background image

M9220-Bxx-3 On/Off Electric Spring Return Actuators Installation Guide

5

Counterclockwise (CCW) Spring Return 
Direction – Clockwise (CW) Powered 
Operation

For CCW spring return direction, mount the actuator to 
the damper shaft so that the Side A of the actuator is 
away from the damper as illustrated in Figure 2. With 
power applied, the actuator drives CW from the 
0° position, and spring returns CCW.

Clockwise (CW) Spring Return Direction – 
Counterclockwise (CCW) Powered Operation

To change the spring return direction to CW, mount the 
actuator to the damper shaft so that Side B of the 
actuator is away from the damper as illustrated in 
Figure 3. With power applied, the actuator now drives 
CCW from the 0° position, and spring returns CW.

Removable Coupler

The coupler may be installed on either side of the 
output hub. If the damper shaft is less than 3-19/32 in. 
(91 mm) long, insert the coupler in the face of the 
actuator closest to the damper. If the damper shaft is 
shorter than 1-5/32 in. (29 mm) long, a shaft extension 
is required to mount the actuator.

To change the position of the coupler, see Figure 4 and 
proceed as follows:

1. Mount the coupler on either Side A or Side B of the 

actuator, as determined by the shaft length.

2. Snap the locking clip securely into the coupler 

retention groove to retain the coupler.

Manual Override

Use only the supplied manual override crank to 
reposition the actuator hub when using the manual 
override feature.

To reposition the actuator hub, proceed as follows:

1. De-energize the actuator.

2. Insert the hex end of the manual override crank 

into the manual override adjustment point on the 
face of the actuator.

3. Rotate the manual override crank in the direction 

indicated by the arrow on the label.

Figure 2:  Side A of Actuator

A

90

-5

10

20

30

40

50

60

70

80

Manual
Override

Pointer Showing
Actuator in the
Spring Return
Position

Auxiliary Switch
Adjuster Located 
on the Right

FI

G

:s

id

ea

Side A: CCW Spring Return Direction

Figure 3:  Side B of Actuator

B

90

-5

10

20

30

40

50

60

70

80

Auxiliary Switch

Adjuster Located 

on the Left

Pointer Showing

Actuator in the

Spring Return

Position

Manual

Override

FI

G

:s

id

eb

Side B: CW Spring Return Direction

IMPORTANT:

Applying excessive torque to the 

manual override or running the manual override with 
a power tool may damage the internal components 
of the actuator and cause premature failure.

Figure 4:  Changing the Position of the Coupler

Shaft Coupler

U-Bolt Nut

and Washer

(Qty Two)

Pointer

U-Bolt 

Locking Clip

FIG

:ch

pos

Assembled View

 of Coupler

 Subassembly

Содержание M9220-Bxx-3

Страница 1: ...c Spring Return Actuator only to control equipment under normal operating conditions Where failure or malfunction of the M9220 Bxx 3 actuator could lead to personal injury or property damage to the controlled equipment or other property additional precautions must be designed into the control system Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit cont...

Страница 2: ...le identifies the electrical connections and wiring details are also included on the actuator housing Parts Included On off electric spring return actuator with coupler Anti rotation bracket Manual override crank Two M3 x 9 5 mm self drilling sheet metal mounting screws Two No 10 32 x 9 16 in thread forming conduit screws Special Tools Needed Torque wrench with 3 8 in 10 mm socket Digital voltmete...

Страница 3: ...ions Figure 1 M9220 Bxx 3 On Off Electric Spring Return Actuator Dimensions in mm A 4 102 10 5 16 262 2 3 16 56 FIG M9210_9220_dimen 1 3 4 44 1 8 3 3 3 16 81 3 4 19 2 3 16 56 1 25 2 51 1 19 32 40 1 1 16 27 1 4 6 5 Mounting Hole 6 Locations 1 19 32 40 1 19 32 40 6 15 16 176 10 254 ...

Страница 4: ...e M9210 20 actuator from rain sleet or snow quantity 1 M9000 400 Jackshaft Linkage Kit Open ended design enables clamping onto a jackshaft without requiring access to the ends of the jackshaft quantity 1 M9000 519 Valve linkage for mounting M9220 actuator to 2 1 2 to 6 in flanged ball valves M9000 604 Replacement Anti rotation Bracket Kit with screws for M9210 xxx 3 Series Proportional Electric Sp...

Страница 5: ...e B of the actuator as determined by the shaft length 2 Snap the locking clip securely into the coupler retention groove to retain the coupler Manual Override Use only the supplied manual override crank to reposition the actuator hub when using the manual override feature To reposition the actuator hub proceed as follows 1 De energize the actuator 2 Insert the hex end of the manual override crank ...

Страница 6: ... to the damper frame or duct using the two M3 x 9 5 mm self drilling sheet metal screws provided and a 1 4 in 6 mm blade screwdriver or 5 16 in 8 mm nut driver 5 Slide the actuator onto the damper shaft and position the tab of the anti rotation bracket into the slot at the bottom of the actuator as illustrated in Figure 6 Table 2 Dimensions from Anti Rotation Bracket to Shaft Center Shaft Diameter...

Страница 7: ...ach progressive mounting position reduces the rotation range an additional 5 1 Check that the damper blade is visually accessible or that its position is permanently marked on the end of the damper shaft as illustrated in Figure 7 Note Two stops are stacked on top of each other and assembled with a single screw 2 Determine the desired rotation range If a 65 to 90 rotation range is desired add two ...

Страница 8: ...isque de décharge électrique Débrancher l alimentation avant de réaliser tout raccordement électrique afin d éviter tout risque de décharge électrique CAUTION Risk of Property Damage Do not apply power to the system before checking all wiring connections Short circuited or improperly connected wires may result in permanent damage to the equipment MISE EN GARDE Risque de dégâts matériels Ne pas met...

Страница 9: ...g example for the most accurate positioning of Auxiliary Switch No 2 To change the switch point of Auxiliary Switch No 2 proceed as follows 1 Position the actuator in the full spring return position Note Auxiliary Switch No 2 is factory set to trip when the actuator reaches the 81 position 2 Rotate the switch adjuster until it points to the desired switch point 3 Connect Auxiliary Switch No 2 to a...

Страница 10: ...op Kit mechanically limited to 90 Rotation Time Power On Running 24 to 57 seconds for 0 to 177 lb in 0 to 20 N m at all operating conditions 35 seconds nominal at full rated load Power Off Spring Returning 11 to 15 seconds for 0 to 177 lb in 0 to 20 N m at room temperature 35 seconds maximum for 0 to 177 lb in 0 to 20 N m at 22 F 30 C 130 seconds maximum for 0 to 177 lb in 0 to 20 N m at 40 F 40 C...

Страница 11: ... requirements and other relevant provisions of the EMC Directive and Low Voltage Directive Australia and New Zealand RCM Mark Australia NZ Emissions Compliant ModeIs All M9220 xGx and M9220 xDx Shipping Weight BAx and BDx Models 7 6 lb 3 5 kg BGx Models 6 4 lb 2 9 kg The performance specifications are nominal and conform to acceptable industry standards For application at conditions beyond these s...

Страница 12: ... 1922 1 770 242 1922 Triatek www triatek com contact 1 888 424 1922 1 770 242 1922 Sales support Region Group Contact information North America Product Sales Support jciorder jci com 1 800 275 5676 Option 1 Order Support Applied DX Sales Support applieddxsalessupport jci com Triatek Sales Support sales triatek com 1 888 424 1922 1 770 242 1922 Technical support Region Group Contact information Nor...

Отзывы: