IOM2710 and IOM3710 Input/Output Modules Installation Instructions

6

Relay 
Output 
Control

OUT NO 

n

Normally Open Contact
Connects OCOM to OUT NO when activated.
240 VAC maximum voltage
1/3 hp 125 VAC, 1/2 hp 250 VAC
400 VA Pilot Duty @ 240 VAC
200 VA Pilot Duty @ 120 VAC
3 A Noninductive 24-240 VAC

OCOM 

n

The relay signal common; isolated from other terminal 
commons, including Relay Output terminal commons.

OUT NC 

n

Normally Closed Contact
Connects OCOM to OUT NC when activated.
240 VAC maximum voltage
1/3 hp 125 VAC, 1/2 hp 250 VAC
400 VA Pilot Duty @ 240 VAC
200 VA Pilot Duty @ 120 VAC
3 A Non-inductive 24-240 VAC

SA/FC Bus 
Port

2,3

SA/FC Bus

Provides SA Bus communication network
RJ-12 6-position modular connector

30.5 m (100 ft) maximum length 
phone cord

SA Bus

3

+
-
COM

Provides SA Bus communication network.

Daisy-chained
366 m (1,200 ft) maximum length

0.6 to 1.5 mm

2

 (18 to 24 AWG)

[22 AWG Recommended]

FC Bus

1

+
-
COM

Provides FC Bus communication network.

Daisy-chained
1,524 m (5,000 ft) maximum length

0.6 to 1.5 mm

2

 (18 to 24 AWG)

[22 AWG Recommended]

SHLD

Provides an optional shield connection.

24~ Power

Hot

AC Supply Input
Supply 20-30 VAC (Nominal 24 VAC)

16 AWG

COM

The 24~ Power common; isolated from all other terminal 
commons.

1.

The terminal block column displays all the points for the IOM3710 model.

2.

The SA Bus and the SA/FC Bus are daisy-chained internally.

3.

The SA Bus and FC Bus specifications in this table are for MS/TP bus communications at 38.4k baud. For more 
information, refer to the 

MS/TP Communications Bus Technical Bulletin (LIT-12011034)

.

Table 1:  IOM2710 and IOM3710 Controller Wiring List (Part 2 of 2)

Terminal 
Block

1

Terminal 
Labels

Function and Electrical Ratings/Requirements

Wiring Requirements 
(See Table 2 for A, B, or C.)

Содержание IOM2710

Страница 1: ...In Metasys system smoke control applications use only the IOM2710 and IOM3720 models that are UL Listed UUKL 864 Listed Smoke Control Equipment See Repair Information on page 8 for UUKL 864 Listed IO...

Страница 2: ...FAULT POWER ADDRESS ON 15V 5V IN 1 ICOM 1 IN 2 ICOM 2 15V 5V IN 3 ICOM 3 IN 4 ICOM 4 UNIVERSAL COM COM SA PWR COM HOT OUT 7 OCOM 7 OUT 8 OCOM 8 OUT 5 OCOM 5 OUT 6 OCOM 6 OUT 4 NO OCOM 4 OUT 4 NC OUT 3...

Страница 3: ...s connected to the FC Bus of a Network Automation Engine NAE or Network Control Engine NCE wire the FC Bus in a daisy chain IMPORTANT Do not overtighten the mounting screws Overtightening the screws m...

Страница 4: ...Figure 7 Figure 5 FC Bus Terminal Block Wiring Stranded 3 Wire Twisted Shielded Cable Isolated Shield Connection Terminal _ COM SHLD To Next Device on the FC Bus Segment FC Bus Terminal Block Plugs FI...

Страница 5: ...only B Analog Input Resistive Mode Accepts 0 600k ohm input signal Internal 12 V 15k ohm Pullup A Binary Input Dry Contact Maintained Mode 1 s minimum pulse width 0 5 Hz at 50 duty cycle Internal 12...

Страница 6: ...M Provides SA Bus communication network Daisy chained 366 m 1 200 ft maximum length 0 6 to 1 5 mm2 18 to 24 AWG 22 AWG Recommended FC Bus1 COM Provides FC Bus communication network Daisy chained 1 524...

Страница 7: ...lications Table 2 Wire Gauge and Length Guidelines Guideline Cable Size Maximum Length Assumptions A 1 5 mm 18 AWG 457 2 m 1 500 ft 100 mV maximum voltage drop 0 8 mm 20 AWG 297 2 m 975 ft 0 6 mm 22 A...

Страница 8: ...tches Set to 21 FIG fec_dip_swtch 128 64 32 16 8 4 2 1 ON Note Switch 128 is used to enable or disable an FEC for wireless operation Figure 10 EOL Switch Positions FIG EOL_Swtch EOL ON Position EOL Of...

Страница 9: ...VA maximum plus all BO and Configurable Output loads Ambient Conditions Operating 0 to 50 C 32 to 122 F 10 to 90 RH noncondensing Storage 40 to 70 C 40 to 158 F 10 to 90 RH noncondensing Terminations...

Страница 10: ...EC in accordance with EN 61000 6 3 2001 Generic Emission Standard for Residential and Light Industry and EN 61000 6 2 2001 Generic Immunity Standard for Heavy Industrial Environment and the Low Voltag...

Отзывы: