FEU16x0 Field Equipment Controller Installation Instructions
8
Binary OUT
(Jumper set
to External)
OUT
n
Binary Output, 24 VAC Triac
Connects OUT to OCOM when activated
30 VAC maximum output voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
Maximum 6 cycles per hour with M9220-BGx-3
40 mA minimum load current
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
(See Row
C
in
.)
OCOM
n
The signal common for Binary OUT terminals; isolated
from all other terminal commons, including Binary Output
terminal commons
Binary OUT
(Jumper Set
to Internal)
OUT
n
Sources 24 VAC Power (Hot)
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
(See Row
C
in
.)
OCOM
n
Binary Output, 24 VAC Triac
Connects OCOM to 24 VAC Power (Com) when activated
(low side switching).
30 VAC maximum output voltage
0.5 A maximum output current
40 mA minimum load current
Configurable
OUT
OUT
n
Analog Output, Voltage Mode
Sources 0-10 VDC
External 1k ohm minimum load required
10 VDC maximum output voltage
10 mA maximum output current
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
(See Row
A
in
.)
Binary Output, 24 VAC Triac mode
Connects OUT to OCOM when activated.
30 VAC maximum output voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
Maximum 6 cycles per hour with M9220-BGx-3
40 mA minimum load current
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
(See Row
C
in
.)
OCOM
n
Analog Output: The signal common for
all
analog CO
terminals; isolated from all other terminal commons,
excluding BI terminal commons
Binary Output: The signal common for binary-configured
CO terminals; isolated from
all
other terminal commons,
including other CO terminal commons
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
(Same as OUT. See OUT cable
type.)
Sensor
2,3
Sensor
Provides SA Bus communication network.
RJ-12 6-position modular connector
24 AWG 3-pair CAT 3 Cable
<30.5 m (100 ft)
+
-
Provides SA Bus communication network.
0.6 mm (22 AWG) stranded, 4-wire
twisted, shielded cable
recommended
COM
Provides reference for network communication bus and
15 VDC source power.
SA PWR
Sources 15 VDC power for devices on the SA Bus
FC Bus
Terminal
Block
+
-
COM
Provides FC Bus communication network.
0.6 mm (22 AWG) stranded, 3-wire
twisted, shielded cable
recommended
SHLD
Provides an optional shield connection.
Table 1: FEC Terminal Blocks, Functions, Ratings, Requirements, and Cables (Part 2 of 3)
Terminal
Block
Terminal
Labels
Function and Electrical Ratings/Requirements
Recommended Cable Type
and Length
1