22
IFC-3030 Programming Manual —
P/N 52025:C 08/05/2005
Program
Panel Program
DISPLAY
ADDRESS:
Press this soft key to toggle between Yes and No. Choose Yes to display all
point address information at the top of event screens and in printouts. Choose No to suppress
address information display and printing. Default: Yes
REMINDER
MENU:
Press this soft key to bring up the Reminder Menu screen.
ACCEPT:
Press this soft key to save the information entered on this screen.
MORE:
Press this key to progress to the second Panel Settings screen.
Figure 3.6 Panel Settings (2) Screen
Soft Keys
LCM
LOCAL
MODE:
Press this soft key to toggle between Yes and No. Enter Yes to enable all SLCs
to participate in local mode. When enabled, all LCMs will operate together in a limited fashion
when communication is lost with the IFC-3030 CPU. Inputs on LCM loops (and associated LEM
loops, if installed) will activate outputs on all loops
• for those inputs and outputs that have been set with point programming to participate in local
mode, and
• when type codes are the same point type: that is, an input with a fire type code will activate
an output with a fire type code.(Refer to Appendix G, “Type Codes”, on page 133 for point
types).
Default:
NO
PANEL
CIRCUIT
BELL
CODING:
Press to toggle between
MARCH
and
TEMPORAL
. This is a
global setting: ZF8 must be entered in the zone map of any panel circuit point that will participate
in this coding. Refer to “Coding Functions for Panel Circuit Outputs” on page 114 for more
information. Default:
MARCH
DCC
PARTICIPATION:
Press this key to program the panel for DCC (Display and Control Center)
participation. This network function ensures that one location at a time is in command of the
Acknowledge, System Reset, Signal Silence and Drill functions. Default:
NO
CAUTION:
On systems utilizing the DCC function, all locations that can participate in DCC should be set to
YES.
P A N E L S E T T I N G S
L C M L O C A L M O D E : Y E S
P A N E L C I R C U I T B E L L C O D I N G : M A R C H
D C C P A R T I C I P A T I O N : N O
L O C A L S E T T I N G S
A C C E P T
D E F A U L T S E T T I N G S
B A C K
!
Содержание IFC-3030
Страница 8: ...Table of Contents 8 IFC 3030 Programming Manual P N 52025 C 08 05 2005...
Страница 64: ...64 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Program Autoprogram Menu...
Страница 78: ...78 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Alter Status Control On Off Point Select...
Страница 84: ...84 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Service Screens Application Corrupt Screen...
Страница 87: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 87 Screens Overview Menu Hierarchy...
Страница 88: ...88 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Menu Hierarchy Screens Overview...
Страница 130: ...130 IFC 3030 Programming Manual P N 52025 C 08 05 2005 CBE Zones and Equations Equations...
Страница 138: ...138 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Type Codes FlashScan Codes...
Страница 146: ...146 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Glossary...
Страница 154: ...154 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Z Z Index...
Страница 155: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 155...
Страница 156: ...Controls Group 507 E Michigan Street P O Box 423 Milwaukee WI 53201 www johnsoncontrols com Release C Printed in U S A...