Wiring

Observe the following guidelines when wiring a controller:

Risk of Electric Shock:

Disconnect the power supply

before making electrical connections to avoid electric
shock.

Mise En Garde: Risque de décharge électrique:

Débrancher l'alimentation avant de réaliser tout
raccordement électrique afin d'éviter tout risque de
décharge électrique.

Risk of Property Damage:

Do not apply power to the

system before checking all wiring connections. Short
circuited or improperly connected wires may result in
permanent damage to the equipment.

Mise En Garde: Risque de dégâts matériels:

Ne pas

mettre le système sous tension avant d'avoir vérifié tous
les raccords de câblage. Des fils formant un court-circuit
ou connectés de façon incorrecte risquent
d'endommager irrémédiablement l'équipement.

Important:

Do not exceed the controller electrical
ratings. Exceeding controller electrical
ratings can result in permanent damage to
the controller and void any warranty.

Important:

Use copper conductors only. Make all wiring
in accordance with local, national, and
regional regulations.

Important:

Electrostatic discharge can damage
controller components. Use proper
electrostatic discharge precautions during
installation, setup, and servicing to avoid
damaging the controller.

For detailed information on configuring and wiring an
MS/TP Bus, FC bus, and SA bus, refer to the

FX-PC

Series Controllers MS/TP Communications Bus Technical
Bulletin (LIT-12011670)

or

MS/TP Communications Bus

for BCM System Technical Bulletin (LIT-12011908)

.

Terminal Blocks and Bus Ports

See

Figure 3

for terminal block and bus port locations on

the controller. Observe the following guidelines when
wiring a controller.

Input and Output Terminal Blocks

All of the input terminal blocks are mounted on the bottom
of the controller and the output terminal blocks are
mounted on the top of the controller. See

Table 3

for more

information about I/O terminal functions, requirements,
and ratings.

SA/FC Bus Terminal Block

An FX-PCX can be connected to a Sensor/Actuator (SA)
bus or a Field Controller (FC) bus, but not to both buses
simultaneously. The SA/FC bus terminal block is a
removable, 4-terminal plug that fits into a board-mounted
jack.

When connecting the FX-PCX to an FC bus, wire the bus
terminal block plugs on the controller, and the other
controllers in a daisy-chain configuration using 3-wire
twisted, shielded cable as shown in

Figure 4

. See

Table

5

for more information.

Figure 4: FC Bus Terminal Block Wiring

When connecting the FX-PCX to an SA bus, wire the bus
terminal block plugs on the controller and other SA bus
devices in a daisy-chain configuration using 4-wire
twisted, shielded cable as shown in

Figure 5

. See

Table

3

for more information.

4

FX-PCX47 Expansion Input/Output Module Installation Instructions

Содержание FX-PCX47

Страница 1: ...nstalled and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area may cause harmful interference in w...

Страница 2: ...rail channel on the back of the controller Figure 2 and position the controller snugly against the DIN rail 4 Push the bottom mounting clips inward up to secure the controller on the DIN rail To remov...

Страница 3: ...le 5 6 Cover Lift Tab One of Two See Removing the Controller Cover 7 Sensor Actuator SA Bus or Field Controller FC Bus Terminal Block See Table 5 8 Binary Input BI Terminal Block 2 Binary Inputs See T...

Страница 4: ...figuring and wiring an MS TP Bus FC bus and SA bus refer to the FX PC Series Controllers MS TP Communications Bus Technical Bulletin LIT 12011670 or MS TP Communications Bus for BCM System Technical B...

Страница 5: ...on the top right of the controller Wire the 24 VAC supply power wires from the transformer to the HOT and COM terminals on the terminal plug as shown in Figure 7 The middle terminal on the supply powe...

Страница 6: ...o the FX ZFR1811 Wireless Field Bus Router Installation Instructions Part No 24 10325 29 Termination Details A set of Johnson Controls termination diagrams provides details for wiring inputs and outpu...

Страница 7: ...rrent Input Internal Source 2 wire UI Current Input Internal Source 3 wire UI Current Input External Source in Loop UI Feedback from EPP 1000 UI or BI Dry Contact Binary Input CO or AO 0 20 VDC Output...

Страница 8: ...CO or AO 0 10 VDC Output to Actuator Internal Source CO or AO 4 20 mA Output to Actuator CO or AO 4 20 mA Output to Actuator AO Voltage Analog Output AO Analog Output Current CO 24 VAC Triac Output Sw...

Страница 9: ...24 VAC Triac Output Switch High Externally Sourced CO Incremental Control to Actuator Switch High Externally Sourced BO Incremental Control to Actuator Switch Low Externally Sourced BO 24 VAC Binary...

Страница 10: ...e BO Incremental Control to Actuator Switch High Externally Sourced SA Bus Network Stat with Phone Jack Fixed Address 199 SA Bus Network Stat with Terminals Addressable SA Bus Network Stat with Termin...

Страница 11: ...rminal Label Terminal Block Label Same as Universal INn Note Use 3 wire cable for devices that source power from the 15V terminal 15 VDC Power Source for active 3 wire input devices connected to the U...

Страница 12: ...greater than 1 000 ohm Devices that drop below 1 000 ohm may not operate as intended for Voltage Mode applications OUTn ANALOG Outputs Analog Output Current Mode 4 20 mA Requires and external load be...

Страница 13: ...imum output voltage 10 mA maximum output current Required an external load of 1 000 ohm or more OUTn CONFIGURABLE Outputs See Guideline C in Table 4 Binary Output 24 VAC Triac External Power Source on...

Страница 14: ...per 100 mV maximum voltage drop Depending on cable and the connected input or output device you may have to define an offset in the setup software for the input or output point 229 m 750 ft twisted wi...

Страница 15: ...cable recommended Note On the SA Bus the and wire are one twisted pair and the COM and SA PWR are the second twisted pair of wires FC or SA Bus Communications FC BUS 2 or SA BUS 2 Signal Reference Co...

Страница 16: ...itch 4 ON followed by switch 1 16 4 1 21 See Figure 9 3 Set switch 128 to ON only for controllers on an FX ZFR Series Wireless Field Bus application For all hard wired SA and FC bus applications ensur...

Страница 17: ...under the two cover lift tabs Figure 3 on the sides of the housing cover and gently pry the top of the cover away from the base to release the cover from the two upper latches 2 Pivot the top of the...

Страница 18: ...Jumpers The current loop fail safe jumpers are on the circuit board under the controller cover near the UI terminals Figure 10 When a UI is defined in the system software as a 4 20 mA Analog Input and...

Страница 19: ...For a replacement controller contact your Johnson Controls representative Accessories See Table 9 for controller accessories ordering information Table 9 Accessories Ordering Information Description...

Страница 20: ...FX PCG FX PCA FX PCX and FX PCV field controllers Also allows use of the FX ZFR Checkout Tool FX ZCT in FX PCT Note The ZFR USBHA 0 replaces the IA OEM DAUBI_2400 ZigBee USB dongle For additional inf...

Страница 21: ...28 KB Random Access Memory RAM Memory 6 Universal Inputs Defined as 0 10 VDC 4 20 mA 0 600k ohm or Binary Dry Contact 2 Binary Inputs Defined as Dry Contact Maintained or Pulse Counter Accumulator Mod...

Страница 22: ...erformance specifications are nominal and conform to acceptable industry standard For application at conditions beyond these specifications consult the local Johnson Controls office Johnson Controls I...

Отзывы: