Troubleshooting the Controllers

Observe the Status LEDs on the front of the controller
and see

Table 8

to troubleshoot the controller.

Table 8: Status LEDs and Descriptions of LED States

Description of LED States

Normal LED
State

LED Color

LED Label

Off Steady = No Supply Power or the controller’s polyswitch/resettable fuse
is open. Check Output wiring for short circuits and cycle power to controller.

On Steady = Power Connected

On Steady

Green

POWER

Off Steady = No Faults

On Steady = Device Fault; no application loaded; Main Code download
required, if controller is in Boot mode, or a firmware mismatch exists between
the controller and the FX-ZFR1811 Wireless Field Bus Router.

Blink - 2 Hz = Download or Startup in progress, not ready for normal operation

Off Steady

Red

FAULT

Blink - 2 Hz = Data Transmission (normal communication)

Off Steady = No Data Transmission (N/A - auto baud not supported)

On Steady = Communication lost, waiting to join communication ring

Blink - 2 Hz

Green

SA/FC BUS

On Steady = EOL switch in ON position

Off Steady = EOL switch in Off position

Off (Except on
terminating
devices)

Amber

EOL

Repair Information

If a controller fails to operate within its specifications,
replace the controller. For a replacement controller,
contact your Johnson Controls

®

representative.

Accessories

See

Table 9

for controller accessories ordering

information.

Table 9: Accessories Ordering Information

Description

Product Code Number

Bluetooth Commissioning Converter

FX-BTCVT-1

Wireless Field Bus Router

FX- ZFR1811-0

Transformer, 120 VAC Primary to 24 VAC secondary, 20 VA, Wall Plug

TP-2420

Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 40 VA, Foot Mount, 8 in.
Primary Leads and Secondary Screw Terminals, Class 2

Note:

Additional Y6x-x Series transformers are also available. Refer to the

Series Y63, Y64,

Y65, Y66, and Y69 Transformers Product Bulletin (LIT-125755)

for more information.

Y65T31-0

Power transformer (Class 2, 24 VAC, 50 VA maximum output), no enclosure

AS-XFR050-0

Replacement SA/FC Bus Terminal Blocks, 4-Position, Gray, Bulk Pack of 10

Note:

This is the standard terminal block that is provided with the controller.

MS-TBK4BUS-0

Replacement SA Bus Terminal Blocks, 4-Position, Brown, Bulk Pack of 10

Note:

These terminal blocks can be used as replacement parts if keeping consistent terminal

block colors is important.

AP-TBK4SA-0

Replacement FC Bus Terminal Blocks, 4-Position, Blue, Bulk Pack of 10

Note:

These terminal blocks can be used as replacement parts if keeping consistent terminal

block colors is important.

AP-TBK4FC-0

19

FX-PCX47 Expansion Input/Output Module Installation Instructions

Содержание FX-PCX47

Страница 1: ...nstalled and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area may cause harmful interference in w...

Страница 2: ...rail channel on the back of the controller Figure 2 and position the controller snugly against the DIN rail 4 Push the bottom mounting clips inward up to secure the controller on the DIN rail To remov...

Страница 3: ...le 5 6 Cover Lift Tab One of Two See Removing the Controller Cover 7 Sensor Actuator SA Bus or Field Controller FC Bus Terminal Block See Table 5 8 Binary Input BI Terminal Block 2 Binary Inputs See T...

Страница 4: ...figuring and wiring an MS TP Bus FC bus and SA bus refer to the FX PC Series Controllers MS TP Communications Bus Technical Bulletin LIT 12011670 or MS TP Communications Bus for BCM System Technical B...

Страница 5: ...on the top right of the controller Wire the 24 VAC supply power wires from the transformer to the HOT and COM terminals on the terminal plug as shown in Figure 7 The middle terminal on the supply powe...

Страница 6: ...o the FX ZFR1811 Wireless Field Bus Router Installation Instructions Part No 24 10325 29 Termination Details A set of Johnson Controls termination diagrams provides details for wiring inputs and outpu...

Страница 7: ...rrent Input Internal Source 2 wire UI Current Input Internal Source 3 wire UI Current Input External Source in Loop UI Feedback from EPP 1000 UI or BI Dry Contact Binary Input CO or AO 0 20 VDC Output...

Страница 8: ...CO or AO 0 10 VDC Output to Actuator Internal Source CO or AO 4 20 mA Output to Actuator CO or AO 4 20 mA Output to Actuator AO Voltage Analog Output AO Analog Output Current CO 24 VAC Triac Output Sw...

Страница 9: ...24 VAC Triac Output Switch High Externally Sourced CO Incremental Control to Actuator Switch High Externally Sourced BO Incremental Control to Actuator Switch Low Externally Sourced BO 24 VAC Binary...

Страница 10: ...e BO Incremental Control to Actuator Switch High Externally Sourced SA Bus Network Stat with Phone Jack Fixed Address 199 SA Bus Network Stat with Terminals Addressable SA Bus Network Stat with Termin...

Страница 11: ...rminal Label Terminal Block Label Same as Universal INn Note Use 3 wire cable for devices that source power from the 15V terminal 15 VDC Power Source for active 3 wire input devices connected to the U...

Страница 12: ...greater than 1 000 ohm Devices that drop below 1 000 ohm may not operate as intended for Voltage Mode applications OUTn ANALOG Outputs Analog Output Current Mode 4 20 mA Requires and external load be...

Страница 13: ...imum output voltage 10 mA maximum output current Required an external load of 1 000 ohm or more OUTn CONFIGURABLE Outputs See Guideline C in Table 4 Binary Output 24 VAC Triac External Power Source on...

Страница 14: ...per 100 mV maximum voltage drop Depending on cable and the connected input or output device you may have to define an offset in the setup software for the input or output point 229 m 750 ft twisted wi...

Страница 15: ...cable recommended Note On the SA Bus the and wire are one twisted pair and the COM and SA PWR are the second twisted pair of wires FC or SA Bus Communications FC BUS 2 or SA BUS 2 Signal Reference Co...

Страница 16: ...itch 4 ON followed by switch 1 16 4 1 21 See Figure 9 3 Set switch 128 to ON only for controllers on an FX ZFR Series Wireless Field Bus application For all hard wired SA and FC bus applications ensur...

Страница 17: ...under the two cover lift tabs Figure 3 on the sides of the housing cover and gently pry the top of the cover away from the base to release the cover from the two upper latches 2 Pivot the top of the...

Страница 18: ...Jumpers The current loop fail safe jumpers are on the circuit board under the controller cover near the UI terminals Figure 10 When a UI is defined in the system software as a 4 20 mA Analog Input and...

Страница 19: ...For a replacement controller contact your Johnson Controls representative Accessories See Table 9 for controller accessories ordering information Table 9 Accessories Ordering Information Description...

Страница 20: ...FX PCG FX PCA FX PCX and FX PCV field controllers Also allows use of the FX ZFR Checkout Tool FX ZCT in FX PCT Note The ZFR USBHA 0 replaces the IA OEM DAUBI_2400 ZigBee USB dongle For additional inf...

Страница 21: ...28 KB Random Access Memory RAM Memory 6 Universal Inputs Defined as 0 10 VDC 4 20 mA 0 600k ohm or Binary Dry Contact 2 Binary Inputs Defined as Dry Contact Maintained or Pulse Counter Accumulator Mod...

Страница 22: ...erformance specifications are nominal and conform to acceptable industry standard For application at conditions beyond these specifications consult the local Johnson Controls office Johnson Controls I...

Отзывы: