North American Electrical Box

To mount the North American Electrical Box:

1.

Remove the Display panel from the device by 
gently pressing on the panel and pulling the front 
panel outward (Figure 3). 

2.

Select a mounting location.

3.

Pull the power and network communication wires 
until they extend 6 in. (152 mm) from the electrical 
box.

4.

Pull the power and network communication wires 
through the wire exit hole (Figure 4).

5.

Position the base plate on the electrical box.

6.

Mount the base plate using the screws provided

 

with the electrical box.

7.

Connect the power and network communication 
wires. See th

Wiring

 section for more information.

8.

Reattach the front panel to the base plate by 
pressing gently on the Display until the panel clicks 
into place.

European Electrical Box

Follow the steps in the 

North American Electrical Box

 

section.

DIN Rail

To mount on a DIN rail:

1.

Remove the Display panel from the device by 
gently pressing on the panel and pulling the front 
panel outward (Figure 3).

2.

Break off the tabs to expose the DIN rail channels 
in the base plate (Figure 5).

3.

Break off the cover from the exit hole (Figure 5).

4.

Pull the power and network communication wires 
through the wire exit hole

5.

Slide the back plate onto the DIN rail (Figure 6).

Figure 3: Removing the Surface Mount 

Casing

FI

G

: C

as

in

g

Figure 4: Mounting Screw Holes

FI

G

: ho

les

3

3

2

4

4

2

3

3

1. Wire exit hole

2. Mounting screw holes for 2x4 electrical boxes
3. Mounting screw holes for 4x4 electrical boxes

4. Mounting screw holes for 1/4 DIN electrical boxes

1

 

Break-off tabs for

Din Rail mounting

Wire exit hole 

break-off cover

 

Figure 5: DIN Rail Installation – Break Off

Figure 6: DIN Rail Mounted

FI

G

: d

in

_

ra

il

Содержание LN-DSWSC1-0

Страница 1: ...terference when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to ...

Страница 2: ...ox and DIN Rail Figure 2 Flush Mount Casing Dimensions 1 4754 in 37 475 mm 0 1813 in 4 605 mm 6 0000 in 152 4 mm 6 0000 in 152 4 mm 5 4500 in 138 43 mm 5 4500 in 113 03 mm Ø0 1540 in 3 91 mm 4 8086 in 122 13 mm 4 8086 in 122 13 mm 1 1543 in 29 31 mm 0 5000 in 12 7 mm 1 0000 in 25 4 mm 0 0800 in 2 032 mm BACK VIEW BOTTOM VIEW FRONT VIEW SIDE VIEW FIG flush_mount ...

Страница 3: ...il the panel clicks into place European Electrical Box Follow the steps in the North American Electrical Box section DIN Rail To mount on a DIN rail 1 Remove the Display panel from the device by gently pressing on the panel and pulling the front panel outward Figure 3 2 Break off the tabs to expose the DIN rail channels in the base plate Figure 5 3 Break off the cover from the exit hole Figure 5 4...

Страница 4: ...s 8 Reattach the front panel to the base plate by pressing gently on the display until the panel clicks into place Location Considerations For proper installation and subsequent operation of the Display controller follow these recommendations Allow for proper clearance of device casing wiring terminals and service pin for easy access hardware configuration and maintenance Record the Neuron ID numb...

Страница 5: ...ON communication wire is polarity insensitive and can be laid out in either bus star loop or free topology Connect both wires to the NET terminals of the controller If you are inserting multiple wires in the terminals properly twist wires together prior to inserting them in the terminal connectors Figure 11 Note For additional information about network topology and wire length restrictions refer t...

Страница 6: ...here are two methods to obtain the Service Pin number To locate the Neuron ID number perform one of the following procedures 1 Manual entry The Neuron ID address and bar code are located on either the top panel of the device surface and DIN rail models or inside the casing of the device flush mount models 2 Service Pin Press the Service Pin on the device to broadcast the Neuron ID on the LONWORKS ...

Страница 7: ... length to verify it does not exceed the specifications Wire type Check the wire type to verify it meets the specifications Ensure you are using unshielded wire Network wiring problem Verify the wire connections are correct Absent or incorrect network termination Check the terminations Incorrect or broken terminations make the communication integrity dependent upon a device s position on the netwo...

Страница 8: ...8 Kbps Status Indicator Green LEDs on outputs Communication Jack Input 1 8 in 3 5 mm Enclosure Material ABS Resin Color Off White Dimension FMT 6 in x 6 in x 1 48 in 151 x 151 x 38 mm Dimension SMT 4 57 in x 4 57 in x 1 48 in 116 x 116 x 38 mm Shipping Weight FMT 0 88 lb 0 40 kg Liquid Crystal Display LCD Type Backlit Definition 128 x 128 pixels Display Area 2 1 x 2 1 in 53 x 53 mm Screen Saver Cu...

Отзывы: