Johnson Controls M9106 Series Скачать руководство пользователя страница 5

 

M9106-xGx-2 Series Electric Non-Spring Return Actuators Installation Instructions    

5

 

Wiring 

!

   CAUTION: Risk of Property Damage. 

Do not apply power to the system before checking 
all wiring connections. Short circuited or improperly 
connected wires may result in permanent damage to 
the equipment. 

MISE EN GARDE: Risque de dégâts matériels. 

Ne pas mettre le système sous tension avant d'avoir 
vérifié tous les raccords de câblage. Des fils formant 
un court-circuit ou connectés de façon incorrecte 
risquent d'endommager irrémédiablement 
l'équipement. 

 

IMPORTANT: 

Make all wiring connections in 

accordance with the National Electrical Code and all 
local regulations. 

The actuator requires a 24 VAC control signal and is 
compatible with a variety of controllers. (See 
Figure 10.) 

Proportional Control

Models: GGx

On-Off Control

Models: IGx

0-10 VDC

0-10 VDC
0-20 mA

+

+

FB

VDC/mA

+24

COM

24 VAC

-

<

~

Auxiliary Switches

Models: All xGC

Feedback Potentiometer

Model: AGF (0-10,000 ohms)

S1

C1

NC1

NO1

10°

S2

NC2

NO2

C2

80°

Floating Control

Models: AGx and IGx 

~

~

CCW

CCW

CW

CW

COM

COM

<

<

24 VAC

24 VAC

~

~

CW

0%

100%

CW

CCW

Wiper

 

Figure 10: Wiring for M9106 Models 

Note: 

To avoid excessive wear or drive time on the 

motor for the AGx models, use a controller and/or 
software that provides a time-out function to remove 
the signal at the end of rotation (stall). The GGx and 
IGx models have an auto shutoff to avoid excessive 
wear or drive time on the motor. 

Through the Conduit Openings 

Depending on the M9106 model selected, one or both 
conduit openings are used. 

1.  Loosen the cover screw and remove the actuator 

cover. 

2.  Push the plastic conduit plug out of the 

conduit opening with fingertip. (See Figure 11.) 

Cover

Screw

Cover

Gear

Release

Plugs

(Conduit Openings)

 

Figure 11: Location of the Conduit Openings 

3.  Use the Phillips No. 1 screwdriver to puncture a 

hole through the center of the plastic conduit plug. 
Reinsert the plug into the conduit opening. 

Note: 

For applications requiring metal conduit, 

thread the conduit fitting into the conduit opening and 
hand tighten. 

4.  Insert the cable wires through the plastic plug, 

compression fitting, or conduit fitting, and connect 
to the terminals using the appropriate wiring 
diagram in Figure 10. 

IMPORTANT: 

Install all quick-connect 

terminals in the same direction to prevent shorting. 
(See Figure 12.) 

 

Figure 12: Orientation of Terminals 

Note: 

If using optional pluggable terminal blocks 

(M9000-105 or M9000-106), insert the cable wires 
through the conduit opening, and then connect the 
wires to the terminals. 

Содержание M9106 Series

Страница 1: ... alarme ou des dispositifs de sécurité ou de limitation ayant une fonction d avertissement ou de protection en cas de défaillance ou de dysfonctionnement du M9106 xGx 2 Series actuator Parts Included M9106 xGx 2 actuator M9000 160 anti rotation bracket two No 12 24 x 1 2 in self tapping hex washer head screws spade terminals Special Tools Needed drill with a 3 16 in No 15 4 57 mm drill bit 5 16 in...

Страница 2: ...hten the mounting screws to avoid stripping the threads 8 Secure the coupler to the shaft using a 5 16 in 8 mm square socket or 3 8 in 10 mm 12 point socket to tighten the coupler set screw against the damper shaft See Figure 1 9 Continue tightening the coupler set screw to achieve a torque of 150 to 180 lb in 17 to 20 N m Note Keep the actuator parallel to the mounting surface while tightening th...

Страница 3: ...river to loosen the end stop set screw on the actuator that is closest to the stop gear and move it in its slot so it is tight against the stop gear See Figure 5 IMPORTANT Do not remove the end stop set screws as this could interfere with the actuator s operation 4 Repeat Steps 1 through 3 to set the desired maximum rotation position 5 Tighten both end stop set screws to a minimum of 25 lb in 2 8 ...

Страница 4: ...tches for the desired rotation time NC2 NO2 C2 C1 NC1 NO1 Time Minutes 1 0 1 5 2 0 5 5 11 0 1 0 Off On Off On Off On A B C Off Off Off Off Off Off On Off On On On On Mode Switch Settings A B C Note The IGA models have Board 1 and the IGC models have both Board 1 and Board 2 Board 1 Board 2 COM CW CCW Off On Figure 8 Mode Switch Settings on IGx Models The 1 1 5 and 2 minute settings are ideal for o...

Страница 5: ...ar or drive time on the motor for the AGx models use a controller and or software that provides a time out function to remove the signal at the end of rotation stall The GGx and IGx models have an auto shutoff to avoid excessive wear or drive time on the motor Through the Conduit Openings Depending on the M9106 model selected one or both conduit openings are used 1 Loosen the cover screw and remov...

Страница 6: ...3 Note At this point the normally closed contact closes and the normally open contact opens See Auxiliary Switches in Figure 10 Switch S2 To change the angle of Switch S2 to 70 refer to Figure 13 and proceed as follows 1 Press and hold the gear release Using the 0 to 90 nodule guides rotate the coupler until the center of the coupler set screw is at 70 2 Rotate Switch S2 CW and align the edge of t...

Страница 7: ... 35 lb in 4 N m Cycles 100 000 full cycles 2 500 000 repositions rated at 53 lb in 6 N m Audible Noise Rating 35 dBA maximum at 1 m Rotation Range Adjustable from 30 to 90 CW or CCW Rotation Time IGx Adjustable with switch settings Factory set for 1 minute See Figure 12 60 90 120 330 or 660 seconds 1 1 5 2 5 5 or 11 min at 60 Hz and 72 108 144 396 or 792 seconds 1 2 1 8 2 4 6 6 or 13 2 minutes at ...

Страница 8: ...s Installation Instructions Building Efficiency 507 E Michigan Street Milwaukee WI 53202 Metasys and Johnson Controls are registered trademarks of Johnson Controls Inc All other marks herein are the marks of their respective owners 2014 Johnson Controls Inc ...

Отзывы: