8 G—G861 Series Integrated Function Direct Spark Ignition Control Technical Bulletin
!
CAUTION:
Equipment Damage Hazard. Connect the high
voltage cable to the spark transformer terminal and
spark igniter before applying power to the control.
Check the voltage rating marked on the control and ensure it is suited to the
application. Use an NEC Class 2 transformer to provide 24 VAC under
maximum load, including the valve. A transformer having excessive
primary impedance due to poor coupling will affect the ignition potential.
Refer to Figure 3 for the G861 wiring diagram. All wiring should be in
accordance with the National Electrical Code (NEC) and all other local
codes and regulations. The high voltage spark transformer cable must not
be in continuous contact with a metal surface. Use standoff insulators.
Ensure that the flame sensor wire and high voltage spark transformer cable
are separated from one another by a minimum distance of 6.35 mm (1/4 in.)
and are not wrapped around any pipe, other wiring, or accessories.
Electrical
Connections