Safety Features – CXM/DXM Controls, Cont’d.

Unit Performance-UPS:

 The UPS feature indicates when 

the heat pump is operating inefficiently. A UPS condition 

exists when:

a.  In heating mode with compressor energized, LT2 is 

greater than 125°F [52°C] for 30 continuous seconds, 

or:

b.  In cooling mode with compressor energized, LT1 is 

greater than 125°F [52°C] for 30 continuous seconds, 

or:

c.  In cooling mode with compressor energized, LT2 is 

less than 40°F [4.5°C] for 30 continuous seconds. 

If a UPS condition occurs, the control will immediately go 

to UPS warning. The status LED will remain on as if the 

control is in normal mode. Outputs of the control, exclud-

ing LED and alarm relay, will NOT be affected by UPS. 

The UPS condition cannot occur during a compressor off 

cycle. During UPS warning, the alarm relay will cycle on 

and off. The cycle rate will be “on” for 5 seconds, “off” for 

25 seconds, “on” for 5 seconds, “off” for 25 seconds, etc.

UPS warning code = 8

Swapped LT1/LT2 thermistors: 

During test mode, the 

control monitors to see if the LT1 and LT2 thermistors are 

in the appropriate places. If the control is in test mode, the 

control will lockout with code 9 after 30 seconds if:

a.  The compressor is on in the cooling mode and the LT1 

sensor is colder than the LT2 sensor, or:

b.  The compressor is on in the heating mode and the 

LT2 sensor is colder than the LT1 sensor.

Swapped LT1/LT2 thermistor code = 9.

ESD (DXM only):

 The ESD (Emergency Shut Down) mode 

can be enabled from an external common signal to termi-

nal ESD to shut down the unit. The green status light will 

flash code 3 when the unit is in ESD mode. 

ESD mode = code 3 (green “status” LED)

CXM/DXM CONTROLS

Diagnostic Features -

 The LED on the CXM board advises 

the technician of the current status of the CXM control. 

The LED can display either the current CXM mode or the 

last fault in memory if in test mode. If there is no fault in 

memory, the LED will flash Code 1 (when in test mode).

The green status LED and red fault LED on the DXM 

board advise the technician of the current status of the 

DXM control. The status LED will indicate the current 

mode that the DXM control is in. The fault LED will 

ALWAYS flash a code representing the LAST fault in 

memory. If there is no fault in memory, the fault LED will 

flash Code 1. The yellow test LED will turn on when in 

test mode. 

CAUTION: Do not restart units without 

inspection and remedy of faulting condition. Damage 

may occur.

CXM/DXM Control Start-up Operation -

 The control 

will not operate until all inputs and safety controls are 

checked for normal conditions. The compressor will have 

a 5 minute anti-short cycle delay at power-up. The first 

time after power-up that there is a call for compressor, the 

compressor will follow a 5 to 80 second random start delay. 

After the random start delay and anti-short cycle delay, 

the compressor relay will be energized. On all subsequent 

compressor calls, the random start delay is omitted.

Содержание JRC Series

Страница 1: ...ter Source Heat Pumps Installation Operation Maintenance Supersedes 14805 NOM1 0521 Form 14805 NOM1 1221 97B0035N10 Issue Date December 8 2021 JRC Series Water Source Heat Pump MODELS JRC 0 75 1 5 Ton...

Страница 2: ...ons 13 Ground Water Heat Pump Applications 14 Water Quality Standards 16 Electrical Line Voltage 20 Electrical 21 JRC Series Wiring Diagram Matrix 24 CXM Controls 25 DXM Controls 26 Safety Features CX...

Страница 3: ...Model Type Unit Size None Motorized Water Valve Autoflow 2 25 Gpm Ton Autoflow 3 0 Gpm Ton Motorized Water Valve Afr 2 25 Motorized Water Valve Afr 3 0 Secondary Circulation Pump Water Circuit Options...

Страница 4: ...ce with the regulations of ALL authorities having jurisdiction and MUST conform to all applicable codes It is the responsibility of the installing contractor to determine and comply with ALL applicabl...

Страница 5: ...he system components Remove any dirt or debris found in or on these components Pre Installation Installation Operation and Maintenance instructions are provided with each unit Horizontal equipment is...

Страница 6: ...ze Bottom Return in mm 1 10 x 30 x 1 254 x 762 x 25 1 10 x 36 x 1 254 x 914 x 25 Front Return In mm 1 7 x 29 5 x 1 8 178 x 749 x 3 2 1 7 x 35 5 x 1 8 178 x 902 x 3 2 Unit Size Bottom Return Std 5 Base...

Страница 7: ...ecure the subbase in place 6 Remove subbase shipping support bracket and discard 7 Make all necessary electrical connections as described in the Electrical Wiring section of this manual Consult the wi...

Страница 8: ...tly Horizontal runs of condensate hose should be pitched downward 1 4 inch minimum for every foot 10 mm per 46 cm of hose Avoid low points because dirt collects in these areas and may cause blockage I...

Страница 9: ...tional Motorized Water Valve 1 75 44 Out In Water Connections 1 2 FPT 2 25 57 In Out 11 25 286 2 00 51 1 50 38 8 00 Min 203 2 25 57 5 8 15 9 ID Vinyl Hose 8 00 Min 203 Water Connections 1 2 FPT 11 25...

Страница 10: ...D Vinyl Hose Optional Motorized Water Valve Optional Autoflow Valve Water Connections 5 8 15 9 OD Copper 1 2 FPT or 1 2 MPT Optional isconnect Box unted to cabinet not chassis Optional Motorized Water...

Страница 11: ...e or pipe joint compound that is applied Maximum allowable torque for brass fittings is 30 ft lbs 41 N m If a torque wrench is not available tighten finger tight plus one quarter turn Tighten steel fi...

Страница 12: ...enoid valve for use in variable speed pumping systems may also be included in the hose kit The piping system should be flushed to remove dirt piping chips and other foreign material prior to operation...

Страница 13: ...to assist the contractor in installing trouble free ground loops These instructions are recommendations only State provincial and local codes MUST be followed and installation MUST conform to ALL app...

Страница 14: ...the pH 7 5 and the calcium hardness is less than 100 ppm scaling potential is low If this method yields numbers out of range of those listed the Ryznar Stability and WARNING Polyolester Oil commonly...

Страница 15: ...re is constantly varying two pressure gauges may be needed Adjust the valve until the desired flow of 1 5 to 2 gpm per ton 2 0 to 2 6 l m per kW is achieved A second method of flow control requires a...

Страница 16: ...l l e c a i r e t c a B Sulfate reducing 0 0 0 0 L m s l l e c a i r e t c a b Suspended Solids 0 1 0 1 0 1 0 1 m p p S S T Earth Ground Resistance 0 s m h O Consult NEC local electrical codes for gro...

Страница 17: ...ed 7 If water temperature is expected to fall below 40 F antifreeze is required Refer to the heat pump IOM for the correct solution ratios to prevent freezing Hydrogen Sulfide has an odor of rotten eg...

Страница 18: ...esistance measured should be zero Ohms The NEC allows a resistance to ground up to 20 Ohms Any resistance above zero indicates a poor earth ground which may be the result of a hot neutral line or that...

Страница 19: ...If higher than 500mV electrolysis will occur and corrosion will result If voltage is measured the cause is a high resistance earth ground or current on the neutral conductor Remedial measures should...

Страница 20: ...open the power supply disconnect switch and secure it in an open position during installation CAUTION Use only copper conductors for field installed electrical wiring Unit terminals are not designed...

Страница 21: ...0 5 N A 4 20 5 13 15 0 8 5 00 5 93 15 E 265 60 1 239 292 3 5 22 0 0 4 N A 3 90 4 78 15 0 7 4 60 5 48 15 JRC12 A 115 60 1 104 126 9 5 50 0 1 0 N A 10 50 12 88 20 1 4 11 90 14 28 20 G 208 230 60 1 197 2...

Страница 22: ...ld supplied and field installed B only required with systems employing remote mounted thermostats Figure 3 Typical Field Installed Wiring WARNING To avoid possible injury or death due to electrical sh...

Страница 23: ...e 18 AWG wire Wire the appropriate thermostat as shown in Figure 7 to the low voltage terminal strip on the CXM or DXM control board Practically any heat pump thermostat will work with JRC WSHP units...

Страница 24: ...ard JRC DIGIT 8 L N CXM w MPC JRC DIGIT 8 M P DXM w MPC JRC DIGIT 8 D S DXM Standard S1 S1 S1 S1 S2 S2 1 2 3 4 5 OFF ON 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 OFF ON OFF ON OFF ON O...

Страница 25: ...ted to R Clipped AL2 dry contact no connection DIP Switches Note In the following field configuration options DIP switches should only be changed when power is removed from the CXM control DIP switch...

Страница 26: ...e control is attempting a retry of a fault the status LED will slow flash slow flash one flash every 2 seconds to indicate the control is in the process of retrying Field Configuration Options Note In...

Страница 27: ...able 7c Accessory DIP Switch Settings 1 3 Thermostat type heat pump or heat cool DIP 1 3 provides selection of thermostat type Heat pump or heat cool thermostats can be selected When in heat cool mode...

Страница 28: ...he compressor contactor coil The high pressure fault recognition is immediate does not delay for 30 continuous seconds before de energizing the compressor High pressure lockout code 2 Example 2 quick...

Страница 29: ...mode and the LT2 sensor is colder than the LT1 sensor Swapped LT1 LT2 thermistor code 9 ESD DXM only The ESD Emergency Shut Down mode can be enabled from an external common signal to termi nal ESD to...

Страница 30: ...30 120 1 49 20 90 6 7 32 Requires optional insulation package when operating below the dew point Requires antifreeze optional insulation package and jumper clipped UNIT OPERATING LIMITS All JRC Model...

Страница 31: ...f water or other equivalent approved cleaning agent Reset the boiler to raise the loop temperature to 100 F 38 C Circulate the solution for a minimum of 8 to 24 hours At the end of this period shut of...

Страница 32: ...promotes longevity of hoses and fittings see Table 3 System flushing Verify that all hoses are connected end to end when flushing to insure that debris bypasses the unit heat exchanger water valves an...

Страница 33: ...urn thermostat to OFF position A hissing noise indicates proper functioning of the reversing valve 6 Allow five 5 minutes between tests for pressure to equalize before beginning heating test a Adjust...

Страница 34: ...57 8 13 8 13 8 13 9 14 8 13 7 12 16 18 12 14 8 10 18 24 18 24 18 24 164 174 165 175 167 177 372 392 375 395 379 399 17 22 18 23 19 24 13 18 13 18 13 18 14 5 16 5 11 2 13 2 7 9 9 9 35 41 35 41 36 42 11...

Страница 35: ...9 14 9 14 9 14 11 16 9 14 6 11 15 8 17 8 14 9 16 9 14 16 18 24 18 24 18 24 164 174 165 175 167 177 372 392 375 395 379 399 17 22 18 23 19 24 13 18 13 18 13 18 14 5 16 5 11 2 13 2 7 9 9 9 35 41 35 41 3...

Страница 36: ...and data entries before the system is put into full operation Temperatures F or C Antifreeze __________________ Pressures PSIG or kPa Type __________________ Cooling Mode Heating Mode Return Air Tempe...

Страница 37: ...erating conditions and be replaced when necessary Units should never be operated without a filter Washable high efficiency electrostatic filters when dirty can exhibit a very high pressure drop for th...

Страница 38: ...e of unit toward outlet Poor venting Check vent location X Moisture on sensor Check for moisture shorting to air coil X X Plugged air filter Replace air filter x X Restricted Return Air Flow Find and...

Страница 39: ...ck fan motor operation and air flow restrictions Too high of external static Check static vs blower table X Reduced or no water flow in cooling Check pump operation or valve operation setting Check wa...

Страница 40: ...HWG HEATING CYCLE ANALYSIS PSI SAT PSI SAT F F AIR COIL F F FP2 HEATING LIQUID LINE F EXPANSION VALVE AIR COIL F F PSI SAT PSI SAT F F F F WATER IN WATER OUT PSI PSI F F WATER IN WATER OUT PSI PSI Use...

Страница 41: ...JRC Series Rev Decem b er 8 2021 TH E SMART SOLUTION FOR ENERGY EFFICI E N CY Installation Operation Maintenance 41 Notes...

Страница 42: ...WATE R SOURCE HEAT PUMPS JRC Series Rev Decemb er 8 2021 Installation Operation Maintenance 42 Notes...

Страница 43: ...JRC Series Rev Decem b er 8 2021 TH E SMART SOLUTION FOR ENERGY EFFICI E N CY Installation Operation Maintenance 43 Notes...

Страница 44: ...o Subordinate 08 19 20 Created Johnson Controls works continually to improve its products As a result the design and specifications of each product at the time for order may be changed without notice...

Отзывы: