller Verify that all parts shipped with the controller Do not drop the controller or subject it to physical shock Parts Included one MS FEU1610 0U Controller with removable Terminal Plugs one Installation Instructions sheet Materials and Special Tools Needed three fasteners appropriate for the mounting sur...

Страница 2: ...ock Universal Inputs Voltage Analog Input Current Analog Input Resistive Analog Inputs Dry Contact Binary Input can be defined as 0 10 VDC 4 20 mA 0 2k ohm RTD 1k Nickel 1k Platinum or A99B SI NTC 10k Type L or 2 225k Type 2 Binary Inputs Dry Contact Maintained Pulse Counter Mode can be defined as 100 Hz high speed Cover Screw Sensor Port RJ 12 6 Pin Modular Jack FIG FEC1610_term ON ADDRESS ADDRES...

Страница 3: ...where electromagnetic emissions from other devices or wiring can interfere with controller communication Observe these additional guidelines when mounting a controller in a panel or enclosure Mount the controller so that the enclosure walls do not obstruct cover removal or ventilation through the controller Mount the controller so that the power transformer and other devices do not radiate excessi...

Страница 4: ... the SA Bus daisy chain If multiple Input Output Modules IOMs are used set the End of Line EOL switch on the last IOM Risk of Electric Shock Disconnect the power supply before making electrical connections to avoid electric shock Mise En Garde Risque de décharge électrique Débrancher l alimentation avant de réaliser tout raccordement électrique afin d éviter tout risque de décharge électrique Risk...

Страница 5: ...The Sensor Bus port on the bottom right of the IOM is an RJ 12 6 position modular jack that provides a connection for an NS sensor See Table 1 for more information The Sensors Port pin assignment is shown in Figure 5 Device Address DIP Switches Ensure the device address DIP switches are set to the appropriate address in the range of 4 127 Ensure that DIP switch 128 is set to Off which disables wir...

Страница 6: ...r phasing is uniform across the devices Powering devices with uniform 24 VAC supply power phasing reduces noise interference and ground loop problems The FEC does not require an earth ground connection Figure 5 Pin Number Assignments for Sensor SA Bus and FC Bus Ports on FEC IOM and VMA16 Power 15 VDC SA or FC Bus SA or FC Bus Bus and Power Common Power 15 VDC Sensor SA Bus or FC Bus Port RJ 12 Mo...

Страница 7: ...able 2 Analog Input Resistive Mode Accepts 0 600k ohm input signal Internal 12 V 15k ohm Pullup RTD 1k Nickel Johnson Controls 1k Platinum A99B Silicon Temperature Sensor Negative Temperature Coefficient NTC Sensor 10k Type L 2 252k Type 2 0 6 mm 22 AWG stranded 2 wire twisted non shielded cable for runs of 30 m 90 ft See Row A in Table 2 Binary Input Dry Contact Maintained Mode 1 second minimum p...

Страница 8: ...OUT to OCOM when activated 30 VAC maximum output voltage 0 5 A maximum output current 1 3 A at 25 duty cycle Maximum 6 cycles per hour with M9220 BGx 3 40 mA minimum load current 0 6 mm 22 AWG stranded 2 wire twisted non shielded cable for runs of 30 m 90 ft See Row C in Table 2 OCOM n Analog Output The signal common for all analog CO terminals isolated from all other terminal commons excluding BI...

Страница 9: ...er to the MS TP Communications Bus Technical Bulletin LIT 12011034 Table 2 Wire Gauge and Length Guidelines Guideline Cable Size Maximum Length Assumptions A 1 0 mm 18 AWG 457 2 m 1 500 ft 100 mV maximum voltage drop 0 8 mm 20 AWG 297 2 m 975 ft 0 6 mm 22 AWG 182 9 m 600 ft 0 5 mm 24 AWG 106 7 m 350 ft B 1 0 mm 18 AWG 228 6 m 750 ft 100 mV maximum voltage drop 0 8 mm 20 AWG 137 1 m 450 ft 0 6 mm 2...

Страница 10: ...s DIP switch block should be set to Off Table 3 shows and describes the valid FC Bus and SA Bus devices addresses for FECs and IOMs on Johnson Controls MS TP communications bus applications Table 3 FC Bus Device Address Descriptions Device Address Description 0 Reserved for FC Bus supervisory controller 1 3 Reserved for peripheral devices 4 127 Available for FECs on the FC bus and IOMs on the SA o...

Страница 11: ...Figure 10 When set to the INT position the FEU16 is the power source for the Binary Output and both sides of the load can be wired directly to the OUTx and COMx terminals Setting the jumper to the EXT position isolates the Binary Outputs and power must come from one or more external sources Do not wire the load directly to the OUTx and COMx terminals Wire one side of the load to the source and the...

Страница 12: ...econnect power to the controller Table 4 Status LEDs Name Color Normal Descriptions Power PWR Green On Steady Off Steady No Power On Steady Power is supplied by Primary Voltage Fault FLT Red Off Steady Blink 2 Hz Download or Startup in progress not ready for normal operation Off Steady No Faults On Steady Device Fault no application loaded Main Code download required if controller is in Boot mode ...

Страница 13: ...r a single 35 mm DIN rail Housing Plastic housing Plastic material ABS and polycarbonate UL94 5VB Analog Input Analog Output Resolution and Accuracy Analog Input Points 15 bit resolution Analog Output Points 16 bit resolution 200 mV accuracy Dimensions Height x Width x Depth 144 x 127 x 58 mm 5 68 x 5 x 2 25 in Minimum space for mounting 174 x 350 x 110 mm 6 8 x 13 8 x 4 3 in Weight 0 5 kg 1 10 lb...

Страница 14: ...ntroller Installation Instructions 14 Metasys and Johnson Controls are registered trademarks of Johnson Controls All other marks herein are the marks of their respective owners 2018 Johnson Controls Building Technologies Solutions 507 E Michigan Street Milwaukee WI 53202 ...

Отзывы: