background image

Table of Contents

6

IFI-WS Installation and Operation Manual – P/N LS10050-000JC-E:A  12/11/2014

3.3.2: Starting and Exiting the Configuration Tool .....................................................................................25
3.3.3: Configuration Tool Layout................................................................................................................26

Figure 3.1 Configuration Tool Layout .................................................................................................26

3.3.4: Monitoring Profiles ...........................................................................................................................27
3.3.5: Color and Sound Configuration.........................................................................................................28
3.3.6: Event Color Coding ...........................................................................................................................28

Table 3.1 Event Icon Color Coding......................................................................................................28

3.3.7: System Options..................................................................................................................................29

Table 3.2 System Options Configuration .............................................................................................29

3.3.8: Control Profiles .................................................................................................................................29

3.3.8.1 Creating Control Profiles..........................................................................................................29
3.3.8.2 Control Profile User Permissions .............................................................................................29

3.4: Adding to an Existing Network ...................................................................................................................30

3.4.1: Importing Network Configuration Data ............................................................................................30
3.4.2: Adding a New Network Connection .................................................................................................30
3.4.3: Adding a Redundant Gateway...........................................................................................................30

3.5: Network Right Click Commands.................................................................................................................31
3.6: Auto-Creation of Screens, Nodes, and Points .............................................................................................32

Figure 3.2 Example of Navigation Tree with Auto-Creation Process..................................................32

3.6.1: Managing the Auto-creation Process.................................................................................................32

Table 3.3 Managing Auto-created Screens ..........................................................................................33

3.7: Autocreating Gateway Point IDs .................................................................................................................33
3.8: Workstation Database Backup and Restore .................................................................................................34

3.8.1: Backing Up the Database ..................................................................................................................34
3.8.2: Restoring a Backed-Up Database ......................................................................................................34

3.9: Macro Commands........................................................................................................................................35
3.10: Custom Icon Recommendations ................................................................................................................36

Table 3.4 Effect on Non-PNG Icon File on Background .....................................................................36
Table 3.5 Effects of Icon Color on Alarm Reporting...........................................................................36

Section 4 Workstation Settings ............................................................................................. 37

4.1: Windows Settings ........................................................................................................................................37

Table 4.1 Windows Settings.................................................................................................................37

4.2: Workstation Settings ....................................................................................................................................38

4.2.1: Options Window Command Buttons.................................................................................................38

Table 4.2 Options Window Command Buttons ...................................................................................38

4.2.2: General Tab .......................................................................................................................................38

Table 4.3 General Tab Settings ............................................................................................................38

4.2.3: User Features Tab..............................................................................................................................40

Table 4.4 User Features Settings ..........................................................................................................40

4.2.4: Event Printer Tab...............................................................................................................................40

Table 4.5 Event Printer Tab Settings....................................................................................................40

4.2.5: Pager/Modem Tab .............................................................................................................................41

Table 4.6 Pager/Modem Tab Settings ..................................................................................................41

4.2.6: Email Tab ..........................................................................................................................................42

Table 4.7 Email Tab Settings ...............................................................................................................42

4.2.7: Output Tab.........................................................................................................................................44

Table 4.8 Output Tab Settings..............................................................................................................44

4.3: Other Settings ..............................................................................................................................................45

4.3.1: Fan Monitoring ..................................................................................................................................45

Section 5 Operation ................................................................................................................ 47

5.1: Login and Log Out.......................................................................................................................................47

5.1.1: Login..................................................................................................................................................47
5.1.2: Log Out..............................................................................................................................................47

5.2: Display Modes .............................................................................................................................................47

5.2.1: Graphics Mode ..................................................................................................................................47

Figure 5.1 Example Graphics Mode Screen.........................................................................................48

Содержание IFI-WS

Страница 1: ...A P N LS10050 000JC E A ECN 14 0859 Document LS10050 000JC E 12 11 2014 IFI WS Installation and Operation Manual Intelligent Fire Integrator IFI WS Installation and Operation Manual ...

Страница 2: ...y not provide adequate warning of a fire Smoke detectors cannot be expected to provide adequate warn ing of fires caused by arson children playing with matches especially in bedrooms smoking in bed and violent explosions caused by escaping gas improper storage of flammable materi als etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a pr...

Страница 3: ...to do so can damage circuits Remove all electronic assemblies prior to any drilling filing reaming or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifi cations verify that they will not interfere with battery trans former and printed circuit board location Do not tighten screw terminals more than 9 in lbs Over tight ening may damage threads ...

Страница 4: ...e any comments or suggestions about our on line help or manuals please e mail us at FireSystems TechPubs honeywell com On Line Help Please include the following information Product name and version number if applicable Topic title The content you think should be corrected improved Detailed suggestions for correction improvement Documents Please include the following information Document part numbe...

Страница 5: ...curity Levels 15 Table 1 4 Security Levels 15 1 9 Field Programmable Settings 15 Table 1 5 UL 864 Field programmable Settings 15 Table 1 6 UL 2572 Field programmable Settings 16 1 10 Compatible Equipment 16 Table 1 7 Compatible Equipment 16 1 11 System Configuration 17 Table 1 8 System Configuration 17 Section 2 Hardware Configuration 19 2 1 System Power 19 2 1 1 Primary and Secondary Power 19 2 1...

Страница 6: ... created Screens 33 3 7 Autocreating Gateway Point IDs 33 3 8 Workstation Database Backup and Restore 34 3 8 1 Backing Up the Database 34 3 8 2 Restoring a Backed Up Database 34 3 9 Macro Commands 35 3 10 Custom Icon Recommendations 36 Table 3 4 Effect on Non PNG Icon File on Background 36 Table 3 5 Effects of Icon Color on Alarm Reporting 36 Section 4 Workstation Settings 37 4 1 Windows Settings ...

Страница 7: ...5 1 When a New Event Occurs 59 Figure 5 9 Example New Event in Progress 59 5 5 2 Protected Premises Control Unit or Proprietary Receiving Unit Event Handling Comparison 60 Table 5 3 Protected Premises Control Unit vs Proprietary Receiving Unit Event Handling 60 Section 6 Data Management 61 6 1 Database Management 61 Table 6 1 Database Management Options 61 6 2 History Manager 62 Figure 6 1 History...

Страница 8: ...y Receiving Unit 70 Figure 7 5 Proprietary Receiving Unit System Example 1 71 Figure 7 6 Proprietary Receiving Unit System Example 2 72 7 3 2 Overview of Event Handling for Proprietary Receiving Unit 73 7 4 Protected Premises Control Unit vs Proprietary Receiving Unit Event Handling 73 Table 7 1 Protected Premises Control Unit vs Proprietary Receiving Unit Comparison 73 ...

Страница 9: ...cted Premises Control Unit the IFI WS support of gateways is limited to a single NFN gateway that is installed and operating on the same PC as the IFI WS The IFI WS is hereinafter referred to as the workstation 1 2 Functionality 1 2 1 System Functions The IFI WS provides the following major functions Displays events by priority New events are displayed in the list based upon their event type prior...

Страница 10: ...Temperature 0 C to 49 C 32 F 120 F Relative Humidity 93 2 non condensing at 32 2 C 90 3 F However it is recommended that this product be installed in an environment with a normal room temperature of 15 27º C 60 80º F Table 1 1 System Limits Limit Feature Maximum Allowed Physical Network Limit Gateways 200 total Logical Network Screen Screens 1000 Devices 100 000 Macros 100 Macro Button 100 NavIcon...

Страница 11: ...ics Printer A graphics printer is a Windows compatible printer that prints what is currently displayed on the workstation s monitor When installing graphics printer drivers be sure to disable bidirectional support and set the graphics mode to raster 1 5 2 Local Event Printer The optional local event printer is a UL 864 listed Windows compatible dot matrix printer that prints all workstation events...

Страница 12: ... Port Settings Port Type Direction Purpose 25 TCP Out SMTP 123 UDP Both SNTP 2004 TCP N A Internal Workstation Plug in Access 2014 TCP Out Connection to DACR Gateway 2017 TCP Out Connection to NFN Gateway 2029 TCP Out Workstation Output Appliances Signs 4016 TCP In Database Import Export Table 1 3 Bandwidth Usage Worst Case Sustained Bandwidth No Gateways Bandwidth Typical 200 3 360 Bytes Sec 26 8...

Страница 13: ...ers Laboratories UL 864 Control Units for Fire Alarm Systems Ninth Edition UL 1076 Proprietary Burglar Alarm Units and Systems Fifth Edition UL 2017 General Purpose Signaling Devices and Systems First Edition UL 2572 Mass Notification Systems First Edition Underwriters Laboratories Canada CAN ULC S527 99 Standard for Control Units for Fire Alarm Systems Second Edition CAN ULC S559 04 Equipment for...

Страница 14: ... UL listing for the IFI WS includes the ability for the workstation to send notifications to alphanumeric pagers These notifications are intended to be transmitted to only a limited number of staff refer to Table 1 1 for details for maintenance purposes and system status reasons This feature is approved by UL as supplementary The UL listing for the IFI WS includes the ability for the workstation t...

Страница 15: ...r Configuration Tool Installation Operation Manual P N 53380 for additional information 1 8 2 UL 2572 Security Levels The IFI WS meets the UL 2572 security levels stated below 1 9 Field Programmable Settings Table 1 4 Security Levels Level Type Level Communication Security 1 Stored Data Security 0 Access Control Security 2 Physical Security 1 Audit Control Security 0 Table 1 5 UL 864 Field program...

Страница 16: ... minutes 0 disables feature 1 20 minutes Table 1 7 Compatible Equipment Equipment Description Monitors MON 22LCDW 22 Wide screen LCD Monitor MON 22LCDW TS Touchscreen 22 Wide screen LCD Monitor MON 42LCDW Touchscreen 42 Wide screen LCD Monitor Monitor electrical ratings 120 VAC 60 Hz 3 5 Amps for both models To remain compliant with UL listing and to meet the Condition of Acceptability the keyboar...

Страница 17: ...terruptible Power Supply R R NFN Gateway See Table 1 7 Any currently UL listed NFN gateway R2 R3 DACR GW JDACR GW Digital Alarm Communicator Receiver Gateway O O NOTIFY IP JNOTIFY IP Live voice paging application O4 O5 LEDSIGN GW JLEDSIGN GW LED sign gateway O O R Required component for functionally minimal system O Optional Notes 1 At least one of the displays listed in Table 1 7 is required for ...

Страница 18: ...Product Overview System Configuration 18 IFI WS Installation and Operation Manual P N LS10050 000JC E A 12 11 2014 ...

Страница 19: ...al Code as well as local codes If available backup power for the workstation must be supplied by the building emergency power source A supervised Uninterruptible Power Supply UPS is required to provide power continuity during the transition period from the primary power source to the emergency power source The UPS must be UL 1481 listed regulated and power limited In Canada backup power for the wo...

Страница 20: ...lass Specifications Connection 1 Power AC Power for Computer Voltage 120 VAC 60 Hz Current 0 6 0 8 amps during normal operation 2 DVI 1 DVI Video 3 USB 3 USB 3 0 Type A Connector 2 Line impedance 90 15 Max distance 40 meters Power limited Supervised 4 USB 2 USB 3 0 Type A Connector 2 Line impedance 90 15 Max distance 40 meters Power limited Supervised 5 LPT Printer Port Not Used 6 VGA VGA Video 7 ...

Страница 21: ...ised Keyboard or Mouse 12 LAN 1 RJ45 2 Line impedance 100 ohm Max distance 328 ft 100 m Power limited Supervised Except for ground faults See Figure 2 2 13 LAN 2 RJ45 2 Used only on stand alone workstations See Figure 2 3 14 Line In 3 5 mm Audio Input 15 Mic 3 5 mm Microphone 16 Speaker Line Out 3 5 mm Audio Output 17 J7 Digital I O Not Used Not Shown USB USB 2 0 Type A Connector on Front of PC 2 ...

Страница 22: ...plicable Use this connection for an IFI WS that will use Ethernet for communications Figure 2 2 LAN Connection For an IFI WS that will not be using Ethernet for communications a single Ethernet patch cable must be plugged in both RJ45 ports to create a loop back between the Ethernet ports Figure 2 3 Stand alone IFI WS Not Used In This Configuration Ethernet Cable Ethernet Patch Cable ...

Страница 23: ...the locking front door is set to the OFF O position 4 Remove the two screws shown below and retain for later use 5 Cut the end off of the factory supplied AC power cord and remove outer insulation 6 Plug the power cord into the IFI WS computer s AC power receptacle 7 Feed the cut end of the power cord through the hole in the power cord locking bracket PCLB reinstall the two screws removed earlier ...

Страница 24: ...connecting electrical components The IFI WS computer s main power switch must be in the OFF position until installation of the entire IFI WS system is complete and ready for testing Before performing any work on a fire alarm system 1 Notify the fire department and the central alarm receiving station if transmitting alarm conditions 2 Notify the people occupying the facility about the impending tes...

Страница 25: ...ge an existing user s password or to add a user and their password The factory defined user Admin has such a security option The workstation software application s factory defined Administrator s password is admin The factory defined Administrator profile cannot be deleted 3 3 Configuration Tool 3 3 1 Overview The configuration tool is used to customize the workstation s graphical user interface G...

Страница 26: ...station Refer to 3 3 4 Monitoring Profiles for additional information Launch Database Editor Allows the Administrator to edit the workstation database in a spreadsheet format Login Allows a user to log in to the Intelligent Fire Integrator system The user can also log out of the system and log in as another user Output Appliances Allows the user to configure the optional output devices Colors and ...

Страница 27: ...to the Intelligent Fire Integrator Configuration Tool Installation Operation Manual P N 53380 for additional information The factory defined monitoring profile Default is set to monitor all networks and nodes Therefore to hide any desired networks or nodes and the respective event types the Administrator must create a new monitoring profile using the configuration tool Monitoring profiles are acti...

Страница 28: ...rol Units and Accessories for Fire Alarm Systems Off normal events and their corresponding default colors are listed in Table 3 1 NOTE The Administrator can customize workstation default color choices if required by the Authority Having Jurisdiction Document any custom color schemes for future reference Table 3 1 Event Icon Color Coding Default Event Color Off Normal Event Default Event Color Off ...

Страница 29: ...3380 for additional information 3 3 8 2 Control Profile User Permissions The Administrator sets control profile user permissions using the User Editor in the workstation configuration tool Refer to the Intelligent Fire Integrator Configuration Tool Installation Operation Manual P N 53380 for additional information Table 3 2 System Options Configuration Setting Possible Settings Comments Icon Set S...

Страница 30: ...d 7 Select the network type from the Type drop down list 8 Click the Add Gateway icon The Gateway Properties window opens 9 Enter the Gateway IP Address and then click OK to return to the Network Properties window The gateway and nodes are displayed in the navigation tree 10 Click Exit and then Save 3 4 3 Adding a Redundant Gateway A redundant gateway see Figure 7 3 is a second gateway which commu...

Страница 31: ... Select the node type from a list of choices and type in the IP address of that node Import Panel Database Imports a Verifire Tools database Any nodes and points that are in the database will be autocreated on the network Rename Allows the user to rename the network This is the equivalent of replacing the network alias in the Properties window Delete Allows the user to delete the network A confirm...

Страница 32: ...cific event in a campus site or building The navigation tree can be arranged in a parent child hierarchical relationship so a user can in a logical progression drill down from a site view to the floor plan of a building on that site The tree also shows at what level of the hierarchy an event is occurring When events occur boxes appear at the left side of the tree in the color corresponding to the ...

Страница 33: ...cally create an icon on the monitoring workstation screen 64 icons per screen before another screen is automatically added Those icons will have the exact point ID When points are auto created a system backup should be performed using the monitoring workstation s PC Monitor application 5 If applicable to your situation you are now ready to proceed with 3 8 Workstation Database Backup and Restore T...

Страница 34: ... a new folder to hold the backup files and folders 4 Enter a file name for the backup database in the File name field and then click Save 3 8 2 Restoring a Backed Up Database Restore backed up database files on the workstation as follows 1 Shut down all fire system applications including gateways except for PC Monitor 2 From the Windows taskbar right click the PC Monitor icon and then click Restor...

Страница 35: ... naming it and assigning it a macro command The macro command s Menu list of choices will be contingent on the gateway type point and node type that is selected Macro settings are saved when exiting the configuration tool and clicking Yes to the Save Changes prompt Refer to the Intelligent Fire Integrator Configuration Tool Installation Operation Manual P N 53380 for additional information On the ...

Страница 36: ...d may degrade system operation Gray scale Light colored gray scale images work best since colored images interfere with the color tinting used in alarm reporting Refer to Table 3 5 Table 3 4 Effect on Non PNG Icon File on Background Table 3 5 Effects of Icon Color on Alarm Reporting PNG File Non PNG File Visible Background Background Blocked by Square Icon Type If Normal Icon Has This Color Alarm ...

Страница 37: ...ings are as follows Table 4 1 Windows Settings Setting Required Value Windows Update Check for updates but let me choose whether to download and install them IP Address Valid IP Address required if connecting to LAN Power Options Display Turn off the display Never Computer Put the computer to sleep Never Time Zone Local time zone Daylight Savings Time Set appropriate for local area Display Resolut...

Страница 38: ...work node and point labels as described below Network Label Network Alias Display the user defined description of the network None Do not display the assigned network alias Node Label Node Alias Display the user defined description of the node Node Number Display the system assigned node number None Do not display the assigned node alias or number Point Label Point Alias Display the user defined d...

Страница 39: ...n PC on Workstation Shutdown True Automatically shut down the computer hosting the workstation when the application is closed normally through File Exit False Do not automatically shut down the workstation s computer when normally closed Suppress Automatic Device Icon Creation True Use this selection to hide automatically created device icons from all navigation window displays This selection also...

Страница 40: ...isabled Unacked Event Timeout 3 60 Minutes 3 60 Time in minutes before the user defined macro is executed Macro Activated on Alarm Macro name Select a macro from the list None Do not activate a macro Security Inactivity Timeout 0 20 minutes 1 20 Length in minutes of no activity after which a user will be automatically logged out Must be enabled for UL 2572 compliance 0 Do not automatically log out...

Страница 41: ...ld Disabled Disable the pager selected in the pager list field All Day Yes Send the event message whenever it occurs No Send the event message at configured start and stop times Start Time 12 AM to 11 PM in Hourly Increments Activates only when All Day No setting is selected Select the times from the drop down list Stop Time Monitoring Default Use the system default monitoring profile User defined...

Страница 42: ...l Highlight an email name in the list and click to delete it Email Only Off normal Events Checkbox Check this check box if only off normal events are to be emailed to recipients i e return to normal notifications are not sent Email Name List Click the fields below the headings to enter modify text or select options from a drop down list Name Text Field Automatically populates the pager name when a...

Страница 43: ...recipient using the format configured above Email Source Click the fields in the right hand column to enter the information SMTP Server Text Field The IP address of the SMTP server Return Address Text Field Return email address of the email sender Subject Test Field The subject that is to appear in the email subject line Table 4 7 Email Tab Settings Continued Setting Possible Settings Description ...

Страница 44: ...setup a message displays indicating that the output format cannot be deleted In order to delete the format the setups using the format must be configured to use another output format or be deleted Output Formats Output Formats Field Listed Outputs Click the down arrow to display the available output formats added formats display automatically The selected output is configured modified using the Av...

Страница 45: ... case ensures that the internal components do not overheat To receive a warning message if the fan motor fails the user can activate fan monitoring as follows 1 Right click on the PC Monitor icon located in the Windows Task Bar 2 Click on Monitor Fan A check mark indicates that the option is enabled Disable fan monitoring by clicking the checked Monitor Fan label The label is unchecked ...

Страница 46: ...Workstation Settings Other Settings 46 IFI WS Installation and Operation Manual P N LS10050 000JC E A 12 11 2014 ...

Страница 47: ...he Intelligent Fire Integrator system continues to be monitored 5 2 Display Modes The Administrator configures how the workstation graphical user interface is normally displayed If the Administrator allows it the user can toggle between graphics and text display modes from the workstation View menu These display modes are described below 5 2 1 Graphics Mode In graphics mode the workstation display...

Страница 48: ...Operation Display Modes 48 IFI WS Installation and Operation Manual P N LS10050 000JC E A 12 11 2014 Figure 5 1 Example Graphics Mode Screen ...

Страница 49: ...ts and Acknowledged Events panes are expanded in tabular form across the entire workstation display see Figure 5 2 As in graphics mode events are updated in real time A Panel Ack column is displayed with check boxes to indicate that the event is known to be acknowledged at the fire alarm control panel FACP Figure 5 2 Example Text Mode Screen ...

Страница 50: ...n and Operation Manual P N LS10050 000JC E A 12 11 2014 5 3 Graphics Display Screen The workstation graphics display screen is shown in Figure 5 3 Each feature is described in Table 5 1 Figure 5 3 Graphics Display Screen Features 4 5 6 7 2 1 3 8 9 10 11 12 ...

Страница 51: ...de Graphics Mode If not grayed out click to toggle between text and graphic display modes Refer to 5 3 1 Graphic Elements for details History Opens the History Manager window System Opens the System Explorer window displaying a Windows type navigation tree showing local system layout Search for Device Opens the System Explorer window where the user can search for a particular device on the system ...

Страница 52: ...repositioning the viewing area This window is helpful when a zoom in scale is selected for the workstation floor plan The overview window does not display the graphic elements within it 8 Navigation Tree Displays the Intelligent Fire Integrator system in a structured hierarchy form similar to Microsoft s Windows Explorer Refer to 5 3 2 Navigation Tree 9 New Events Pane Displays list of newly repor...

Страница 53: ...ds are available only when you have a node control and security profile that allows it Only one workstation can control any single system device at a given time Taking control of a device removes control from the previous supervisor of that device 5 3 1 5 Point Right Click Choices to Respond to Events Addressable devices have right click menus that provide you with a list of device specific choice...

Страница 54: ...sonnel on Scene Device Undergoing Test Device Testing Completed Contacted System Contractor Faulty Device Replaced Device Preventative Maintenance History Of Device Only displays the history information in the History Manager window for the selected node point Linked Media Accesses any media that has been created and then assigned to the node point Several types of media files may be linked to the...

Страница 55: ...gation Tree Overview Item Feature Description 1 Window Title Describes the hierarchy levels displayed in the floor plan window 2 Expand Contract Buttons Click to expand Vand collapse U the pane 3 Level Indicator Box Click to collapse the level and its child screens 4 Node Label Double click to display the nodes devices location on the floor plan 5 Level Indicator Box Click to expand the level and ...

Страница 56: ...d at the panel Acked will be displayed prefixing the event in the New Events list If the workstation has node control of the point a colored box will display to the left of the event in the Navigation Tree If the event is unreliable meaning it was reported while a gateway or node was in fault an asterisk will be displayed prefixing the event in the New Events list 5 3 3 1 New Events Buttons The al...

Страница 57: ...ons have been resolved Hovering the cursor over the icon displays its label Clicking on the icon displays the following information Fire Events issued by fire protection related devices such as pull stations smoke detectors and sprinkler systems PreAlarm Events that indicate that a point is close to declaring an alarm giving the facility manager opportunity to address the problem before an emergen...

Страница 58: ...le reaching 100 000 entries Other Other event types such as disabled points on the system 5 4 Auto creation of Screens Nodes and Points 5 4 1 Overview The auto creation process of the workstation software application accomplishes the following Creates a parent screen for the gateway 1 a child screen for the node 2 and a child screen under that 3 for the points for that node in a navigation tree fo...

Страница 59: ... across the bottom of the screen with details about the point The window s title bar is color coded based on the current state of the associated icon In the Navigation Tree a colored box displays adjacent to the level s with the event s Priority of the event s is displayed by color red for fire blue for security yellow for trouble etc In the New Events window the event is added to a list In the Al...

Страница 60: ...described in Table 5 3 Table 5 3 Protected Premises Control Unit vs Proprietary Receiving Unit Event Handling Action Protected Premises Mode Proprietary Receiving Unit If an event is acknowledged at the fire alarm control panel FACP it is acknowledged at the workstation Yes No If an event is acknowledged at the workstation it is acknowledged at the FACP Yes If the user has the security privilege t...

Страница 61: ...ractical to back up the fire system database to the default folder using the same dat file after each editing session and then archive to a CD The workstation has a CD RW drive CAUTION If a second backup file is saved to an existing backup folder both dat files remain but the newer backup overwrites the data for the existing one Do not save backup system data to a folder which contains existing ba...

Страница 62: ...is accessed by clicking View History within a network client such as the workstation or it can be started from outside the application environment from Start Programs Facilities Monitoring History Manager At the top of the window are File View and Filter menus see Figure 6 1 Below that are the record viewer tabs Event Point Screen and Statistics if they are enabled The information bar at the botto...

Страница 63: ...display of the record viewer tabs With the record viewer tabs displayed click an item from the event list to select it and then click a record viewer tab Event Point Screen or Statistics to view that type of information about the selected event Filters Toggles display of the filter pane on the left side of the event list providing more horizontal space for the event list Note Hiding the filter pan...

Страница 64: ...ed column such that any hidden text is displayed Resize All Columns Resizes the width of all displayed columns such that any hidden text is displayed Left click on a header to do the following Sort Ascending Descending Toggles between sorting the column data in ascending or descending order numeric or alphabetical Table 6 4 History Manager Row Options Option Description Filter By Selection Allows ...

Страница 65: ... window displays 3 Type the code into the Upgrade Code field 4 Click on the Perform Upgrade button Fields on the window update to reflect the upgrade code 5 Click Done to complete the upgrade and close the window 6 4 3 Key Upgrade Utility Field Descriptions Refer to the following table for descriptions of the fields in the Key Upgrade Utility Table 6 5 Upgrade Utility Fields Field Description Inst...

Страница 66: ...Data Management Key Upgrade Utility 66 IFI WS Installation and Operation Manual P N LS10050 000JC E A 12 11 2014 ...

Страница 67: ...equipment Each gateway relays Ethernet protocol messages from the monitored equipment using the equipment s native protocol to the workstation An Intelligent Fire Integrator system can support up to 200 gateways Example system architectures are described in the figures below Figure 7 1 Basic NFN Network Example Workstation FACP FACP FACP Workstation NFN Network Ethernet Embedded Gateway Both works...

Страница 68: ...xample FACP Workstation Proprietary Receiving Unit System Not UL listed for Control Ethernet Workstation Gateway PC Protected Premises Control Unit System UL listed for Control of NFN Network 1 only Embedded Gateway NFN Network 1 NFN Network 2 FACP FACP FACP FACP FACP Workstation Proprietary Receiving Unit System Not UL listed for Control ...

Страница 69: ... Network Workstation Ethernet Hub TCP IP UL 864 Listed Switch Redundant Gateway Other Technologies LAN WAN Internet Intranet Dedicated Only Ethernet Hub TCP IP UL 864 Listed Switch Ethernet Hub TCP IP UL 864 Listed Switch Embedded Gateway NFN Network Workstation acting as a Proprietary Receiving Unit with redundant gateways System is not UL listed for control in this configuration ...

Страница 70: ... Proprietary Receiving Unit Proprietary Receiving Unit fire alarm systems monitor the life safety systems of the protected premises that are under the same ownership The proprietary receiving unit can be located at the protected premises or at multiple protected properties Properties may consist of a single building such as a high rise building or several buildings such as a campus where multiple ...

Страница 71: ... are supported simultaneously and can be constantly supervised and communicating with the same workstation They can also span the TCP IP network and exist on multiple workstations or embedded hardware The choice of which gateways to use and where they should be located is application specific and should be analyzed by a trained individual See Figures 7 5 and 7 6 for examples of proprietary receivi...

Страница 72: ...Operation Manual P N LS10050 000JC E A 12 11 2014 Figure 7 6 Proprietary Receiving Unit System Example 2 Supervising Station Transmission and Communications Path Protected Premises Unit Workstation PC Gateway Receiver Gateway Digital Alarm Communicator Receiver NFN Network RS 232 PRU ...

Страница 73: ...r the workstation is running as a Protected Premises Control Unit or Proprietary Receiving Unit For example If the event is acknowledged at the panel Acked will be displayed prefixing the event in the New Events list If the workstation has node control of the point a colored box displays to the left of the event in the Navigation Tree If the event is unreliable meaning it was reported while a gate...

Страница 74: ...System Architecture Protected Premises Control Unit vs Proprietary Receiving Unit Event Handling 74 IFI WS Installation and Operation Manual P N LS10050 000JC E A 12 11 2014 ...

Страница 75: ...Controls Group 507 E Michigan Street P O Box 423 Milwaukee WI 53201 www johnsoncontrols com Release Rev A Printed in U S A ...

Отзывы: