Important:
Do
not
connect an external power source
to a when the BO power source jumper is
in the internal power (INT) position.
Connecting external power to a BO that
sources internal power can damage the
controller and void any warranties.
The BO source power selection jumpers determine
whether a BO provides internal power (sourced from the
controller) to the output load (INT position) or requires
an external power source (EXT position) for the output
load.
shows an example of a controller BOs
and the associated power selection jumpers to the right
of the BOs terminal block.
Figure 12: Example Binary Outputs and the
Associated Source Power Jumper Positions
UI Current Loop Jumpers
The current loop fail-safe jumpers are on the circuit board
under the controller cover near the UI terminals (
). When a UI is defined (in the system software) as a
4-20 mA Analog Input and the UI’s current loop jumper
is in the Disabled (default) position (
), the 4-20
mA current loop circuit opens whenever power to the
controller is interrupted or off.
Figure 13: Current Loop Jumper Positions
Setting the current loop jumper to the Enabled position
(
) connects an internal 100 ohm resistor across
the UI terminals, which maintains the 4-20 mA current
loop circuit even when power to the controller is
interrupted or off.
Important:
Current Loop jumpers must be in the
Disabled (default) position for all UIs that
are not set up to operate as 4-20 mA analog
inputs.
identifies the current loop switches associated
with each UI on the FX-PCA2611-0 controller.
Table 7: FX-PCA2611-0 UI Inputs and Jumper Labels
Switch Label on Current Loop DIP
Switch Block Board
Universal Input
Label
J20
IN1
J21
IN2
J22
IN3
J23
IN4
J24
IN5
J25
IN6
Setting Up a Local Display
FX-PCA2611-0 models do not have an integral display,
but can be connected to an FX-DIS1710 Local Controller
Display. For detailed information on setting up and
operating either an integral user interface or a remotely
connected FX-DIS1710 display, refer to the
FX-DIS Local
Controller Display Technical Bulletin (LIT-12011666)
.
Commissioning the Controllers
You commission MS/TP controllers with the Facility
Explorer Programmable Controller Tool (FX-PCT)
software, either via a Bluetooth
®
Wireless Commissioning
Converter, a ZFR wireless dongle, or in router mode when
connected to an FX Supervisory Controller. Refer to
Controller Tool Help (LIT-12011147)
for detailed
information on commissioning controllers.
Troubleshooting the Controllers
Observe the Status LEDs on the front of the controller
and see
LED Status and Description Table
to troubleshoot
the controller. To troubleshoot an integral or local
controller display, refer to the
FX-DIS Local Controller
Display Technical Bulletin (LIT-12011666)
.
23
FX-PCA2611-0 Advanced Application Programmable Controller Installation Instructions