G—G861 Series Integrated Function Direct Spark Ignition Control Technical Bulletin    5

Upon receiving a call for continuous manual fan, the G861 energizes the
circulator/blower motor at medium fan speed. The continuous fan on
request is immediately overridden by a call for heat.

The G861 offers the following responses based on abnormal system
operation.

A pressure switch within the appliance provides proof of combustion air
flow. During a heating cycle, the G861 control responds to the state of this
switch in the following ways:

 

At the beginning of the heating cycle, if the pressure switch is not open
before the inducer is energized, the control will wait for the switch to
open for as long as the call for heat is present. The G861 control LED
(Light-Emitting Diode) will blink with a flash code of 3 while waiting
for the pressure switch to open.

 

If the pressure switch does not close after the inducer has been
energized for 8 seconds, the control will keep the inducer energized and
the LED will blink with a flash code of 3 until the pressure switch
closes or the call for heat is removed.

 

If the pressure switch opens any time after the G861 control has begun
the trial for ignition, the control will immediately de-energize the gas
valve. If the pressure switch fault occurs after the flame is sensed, the
circulator/blower will run for 90 seconds, the inducer motor will remain
energized, and the control will go into the Pressure Switch Open Fault
state. During this time, the LED will blink with a flash code of 3. As
long as the call for heat is still present, the control will continue to wait
for the pressure switch to close before resuming the heating cycle. If the
pressure switch fails three times with no more than 30 seconds between
successive faults, the control will go to PSWFLT1 and PSWFLT 2 state
with an LED flash code of 3.

If a flame is present at power up, the G861 allows the flame to extinguish
within 10 seconds. If this occurs, the normal sequence of operation
continues. If the flame is still present after 10 seconds, the G861 goes into
flame lockout. If flame is present any other time it should not be, the G861
goes into flame lockout after a 10-second delay.

During the flame lockout, the inducer motor and the circulator/blower
remain energized, and the main valve is de-energized. The G861 control
LED flashes with a duty cycle of 1/2 second On, 1/2 second Off for
five flashes with a longer Off time before repeating the series. The control
remains in this state until the main power is cycled.

Call for Manual
Fan

Abnormal
System
Operation

Pressure Switch
Detection

Undesired Flame

Содержание G861 Series

Страница 1: ...nsor It provides outputs for timing and sequencing of the main gas valve induced draft motor circulator blower and spark igniter The G861 utilizes quick connect terminals for all off board connections except thermostat inputs and spark output The thermostat inputs are connected to a terminal strip with screw terminals and the spark output is connected by a rajah spike or 1 4 in male tab type spark...

Страница 2: ...ontrol 24 VAC 50 60 Hz nominal Operation Current 0 3A 24 VAC Contact Rating Main Valve 2A continuous at 24 VAC 5A inrush Inducer 2A continuous 120 VAC Blower 1 3 hp 7 20 FLA 125 VAC Ambient Operating and Storage Temperature 40 to 70 C 40 to 160 F Humidity 95 RH non condensing Wiring Connections Spark Spike rajah or 1 4 in male tab Types of Gas Natural Liquefied Petroleum LP manufactured mixed or L...

Страница 3: ...of operation of the G861 control Upon receiving a call for heat from the system thermostat the G861 follows this normal sequence of operation 1 Pressure Switch Detection The control checks the inducer pressure switch to ensure that it is open 2 Prepurge The control energizes the inducer motor and verifies that the pressure switch closes 3 Pressure Switch Detection The control checks the pressure s...

Страница 4: ...No Postpurge No End Thermostat calls for m anual fan G No Run manual fan speed Thermostat call for heat Pressure switch open Yes Retry mode 60 m inute delay No Yes Pressure switch closed Third trial Trial for ignition Sixteenth flameout Flam e sensed Circulator Blower on delay Thermostat satisfied Circulator Blower off delay field selectable Figure 2 G861 Sequence of Operation ...

Страница 5: ...ill immediately de energize the gas valve If the pressure switch fault occurs after the flame is sensed the circulator blower will run for 90 seconds the inducer motor will remain energized and the control will go into the Pressure Switch Open Fault state During this time the LED will blink with a flash code of 3 As long as the call for heat is still present the control will continue to wait for t...

Страница 6: ...rmostat will run the circulator blower at medium speed During the 60 minute retry delay period the LED will blink with a flash code of 2 A manual fan call from the thermostat during the 60 minute retry will run the circulator blower at medium speed The G861 offers the following responses to the two possible interrupted thermostat situations If the call for heat is removed before the gas valve is e...

Страница 7: ... If the control is installed in an area that is exposed to water dripping spraying rain etc it must be protected If the control has been exposed to water in any way do not use it WARNING Shock Hazard Avoid electrical shock and equipment damage Disconnect the electrical power and turn off the gas before wiring the control into the circuit Choose a location that provides the shortest direct cable ro...

Страница 8: ... transformer having excessive primary impedance due to poor coupling will affect the ignition potential Refer to Figure 3 for the G861 wiring diagram All wiring should be in accordance with the National Electrical Code NEC and all other local codes and regulations The high voltage spark transformer cable must not be in continuous contact with a metal surface Use standoff insulators Ensure that the...

Страница 9: ...rm e r 24 V L in e 2 4 V C o m m o n S p ark Tra n s fo rm er 24 VA C H o t G ro u nd F lam e S e n se P S W P re s s u re S w itc h H ig h L im it In H igh L im it O ut R o llo u t In B lo w e r O ff D e la y S etting H igh L im it S w itc h R o llo ut S w itc h T he rm o s ta t 3 1 6 in ch Te rm in a l W G R S e nso r N ote A ll term in a ls are 1 4 in ch u n less o the rw ise spe cified P re ss...

Страница 10: ...nd verify that the control goes through the operating sequence to a shutoff condition Note The burner will not light because the gas is off 3 Turn the thermostat off 4 Turn gas on and purge gas lines of all air 5 Check for gas leaks on all pipe joints upstream of the gas valve with a soap solution 6 Turn the thermostat to a high setting and verify successful ignition and a normal run condition for...

Страница 11: ...draw of the heating system at the thermostat location Measuring this current can be accomplished by opening the thermostat contacts lowering the setpoint and installing an AC ammeter across the terminals or by using a clamp on ammeter with a 10 turn multiplier attached to the terminals See Figure 4 Ten Turns Clamp on Ammeter Divide reading by ten W R W R AC Ammeter Low Scale Setting To Heating Sys...

Страница 12: ...ash Three Pressure switch open or closed Flash Four High limit open Flash Five Flame sensed and gas valve not energized Steady On Internal failure microcontroller self check failure CAUTION Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Do not attempt field repairs to the ignition control Use only an exact or recommended repl...

Отзывы: