M9106-xGx-2 Series Electric Non-Spring Return Actuators Installation Instructions
5
Wiring
!
CAUTION: Risk of Property Damage.
Do not apply power to the system before checking
all wiring connections. Short circuited or improperly
connected wires may result in permanent damage to
the equipment.
MISE EN GARDE: Risque de dégâts matériels.
Ne pas mettre le système sous tension avant d'avoir
vérifié tous les raccords de câblage. Des fils formant
un court-circuit ou connectés de façon incorrecte
risquent d'endommager irrémédiablement
l'équipement.
IMPORTANT:
Make all wiring connections in
accordance with the National Electrical Code and all
local regulations.
The actuator requires a 24 VAC control signal and is
compatible with a variety of controllers. (See
Figure 10.)
Proportional Control
Models: GGx
On-Off Control
Models: IGx
0-10 VDC
0-10 VDC
0-20 mA
+
+
FB
VDC/mA
+24
COM
24 VAC
-
<
~
Auxiliary Switches
Models: All xGC
Feedback Potentiometer
Model: AGF (0-10,000 ohms)
S1
C1
NC1
NO1
10°
S2
NC2
NO2
C2
80°
Floating Control
Models: AGx and IGx
~
~
CCW
CCW
CW
CW
COM
COM
<
<
24 VAC
24 VAC
~
~
CW
0%
100%
CW
CCW
Wiper
Figure 10: Wiring for M9106 Models
Note:
To avoid excessive wear or drive time on the
motor for the AGx models, use a controller and/or
software that provides a time-out function to remove
the signal at the end of rotation (stall). The GGx and
IGx models have an auto shutoff to avoid excessive
wear or drive time on the motor.
Through the Conduit Openings
Depending on the M9106 model selected, one or both
conduit openings are used.
1. Loosen the cover screw and remove the actuator
cover.
2. Push the plastic conduit plug out of the
conduit opening with fingertip. (See Figure 11.)
Cover
Screw
Cover
Gear
Release
Plugs
(Conduit Openings)
Figure 11: Location of the Conduit Openings
3. Use the Phillips No. 1 screwdriver to puncture a
hole through the center of the plastic conduit plug.
Reinsert the plug into the conduit opening.
Note:
For applications requiring metal conduit,
thread the conduit fitting into the conduit opening and
hand tighten.
4. Insert the cable wires through the plastic plug,
compression fitting, or conduit fitting, and connect
to the terminals using the appropriate wiring
diagram in Figure 10.
IMPORTANT:
Install all quick-connect
terminals in the same direction to prevent shorting.
(See Figure 12.)
Figure 12: Orientation of Terminals
Note:
If using optional pluggable terminal blocks
(M9000-105 or M9000-106), insert the cable wires
through the conduit opening, and then connect the
wires to the terminals.