IOM2710 and IOM3710 Input/Output Modules Installation Instructions

10

Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.

All other marks herein are the marks of their respective owners. © 2010 Johnson Controls, Inc.

Building Efficiency

507 E. Michigan Street, Milwaukee, WI  53202

Compliance

United States:

UL Listed, File E107041, CCN PAZX, UL 916, Energy Management Equipment;
UL Listed, File S4977, UUKL 864 - 9th Edition, Smoke Control Equipment (MS-IOMx710-0U 
and MS-IOU4710-0U models only)
FCC Compliant to CFR47, Part 15, Subpart B, Class A

Canada:

UL Listed, File E107041, CCN PAZX7, CAN/CSA C22.2 No. 205, Signal Equipment;
Industry Canada Compliant, ICES-003

Europe:

CE Mark, EMC Directive 89/336/EEC, in accordance with EN 61000-6-3 (2001) Generic 
Emission Standard for Residential and Light Industry and EN 61000-6-2 (2001) Generic 
Immunity Standard for Heavy Industrial Environment and the Low Voltage Directive 
73/23/EEC in accordance with EN 60730-1 (1999) Automatic electrical controls for 
household and similar use.

Australia and New Zealand:

C-Tick Mark, Australia/NZ Emissions Compliant

BACnet International:

BACnet Testing Laboratories™ (BTL) 135-2004 Listed BACnet Application Specific 
Controller (B-ASC)

1.

For more information, refer to the 

MS/TP Communications Bus Technical Bulletin (LIT-12011034)

.

The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond these 
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or 
misuse of its products.

IOM2710 and IOM3710 Input/Output Modules  (Part 2 of 2)

Содержание IOM2710

Страница 1: ...In Metasys system smoke control applications use only the IOM2710 and IOM3720 models that are UL Listed UUKL 864 Listed Smoke Control Equipment See Repair Information on page 8 for UUKL 864 Listed IO...

Страница 2: ...FAULT POWER ADDRESS ON 15V 5V IN 1 ICOM 1 IN 2 ICOM 2 15V 5V IN 3 ICOM 3 IN 4 ICOM 4 UNIVERSAL COM COM SA PWR COM HOT OUT 7 OCOM 7 OUT 8 OCOM 8 OUT 5 OCOM 5 OUT 6 OCOM 6 OUT 4 NO OCOM 4 OUT 4 NC OUT 3...

Страница 3: ...s connected to the FC Bus of a Network Automation Engine NAE or Network Control Engine NCE wire the FC Bus in a daisy chain IMPORTANT Do not overtighten the mounting screws Overtightening the screws m...

Страница 4: ...Figure 7 Figure 5 FC Bus Terminal Block Wiring Stranded 3 Wire Twisted Shielded Cable Isolated Shield Connection Terminal _ COM SHLD To Next Device on the FC Bus Segment FC Bus Terminal Block Plugs FI...

Страница 5: ...only B Analog Input Resistive Mode Accepts 0 600k ohm input signal Internal 12 V 15k ohm Pullup A Binary Input Dry Contact Maintained Mode 1 s minimum pulse width 0 5 Hz at 50 duty cycle Internal 12...

Страница 6: ...M Provides SA Bus communication network Daisy chained 366 m 1 200 ft maximum length 0 6 to 1 5 mm2 18 to 24 AWG 22 AWG Recommended FC Bus1 COM Provides FC Bus communication network Daisy chained 1 524...

Страница 7: ...lications Table 2 Wire Gauge and Length Guidelines Guideline Cable Size Maximum Length Assumptions A 1 5 mm 18 AWG 457 2 m 1 500 ft 100 mV maximum voltage drop 0 8 mm 20 AWG 297 2 m 975 ft 0 6 mm 22 A...

Страница 8: ...tches Set to 21 FIG fec_dip_swtch 128 64 32 16 8 4 2 1 ON Note Switch 128 is used to enable or disable an FEC for wireless operation Figure 10 EOL Switch Positions FIG EOL_Swtch EOL ON Position EOL Of...

Страница 9: ...VA maximum plus all BO and Configurable Output loads Ambient Conditions Operating 0 to 50 C 32 to 122 F 10 to 90 RH noncondensing Storage 40 to 70 C 40 to 158 F 10 to 90 RH noncondensing Terminations...

Страница 10: ...EC in accordance with EN 61000 6 3 2001 Generic Emission Standard for Residential and Light Industry and EN 61000 6 2 2001 Generic Immunity Standard for Heavy Industrial Environment and the Low Voltag...

Отзывы: