IOM2710 and IOM3710 Input/Output Modules Installation Instructions

1

Applications

The Input/Output Module (IOM) 2710 and IOM3710 are 
members of the Metasys® system Field Equipment 
Controller (FEC) family. The IOM controller provides 
increased capacity to larger FEC applications when 
used on the Sensor-Actuator (SA) Bus. The IOM 
controller can also be used on the Field Controller (FC) 
Bus to connect additional I/O points to the system.

North American Emissions Compliance

United States

Canada

Installation

Observe the following guidelines when installing the 
IOM controller:

Transport the IOM controller in the original 
container to minimize vibration and shock damage 
to the IOM.

Do not drop the IOM controller or subject it to 
physical shock.

Materials and Special Tools Needed

You need either of the following items to install the IOM 
controller:

three fasteners appropriate for the mounting 
surface (#8 screws or M4 screws)

one 20.3 cm (8 in.) or longer piece of DIN rail and 
appropriate hardware for mounting the DIN rail

Mounting

Follow these guidelines when mounting an IOM 
controller:

Ensure that the mounting surface can support the 
IOM controller and any user-supplied enclosure.

Mount the IOM controller in the proper orientation. 
See th

Wall Mount Applications

 an

DIN Rail 

Mount Applications

 sections.

Mount the IOM controller on an even surface 
whenever possible.

Use shims or washers to mount the unit securely 
on the mounting surface.

Mount the IOM controller in areas free of corrosive 
vapors and observe the environmental limitations 
listed in the 

Technical Specifications

 section. 

IMPORTANT:

In Metasys system smoke control 

applications, use only the IOM2710 and IOM3720 
models that are UL Listed, UUKL 864 Listed, Smoke 
Control Equipment. See 

Repair Information

 on page 

8 for UUKL 864 Listed IOM2710 and IOM3710 
models. For Metasys system smoke control 
applications, you must refer to the 

Metasys System 

UL 864 UUKL Ninth Edition Smoke Control System 
Technical Bulletin (LIT-12011252)

 for detailed 

requirements and procedures for installing and 
operating UUKL 864 Listed Metasys system 
devices. Failure to meet the requirements or follow 
the procedures in the 

Metasys System UL 864 

UUKL Ninth Edition Smoke Control System 
Technical Bulletin (LIT-12011252)

 can void the 

UUKL 864 listing for Smoke Control Equipment.

This equipment has been tested and found to 
comply with the limits for a Class A digital device 
pursuant to Part 15 of the FCC Rules. These limits 
are designed to provide reasonable protection 
against harmful interference when this equipment is 
operated in a commercial environment. This 
equipment generates, uses, and can radiate radio 
frequency energy and, if not installed and used in 
accordance with the instruction manual, may cause 
harmful interference to radio communications. 
Operation of this equipment in a residential area is 
likely to cause harmful interference, in which case 
the user will be required to correct the interference 
at his/her own expense.

This Class (A) digital apparatus meets all the 
requirements of the Canadian Interference-Causing 
Equipment Regulations.

Cet appareil numérique de la Classe (A) respecte 
toutes les exigences du Règlement sur le matériel 
brouilleur du Canada.

IOM2710 and IOM3710 Input/Output Modules

Installation Instructions

MS-IOM2710-0, MS-IOM3710-0

Part No. 24-10144-17, Rev. G

Release  5.0

Issued January 4, 2010

Supersedes October 6, 2008

Содержание IOM2710

Страница 1: ...In Metasys system smoke control applications use only the IOM2710 and IOM3720 models that are UL Listed UUKL 864 Listed Smoke Control Equipment See Repair Information on page 8 for UUKL 864 Listed IO...

Страница 2: ...FAULT POWER ADDRESS ON 15V 5V IN 1 ICOM 1 IN 2 ICOM 2 15V 5V IN 3 ICOM 3 IN 4 ICOM 4 UNIVERSAL COM COM SA PWR COM HOT OUT 7 OCOM 7 OUT 8 OCOM 8 OUT 5 OCOM 5 OUT 6 OCOM 6 OUT 4 NO OCOM 4 OUT 4 NC OUT 3...

Страница 3: ...s connected to the FC Bus of a Network Automation Engine NAE or Network Control Engine NCE wire the FC Bus in a daisy chain IMPORTANT Do not overtighten the mounting screws Overtightening the screws m...

Страница 4: ...Figure 7 Figure 5 FC Bus Terminal Block Wiring Stranded 3 Wire Twisted Shielded Cable Isolated Shield Connection Terminal _ COM SHLD To Next Device on the FC Bus Segment FC Bus Terminal Block Plugs FI...

Страница 5: ...only B Analog Input Resistive Mode Accepts 0 600k ohm input signal Internal 12 V 15k ohm Pullup A Binary Input Dry Contact Maintained Mode 1 s minimum pulse width 0 5 Hz at 50 duty cycle Internal 12...

Страница 6: ...M Provides SA Bus communication network Daisy chained 366 m 1 200 ft maximum length 0 6 to 1 5 mm2 18 to 24 AWG 22 AWG Recommended FC Bus1 COM Provides FC Bus communication network Daisy chained 1 524...

Страница 7: ...lications Table 2 Wire Gauge and Length Guidelines Guideline Cable Size Maximum Length Assumptions A 1 5 mm 18 AWG 457 2 m 1 500 ft 100 mV maximum voltage drop 0 8 mm 20 AWG 297 2 m 975 ft 0 6 mm 22 A...

Страница 8: ...tches Set to 21 FIG fec_dip_swtch 128 64 32 16 8 4 2 1 ON Note Switch 128 is used to enable or disable an FEC for wireless operation Figure 10 EOL Switch Positions FIG EOL_Swtch EOL ON Position EOL Of...

Страница 9: ...VA maximum plus all BO and Configurable Output loads Ambient Conditions Operating 0 to 50 C 32 to 122 F 10 to 90 RH noncondensing Storage 40 to 70 C 40 to 158 F 10 to 90 RH noncondensing Terminations...

Страница 10: ...EC in accordance with EN 61000 6 3 2001 Generic Emission Standard for Residential and Light Industry and EN 61000 6 2 2001 Generic Immunity Standard for Heavy Industrial Environment and the Low Voltag...

Отзывы: