background image

 

Installation Instructions 

M9106-xGx-2 

 

Issue Date 

June 30, 2014 

 
 

©  2014 Johnson Controls, Inc.

 

1

 

  Part No. 34-636-1085, Rev. D 

www.johnsoncontrols.com 

M9106-xGx-2 Series Electric 

Non-Spring Return Actuators

 

Installation 

IMPORTANT: 

Use this M9106-xGx-2 Series 

actuator only as an operating control. Where failure 
or malfunction of the this M9106-xGx-2 actuator 
could lead to personal injury or property damage to 
the controlled equipment or other property, 
additional precautions must be designed into the 
control system. Incorporate and maintain other 
devices, such as supervisory or alarm systems or 
safety or limit controls, intended to warn of or protect 
against failure or malfunction of the M9106-xGx-2 
Series actuator. 

Utiliser ce M9106-xGx-2 Series actuator uniquement 
en tant que dispositif de contrôle de fonctionnement. 
Lorsqu'une défaillance ou un dysfonctionnement du 
M9106-xGx-2 actuator risque de provoquer des 
blessures ou d'endommager l'équipement contrôlé 
ou un autre équipement, la conception du système 
de contrôle doit intégrer des dispositifs de protection 
supplémentaires. Veiller dans ce cas à intégrer de 
façon permanente d'autres dispositifs, tels que des 
systèmes de supervision ou d'alarme, ou des 
dispositifs de sécurité ou de limitation, ayant une 
fonction d'avertissement ou de protection en cas de 
défaillance ou de dysfonctionnement du  
M9106-xGx-2 Series actuator. 

Parts Included 

 

M9106-xGx-2 actuator 

 

M9000-160 anti-rotation bracket 

 

two No. 12-24 x 1/2 in. self-tapping hex 
washer-head screws 

 

spade terminals 

Special Tools Needed 

 

drill with a 3/16 in. (No. 15, 4.57 mm) drill bit 

 

5/16 in. (8 mm) square socket or 3/8 in.(10 mm) 
12-point socket 

 

wire/terminal crimper 

Mounting 

The actuators are not position sensitive, and may be 
mounted in any convenient orientation. They may be 
installed on a 3/8 to 1/2 in. (10 to 12.7 mm) round shaft 
or a 3/8 in. (10 mm) square shaft, 1.7 in. (43 mm) or 
longer. If the shaft is less than 1.7 in. (43 mm), install 
an extension recommended by the damper 
manufacturer. 

To mount the actuator, proceed as follows: 

1.  Press and hold the gear release lever, and rotate 

the coupler to the 0 or 90° position. Release the 
gear release lever. (See Figure 1.) 

90

0

60

30

0

90

30

60

Anti-rotation

Bracket

Coupler

Set Screw

Shaft

Center

Coupler

A

Damper

Frame

or Duct

Gear
Release

“A” is the distance from the center of the holes in 
the anti-rotation bracket to the center of the shaft.
(See Table 1.)

Note:

 

Figure 1: Mounting Positions 

Table 1: Distances from the Anti-rotation 
Bracket to the Shaft Center 

Shaft Diameter 

1/2 in. 

3/8 in. 

“A” Dimensions 

5-1/8 in. 

5-1/16 in. 

(See Figure 1.) 

130 mm 

128 mm 

 

Содержание M9106 Series

Страница 1: ... alarme ou des dispositifs de sécurité ou de limitation ayant une fonction d avertissement ou de protection en cas de défaillance ou de dysfonctionnement du M9106 xGx 2 Series actuator Parts Included M9106 xGx 2 actuator M9000 160 anti rotation bracket two No 12 24 x 1 2 in self tapping hex washer head screws spade terminals Special Tools Needed drill with a 3 16 in No 15 4 57 mm drill bit 5 16 in...

Страница 2: ...hten the mounting screws to avoid stripping the threads 8 Secure the coupler to the shaft using a 5 16 in 8 mm square socket or 3 8 in 10 mm 12 point socket to tighten the coupler set screw against the damper shaft See Figure 1 9 Continue tightening the coupler set screw to achieve a torque of 150 to 180 lb in 17 to 20 N m Note Keep the actuator parallel to the mounting surface while tightening th...

Страница 3: ...river to loosen the end stop set screw on the actuator that is closest to the stop gear and move it in its slot so it is tight against the stop gear See Figure 5 IMPORTANT Do not remove the end stop set screws as this could interfere with the actuator s operation 4 Repeat Steps 1 through 3 to set the desired maximum rotation position 5 Tighten both end stop set screws to a minimum of 25 lb in 2 8 ...

Страница 4: ...tches for the desired rotation time NC2 NO2 C2 C1 NC1 NO1 Time Minutes 1 0 1 5 2 0 5 5 11 0 1 0 Off On Off On Off On A B C Off Off Off Off Off Off On Off On On On On Mode Switch Settings A B C Note The IGA models have Board 1 and the IGC models have both Board 1 and Board 2 Board 1 Board 2 COM CW CCW Off On Figure 8 Mode Switch Settings on IGx Models The 1 1 5 and 2 minute settings are ideal for o...

Страница 5: ...ar or drive time on the motor for the AGx models use a controller and or software that provides a time out function to remove the signal at the end of rotation stall The GGx and IGx models have an auto shutoff to avoid excessive wear or drive time on the motor Through the Conduit Openings Depending on the M9106 model selected one or both conduit openings are used 1 Loosen the cover screw and remov...

Страница 6: ...3 Note At this point the normally closed contact closes and the normally open contact opens See Auxiliary Switches in Figure 10 Switch S2 To change the angle of Switch S2 to 70 refer to Figure 13 and proceed as follows 1 Press and hold the gear release Using the 0 to 90 nodule guides rotate the coupler until the center of the coupler set screw is at 70 2 Rotate Switch S2 CW and align the edge of t...

Страница 7: ... 35 lb in 4 N m Cycles 100 000 full cycles 2 500 000 repositions rated at 53 lb in 6 N m Audible Noise Rating 35 dBA maximum at 1 m Rotation Range Adjustable from 30 to 90 CW or CCW Rotation Time IGx Adjustable with switch settings Factory set for 1 minute See Figure 12 60 90 120 330 or 660 seconds 1 1 5 2 5 5 or 11 min at 60 Hz and 72 108 144 396 or 792 seconds 1 2 1 8 2 4 6 6 or 13 2 minutes at ...

Страница 8: ...s Installation Instructions Building Efficiency 507 E Michigan Street Milwaukee WI 53202 Metasys and Johnson Controls are registered trademarks of Johnson Controls Inc All other marks herein are the marks of their respective owners 2014 Johnson Controls Inc ...

Отзывы: