Once the command to rotate is removed, the actuator 
holds its position, until either another command to 
rotate is applied or until all power is removed. When 
power is removed, the actuator spring returns to its -5° 
position (unless an external mechanical limit is 
reached). A stall condition while driving between -5 to 
90° causes the output hub to stop motion and hold its 
position until power is removed. Rotation is 
mechanically limited to the -5 and 90° positions by 
integral end-stops. Optional end-stops are available to 
limit the output hub travel. An anti-rotation bracket 
prevents rotational movement of the actuator body.

See Figure 9 and Figure 10 for proper wiring of the 
M9220-Bxx-3 On/Off Electric Spring Return Actuator.      

 

!

CAUTION: Risk of Electric Shock.

Disconnect the power supply before making 
electrical connections to avoid electric 
shock.

MISE EN GARDE : Risque de décharge 
électrique.

Débrancher l'alimentation avant de réaliser 
tout raccordement électrique afin d'éviter 
tout risque de décharge électrique.

!

CAUTION: Risk of Property Damage.

Do not apply power to the system before 
checking all wiring connections. Short 
circuited or improperly connected wires may 
result in permanent damage to the 
equipment.

MISE EN GARDE : Risque de dégâts 
matériels.

Ne pas mettre le système sous tension 
avant d'avoir vérifié tous les raccords de 
câblage. Des fils formant un court-circuit ou 
connectés de façon incorrecte risquent 
d'endommager irrémédiablement 
l'équipement

IMPORTANT:

Make all wiring connections in 

accordance with local, national, and regional 
regulations. Do not exceed the electrical ratings of 
the M9220-Bxx-3 On/Off Electric Spring Return 
Actuator.

Figure 9:  Auxiliary Switch Wiring Diagram for 

BxC Models

COM

NC

NO

21

21

23

22

21

22

23

BLK/
RED

BLK/
BLU

BLK/
GRY

COM

NC

NO

24

25

26

WHT/
RED

WHT/
BLU

WHT/
GRY

25

24

24

26

S2

S1

F

IG

:B

xC

w

ir

in

g

Figure 10:  Control Wiring Diagrams

AC 24 V  50/60 Hz
DC 24 V

RED

2

1

BLK

+

-

~

L1

N

WHT BLK

2

1

AC 120 V  60 Hz

L1

N

BLU BRN

2

1

AC 230 V  50/60 Hz

FI

G

:c

nt

rl

_w

ir

Содержание M9220-Bxx-3

Страница 1: ...c Spring Return Actuator only to control equipment under normal operating conditions Where failure or malfunction of the M9220 Bxx 3 actuator could lead to personal injury or property damage to the controlled equipment or other property additional precautions must be designed into the control system Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit cont...

Страница 2: ...le identifies the electrical connections and wiring details are also included on the actuator housing Parts Included On off electric spring return actuator with coupler Anti rotation bracket Manual override crank Two M3 x 9 5 mm self drilling sheet metal mounting screws Two No 10 32 x 9 16 in thread forming conduit screws Special Tools Needed Torque wrench with 3 8 in 10 mm socket Digital voltmete...

Страница 3: ...ions Figure 1 M9220 Bxx 3 On Off Electric Spring Return Actuator Dimensions in mm A 4 102 10 5 16 262 2 3 16 56 FIG M9210_9220_dimen 1 3 4 44 1 8 3 3 3 16 81 3 4 19 2 3 16 56 1 25 2 51 1 19 32 40 1 1 16 27 1 4 6 5 Mounting Hole 6 Locations 1 19 32 40 1 19 32 40 6 15 16 176 10 254 ...

Страница 4: ...e M9210 20 actuator from rain sleet or snow quantity 1 M9000 400 Jackshaft Linkage Kit Open ended design enables clamping onto a jackshaft without requiring access to the ends of the jackshaft quantity 1 M9000 519 Valve linkage for mounting M9220 actuator to 2 1 2 to 6 in flanged ball valves M9000 604 Replacement Anti rotation Bracket Kit with screws for M9210 xxx 3 Series Proportional Electric Sp...

Страница 5: ...e B of the actuator as determined by the shaft length 2 Snap the locking clip securely into the coupler retention groove to retain the coupler Manual Override Use only the supplied manual override crank to reposition the actuator hub when using the manual override feature To reposition the actuator hub proceed as follows 1 De energize the actuator 2 Insert the hex end of the manual override crank ...

Страница 6: ... to the damper frame or duct using the two M3 x 9 5 mm self drilling sheet metal screws provided and a 1 4 in 6 mm blade screwdriver or 5 16 in 8 mm nut driver 5 Slide the actuator onto the damper shaft and position the tab of the anti rotation bracket into the slot at the bottom of the actuator as illustrated in Figure 6 Table 2 Dimensions from Anti Rotation Bracket to Shaft Center Shaft Diameter...

Страница 7: ...ach progressive mounting position reduces the rotation range an additional 5 1 Check that the damper blade is visually accessible or that its position is permanently marked on the end of the damper shaft as illustrated in Figure 7 Note Two stops are stacked on top of each other and assembled with a single screw 2 Determine the desired rotation range If a 65 to 90 rotation range is desired add two ...

Страница 8: ...isque de décharge électrique Débrancher l alimentation avant de réaliser tout raccordement électrique afin d éviter tout risque de décharge électrique CAUTION Risk of Property Damage Do not apply power to the system before checking all wiring connections Short circuited or improperly connected wires may result in permanent damage to the equipment MISE EN GARDE Risque de dégâts matériels Ne pas met...

Страница 9: ...g example for the most accurate positioning of Auxiliary Switch No 2 To change the switch point of Auxiliary Switch No 2 proceed as follows 1 Position the actuator in the full spring return position Note Auxiliary Switch No 2 is factory set to trip when the actuator reaches the 81 position 2 Rotate the switch adjuster until it points to the desired switch point 3 Connect Auxiliary Switch No 2 to a...

Страница 10: ...op Kit mechanically limited to 90 Rotation Time Power On Running 24 to 57 seconds for 0 to 177 lb in 0 to 20 N m at all operating conditions 35 seconds nominal at full rated load Power Off Spring Returning 11 to 15 seconds for 0 to 177 lb in 0 to 20 N m at room temperature 35 seconds maximum for 0 to 177 lb in 0 to 20 N m at 22 F 30 C 130 seconds maximum for 0 to 177 lb in 0 to 20 N m at 40 F 40 C...

Страница 11: ... requirements and other relevant provisions of the EMC Directive and Low Voltage Directive Australia and New Zealand RCM Mark Australia NZ Emissions Compliant ModeIs All M9220 xGx and M9220 xDx Shipping Weight BAx and BDx Models 7 6 lb 3 5 kg BGx Models 6 4 lb 2 9 kg The performance specifications are nominal and conform to acceptable industry standards For application at conditions beyond these s...

Страница 12: ... 1922 1 770 242 1922 Triatek www triatek com contact 1 888 424 1922 1 770 242 1922 Sales support Region Group Contact information North America Product Sales Support jciorder jci com 1 800 275 5676 Option 1 Order Support Applied DX Sales Support applieddxsalessupport jci com Triatek Sales Support sales triatek com 1 888 424 1922 1 770 242 1922 Technical support Region Group Contact information Nor...

Отзывы: