M9106-xGx-2 Series Electric Non-Spring Return Actuators Installation Instructions    

3

 

Less than 90 Degrees 

If the damper shaft rotation is less than 90°, the 
rotation range of the actuator has to be adjusted with 
the scale on the actuator cover. (See Figure 5.) 

90

60

30

0

0

90

30

60

End-stops (2)

Coupler Set

Screw

Damper
Shaft

End-stop

Set Screws

(2)

Stop Gear

 

Figure 5: Setting the Rotation Range 

Use the center of the coupler set screw as a pointer to 
observe the position on the scale when rotating the 
coupler from one side to the other. 

Examples: 

 

For a rotation range of 90°, move both end-stop 
set screws fully up as shown in Figure 5. 

 

To set a rotation range of 60°, leave one end-stop 
set screw fully up, and adjust the other set screw 
so the coupler rotates between the 30 and 90° 
indicator marks on the scale. 

 

For a rotation range of 45°, adjust both end-stop 
set screws so the coupler rotates between the 
30 and 75° indicator marks on the scale. 

 

To set a rotation range of 30°, move both end-stop 
set screws so the coupler rotates between the 
30 and 60° indicator marks on the scale. 

To accurately set the end stops: 

1.  Press and hold the gear release lever. Turn the 

actuator coupler to the minimum rotation position 
for the minimum ventilation flow required. 

2.  Release the gear release lever. 

3.  Use a No. 2 Phillips screwdriver to loosen the 

end-stop set screw on the actuator that is closest 
to the stop gear, and move it in its slot so it is tight 
against the stop gear. (See Figure 5.) 

IMPORTANT: 

Do not remove the end-stop 

set screws, as this could interfere with the actuator’s 
operation. 

4.  Repeat Steps 1 through 3 to set the desired 

maximum rotation position. 

5.  Tighten both end-stop set screws to a minimum of 

25 lb

∙in (2.8 N∙m). 

6.  Turn the actuator coupler and the damper shaft to 

the minimum rotation position. 

Setup and Adjustments 

Direction of Action 

In the Direct Acting (DA) mode, a minimum control 
signal drives the actuator to the full CCW position, and 
a maximum control signal drives it fully CW. For 
Reverse Acting (RA) operation, a minimum control 
signal drives the actuator to the full CW position, and a 
maximum control signal drives it fully CCW. To set an 
actuator for RA, proceed to the appropriate section for 
the actuator model. 

Floating Application:

 

AGx and IGx Models 

For CW rotation and RA operation, apply 24 VAC to 
the Common (COM) and CW Terminals. For CCW 
rotation and DA operation, apply 24 VAC to the COM 
and CCW Terminals. (See Figure 6.) 

CW

COM

CCW

 

Figure 6: Direction of Action on 

AGx and IGx Model

 

On/Off Application: IGx Model Only 

Drive the IGx model as an On/Off actuator by wiring 
continuous 24 VAC power to the COM and 
CW Terminals. At the same time, command the 
actuator to open by powering the CCW Terminal with 
24 VAC. To drive the actuator back to the full CW 
position, remove the 24 VAC signal from the CCW 
Terminal. 

Содержание M9106 Series

Страница 1: ... alarme ou des dispositifs de sécurité ou de limitation ayant une fonction d avertissement ou de protection en cas de défaillance ou de dysfonctionnement du M9106 xGx 2 Series actuator Parts Included M9106 xGx 2 actuator M9000 160 anti rotation bracket two No 12 24 x 1 2 in self tapping hex washer head screws spade terminals Special Tools Needed drill with a 3 16 in No 15 4 57 mm drill bit 5 16 in...

Страница 2: ...hten the mounting screws to avoid stripping the threads 8 Secure the coupler to the shaft using a 5 16 in 8 mm square socket or 3 8 in 10 mm 12 point socket to tighten the coupler set screw against the damper shaft See Figure 1 9 Continue tightening the coupler set screw to achieve a torque of 150 to 180 lb in 17 to 20 N m Note Keep the actuator parallel to the mounting surface while tightening th...

Страница 3: ...river to loosen the end stop set screw on the actuator that is closest to the stop gear and move it in its slot so it is tight against the stop gear See Figure 5 IMPORTANT Do not remove the end stop set screws as this could interfere with the actuator s operation 4 Repeat Steps 1 through 3 to set the desired maximum rotation position 5 Tighten both end stop set screws to a minimum of 25 lb in 2 8 ...

Страница 4: ...tches for the desired rotation time NC2 NO2 C2 C1 NC1 NO1 Time Minutes 1 0 1 5 2 0 5 5 11 0 1 0 Off On Off On Off On A B C Off Off Off Off Off Off On Off On On On On Mode Switch Settings A B C Note The IGA models have Board 1 and the IGC models have both Board 1 and Board 2 Board 1 Board 2 COM CW CCW Off On Figure 8 Mode Switch Settings on IGx Models The 1 1 5 and 2 minute settings are ideal for o...

Страница 5: ...ar or drive time on the motor for the AGx models use a controller and or software that provides a time out function to remove the signal at the end of rotation stall The GGx and IGx models have an auto shutoff to avoid excessive wear or drive time on the motor Through the Conduit Openings Depending on the M9106 model selected one or both conduit openings are used 1 Loosen the cover screw and remov...

Страница 6: ...3 Note At this point the normally closed contact closes and the normally open contact opens See Auxiliary Switches in Figure 10 Switch S2 To change the angle of Switch S2 to 70 refer to Figure 13 and proceed as follows 1 Press and hold the gear release Using the 0 to 90 nodule guides rotate the coupler until the center of the coupler set screw is at 70 2 Rotate Switch S2 CW and align the edge of t...

Страница 7: ... 35 lb in 4 N m Cycles 100 000 full cycles 2 500 000 repositions rated at 53 lb in 6 N m Audible Noise Rating 35 dBA maximum at 1 m Rotation Range Adjustable from 30 to 90 CW or CCW Rotation Time IGx Adjustable with switch settings Factory set for 1 minute See Figure 12 60 90 120 330 or 660 seconds 1 1 5 2 5 5 or 11 min at 60 Hz and 72 108 144 396 or 792 seconds 1 2 1 8 2 4 6 6 or 13 2 minutes at ...

Страница 8: ...s Installation Instructions Building Efficiency 507 E Michigan Street Milwaukee WI 53202 Metasys and Johnson Controls are registered trademarks of Johnson Controls Inc All other marks herein are the marks of their respective owners 2014 Johnson Controls Inc ...

Отзывы: