Special Zone Outputs
Coding Functions for Panel Circuit Outputs
• TM-4 polarity reversal alarm output
• TM-4 municipal box output
• UDACT
Positive Alarm Sequence (PAS)
Outputs selected for PAS delay for 15 seconds. Acknowledgement within the 15-second delay will
set the Presignal Delay Timer to the full programmed value (60-180 seconds, including the PAS
delay of 15 seconds). When an alarm comes from an initiating device with a CBE list that includes
ZF0, the control panel delays the following outputs:
• System Alarm relay
• TM-4 polarity reversal alarm output
• TM-4 municipal box output
• UDACT
C.2 Coding Functions for Panel Circuit Outputs
Coding Functions are selectable pulsed signals that energize Panel Circuit outputs when a fire
alarm occurs.
NOTE:
Do not include ZF8 in the zone map of Panel Circuits used for releasing or zone coding
applications.
Select Coding Functions on a global basis by setting the Panel Circuit Bell Coding field to March
or Temporal. (Refer to “Panel Settings (2) Screen” on page 22). Select individual panel circuit
output points for coding participation by entering ZF8 in the point’s zone map. All Panel Circuit
outputs with ZF8 in their zone maps will sound the same code when activated. The table below
contains descriptions of each Coding Function selection:
Table C.1 Coding Function Selections
Coding Function
Selection
Signal
March Time (default)
120 PPM (pulses per minute)
Temporal
0.5s on, 0.5s off, 0.5s on, 0.5s off, 0.5s on, 1.5s off, repeats
Содержание IFC-3030
Страница 8: ...Table of Contents 8 IFC 3030 Programming Manual P N 52025 C 08 05 2005...
Страница 64: ...64 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Program Autoprogram Menu...
Страница 78: ...78 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Alter Status Control On Off Point Select...
Страница 84: ...84 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Service Screens Application Corrupt Screen...
Страница 87: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 87 Screens Overview Menu Hierarchy...
Страница 88: ...88 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Menu Hierarchy Screens Overview...
Страница 130: ...130 IFC 3030 Programming Manual P N 52025 C 08 05 2005 CBE Zones and Equations Equations...
Страница 138: ...138 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Type Codes FlashScan Codes...
Страница 146: ...146 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Glossary...
Страница 154: ...154 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Z Z Index...
Страница 155: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 155...
Страница 156: ...Controls Group 507 E Michigan Street P O Box 423 Milwaukee WI 53201 www johnsoncontrols com Release C Printed in U S A...