P5–Exhaust Protection
Explanation of
error
Cause: the exhaust sensor detects that the exhaust temperature is too
high and triggers the exhaust protection shutdown.
Inspection path: system pressure
→
indoor / outdoor air inlet
→
exhaust sensor
→
external panel
Tools required
for inspection
Multimeter, pressure gauge, regular 50K
Ω
exhuast sensor (25
℃
)
Frequent
problematic part
Indoor coil sensor
Inspection
procedure and
key points
1.
Check if the system pressure is low, if is, usually it the shortage of
liquid that leads to excessive exhasut temperature protection;
2.
Check whether the indoor/outdoor air inlet is blocked, such as
whether the evaporator or condenser is dirty or whether the filter is
dirty or blocked and if inlet is affected, reove the shield.
3.
Check whether the air volume at the tuyere is too small, observe
whether the internal fan blades are dirty blocked, and if dirty blocked
blades are found, clean the blades.
4.
Measure the resistance drift of the exhaust sensor with a
multimeter at ambient temperature.