Johnson Controls Frick Vyper 305/254 Horsepower Скачать руководство пользователя страница 62

VYPER

 VARIABLE SPEED DRIVE

MAINTENANCE

100.200-IOM (SEP 13)

Page 62

in the Quantum

LX panel, and all other wiring involved in 

energizing #24 in the Vyper

 cabinet. Also check to ensure 

that the serial communications wiring between the micro 

board and the Interface board, and Vyper

 Logic board and 

the Interface board are connected properly.

 Fault 39: Vyper High Converter Heat Sink Temperature

Message

Quantum: “Fault 39”

Quantum LX: “VSD High Converter Heat Sink Temp Fault”

A  thermistor  sensor  is  located  behind  the  last  SCR/Diode 

block on the copper chill plate of the Vyper

 Power Unit. If 

at anytime this thermistor detects a temperature of 170°F 

(76°C) or higher, a shutdown will occur. The cooling fans and 

coolant pump on the Vyper

 will continue to run after the 

shutdown, until the thermistor temperature has dropped to 

below 160°F (71°C). This shutdown requires a manual reset 

via the Reset push button on the Vyper

 Logic board.

 Fault 40:  Vyper Invalid Current Scale Selection

Message

Quantum: “Fault 40”

Quantum LX: “VSD Invalid Current Scale Selection Fault”

The J1 connector on the Vyper

 Logic board contains jumpers 

along with wires from the output CTs. Since the part number 

of the Logic board is the same on all horsepower sizes, the 

jumpers  tell  the  logic  board  the  size  of  the  Vyper

  being 

employed in order to properly scale the output current. If 

the jumper configuration is found by the Logic board to be 

invalid, the system will be shut down and the above message, 

Fault 40, will be generated. The proper 

jumper configuration 

is shown on the wiring label for the Vyper

.

 Fault 41:  Vyper Low Inverter Base plate Temperature

Message

Quantum: “Fault 41”

Quantum

LX: “VSD Low Inverter Base plate Temp Fault”

The phase bank assembly heatsink temperature and the in-

verter module base plate temperature are compared to a lower 

limit of 37°F. If the inverter module base plate temperature falls 

below this limit the unit will trip and the Quantum

LX Panel will 

display the message Fault 41. In addition, if both the inverter 

and converter temperatures fall below the 37°F limit, the unit 

will trip and the fan(s) and water pump will be energized. This 

feature provides the Service Dept. with a means to run the 

water pump while filling the cooling system (by pulling Vyper

 

logic board plug P2). In most case the problem will be broken 

wiring or an open thermistor. Check the circuit for continuity 

at Vyper

 Logic board plug J2. Also make certain that one side 

of the circuit is not shorted to the enclosure.

 Fault 42: Vyperdrive - Serial Communication 

Message

Quantum: “Fault 42”

Quantum LX: “VSD Serial Communications Fault”

When  requesting  Status  data,  the  response  data  from  the 

Vyper

 includes a bit that indicates whether communications 

were lost from the Frick Interface Board to the Vyper

. If this bit 

is high for 22 consecutive seconds, this fault occurs. This fault 

also occurs whenever a receive, timeout, or checksum fault 

is detected on the Vyper

 communications, for twenty con-

tinuous seconds. While this fault is active, the Frick Interface 

Board will send Initialize data requests in order to reestablish 

the communications link. All serial input data is also cleared.

This message is generated when communications between 

the Quantum

LX Panel and the Frick Interface board, or the 

Frick Interface board and Vyper

 Logic board is disrupted 

for a least 22 seconds. Check the shielded cable between 

J11 on the Vyper

 Logic board and J8 on the Frick Interface 

board. Check for continuity and also check to see that none 

of the conductors are shorted together or shorted to ground. 

The terminal block in the lower left corner of the Vyper

 

cabinet serves as a junction point for this cable, and it is 

possible for strands of wire to bridge across the terminals 

at this location. If all wiring is intact, this problem may also 

be caused by electrical noise. Ensure that the chiller and the 

Quantum

LX Panel are properly ground through the Vyper

Make certain the shield for this cable is tied to chassis ground 

at  the  Quantum

LX  panel  end  only  via  a  green  chassis 

ground screw. The shield should not go to ground through 

the Frick Interface board.  If all of this has been done and 

communications cannot be established, even at power-up, 

you may have a bad communications driver on either the 

Vyper

 Logic or the Frick Interface boards. Change out both 

the  Frick  Interface  and  Vyper

  Logic  boards.  If  the  Serial 

Receive fault problem only occurs intermittently during times 

when the unit is running, the culprit could be electrical noise. 
If the Harmonic Filter is installed then the fault can be gener-

ated when the communications between the Vyper

 Logic 

board and the Harmonic Filter Logic board, or the Harmonic 

Filter Logic board and the Frick Interface board is disrupted. 

Also check J8 on the filter logic board and J9 on the Frick 

Interface board. Repeat the above procedure for the Vyper

 

serial cable on the Harmonic Filter serial cable.

 Fault 43:  Vyper

 Precharge  Lockout

Message

Quantum: “Fault 43”

Quantum LX: “VSD Precharge Lockout”

If the Vyper

 fails to meet the precharge criteria (refer to 

precharge  faults  below),  then  the  precharge  circuit  will 

wait for a period of 10 seconds. During this time, the unit’s 

cooling fans and coolant pump remain energized in order to 

cool the input SCR’s. Following this 10-second cool-down 

period, precharge will again be initiated. The unit will attempt 

to meet the precharge criteria three consecutive times. If 

the  Vyper

  fails  to  meet  the  precharge  criteria  on  three 

consecutive tries, the Vyper

 will shut down, lock out, and 

display this message. In order to initiate precharge again, 

the Quantum

LX panel’s compressor switch must first be 

placed into the STOP/RESET position.

 Fault 44:  Vyper

 Low Converter Heat Sink Temperature

Message

Quantum: “Fault 44”

Quantum LX: “VSD Low Converter Heatsink Temp Fault”

The  phase  bank  assembly  heatsink  temperature  and  the 

inverter  module  base  plate  temperature  are  compared  to 

a lower limit of 37°F. If the inverter base plate temperature 

or  the  converter  heat  sink  temperature  falls  below  37°F, 

the message displayed will be Fault 44. In addition, if both 

temperatures fall below the 37°F limit, the unit will trip and 

the fan(s) and water pump will be energized. This feature 

provides the Service Dept. with a means to run the water 

pump while filling the cooling system (by pulling VSD logic 

board plug P2).
A  thermistor  sensor  is  located  behind  the  last  SCR/Diode 

block on the copper chill plate of the Vyper

 Power Unit. If at 

anytime this thermistor detects a temperature of 37°F (3°C) 

Содержание Frick Vyper 305/254 Horsepower

Страница 1: ...3b 3c THIS MANUAL CONTAINS RIGGING ASSEMBLY START UP AND MAINTENANCE INSTRUCTIONS READ THOROUGHLY BEFORE BEGINNING INSTALLATION FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN DAMAGE OR IMPROPER...

Страница 2: ...TECTION 28 MOTOR RTD THERMAL PROTECTION 29 TEMPERATURE CONTROL VALVE WIRING 29 DRAWING NOTES 30 MOTOR COOLING BLOWER WIRING 30 ANALOG BOARD WIRING 31 QUANTUM LX COMMUNICATIONS WIRING 32 INSTALLATION C...

Страница 3: ...Valve 34 Figure 32 Step 4 Close the Drain and Refill the Unit 34 Figure 33 Step 5 Reapply power and Unplug J2 34 Figure 34 Step 6 Top Off the Cooling System 34 Figure 35 Step 7 Replace the Pipe Plug a...

Страница 4: ...ic con trol equipment All safety precautions consistent with opera tion of high current and voltage electrical equipment should be strictly enforced JOB INSPECTION Immediately upon arrival examine all...

Страница 5: ...GING AND HANDLING The Vyper cabinet unit is best moved via lifting lugs on the top sides of the cabinet Special care must be exercised not to damage the pump or peripheral equipment on the rear of the...

Страница 6: ...in the INSTALLATION section of this manual Verify that all control power 120 VAC communications analog wiring and 460 VAC power are in separate metallic conduits Properly shielded and grounded analog...

Страница 7: ...tables in this manual to calculate what they should be 7 Verify proper operation of the motorized coolant mixing valve on the back of the drive Locate the Coolant mixing valve on the back of the driv...

Страница 8: ...operating frequency range of the drive The unit is started with the compressor fully unloaded until the frequency reaches the minimum operating frequency range In addition the drive is capable of oper...

Страница 9: ...feet Adequate service clearances including door swing must be maintained around the Vyper Care should be taken to ensure that the Vyper and it s associated piping and wiring do not obstruct the acces...

Страница 10: ...GER PRESSURE DROP In order to adequately size piping and booster pump require ments the pressure drop of the coolant across the heat Figure 3 Minimum Flow Rates GLYCOL exchanger must be known Figure 4...

Страница 11: ...g procedures for electronic equipment instal lation These procedures do not override any rules by the NEC but are to be used in conjunction with the NEC code and any other applicable codes With exclus...

Страница 12: ...from various locations can create multiple potentials resulting in ground loop currents A single ground wire 10 AWG or 8 AWG from the electronic control panel that is bonded to the control power neut...

Страница 13: ...e grounded at both ends When not required to be in metal or other material by na tional or local codes conduits for the power feed 3 phase of constant speed starters may be PVC When not required to be...

Страница 14: ...ure Route the conduit to the sides or bottom of the panel and use a conduit drain If the conduit must be routed to the top of the panel use a sealable conduit fitting which is poured with a sealer aft...

Страница 15: ...ng shutdown protection for a Quantum panel the panel may not see the loss of the 3 phase voltage on the motor because the UPS may prevent the motor starter contactor from dropping out With the starter...

Страница 16: ...nce the Vyper has a 0 95 minimum power factor at all operational loads and conditions Capacitors can be located at one or several places on a distribution system Solid state motor controllers may not...

Страница 17: ...fiers SCRs and 3 diodes One SCR and one diode are contained in each module Three modules are required to covert the three phase input AC voltage to DC voltage 1SCR 3SCR The modules are mounted on a li...

Страница 18: ...SPEED DRIVE INSTALLATION 100 200 IOM SEP 13 Page 18 Figure 10 Vyper Elementary Wiring Diagram NOTE Drawings for specific units can be found in the door of the Vyper drive or check with Frick Engineer...

Страница 19: ...module does not rupture if a failure were to occur on the DC link of the Filter Power Unit THE THREE PHASE INDUCTOR provides some impedance for the filter to work against It effectively limits the rat...

Страница 20: ...VYPER VARIABLE SPEED DRIVE INSTALLATION 100 200 IOM SEP 13 Page 20 Figure 12 Harmonic Filter Elementary Wiring Diagram NOTE Typical Check with engineering for latest drawings...

Страница 21: ...nd shutdowns as sociated with the Vyper coolant temperature reading These wil also be factory set for a Low Temp alarm and shutdown at 85 F and 80 F with a 90 second delay when running The High Temp A...

Страница 22: ...VYPER VARIABLE SPEED DRIVE INSTALLATION 100 200 IOM SEP 13 Page 22 Liquid Cooled Vyper P I Diagram Economized...

Страница 23: ...VYPER VARIABLE SPEED DRIVE INSTALLATION 100 200 IOM SEP 13 Page 23 Liquid Cooled Vyper P I Diagram Noneconomized...

Страница 24: ...d also helps to maintain the rigidity of the cabinet during service The channel assembly VSD cabinet is mounted on two extension brackets welded to pads on the system s oil separator All package mount...

Страница 25: ...e top left of the cabinet that designates the point of entry for the incoming power This is the only acceptable point of entry for power into a Vyper drive For remote mounted 305 and 437 HP Vyper driv...

Страница 26: ...ernal capacitors resistors to discharge the DC bus and allow for safe maintenance of the unit Failure to do so may cause serious injury or death Also ensure that all power has been removed from the le...

Страница 27: ...tor Size Termination Torque 3 8 lug Compression 216 240 in lb ELECTRICAL CONDUITS All power wiring must be contained in metallic conduit All compressor motor wiring must be in a separate metallic cond...

Страница 28: ...VYPER VARIABLE SPEED DRIVE INSTALLATION 100 200 IOM SEP 13 Page 28 Figure 20 Motor Thermistor Protection WIRING DIAGRAM OPTIONS...

Страница 29: ...e speed drive systems Frick employs two types of thermal protection for motors One method uses thermistors and one method uses RTDs Figures 20 25 show the wiring scheme for both options MOTOR Thermist...

Страница 30: ...VYPER VARIABLE SPEED DRIVE INSTALLATION 100 200 IOM SEP 13 Page 30 MOTOR COOLING BLOWER WIRING Figure 23 Motor Cooling Blower Wiring Figure 24 Notes for Figures 20 23 and 25 DRAWING NOTES...

Страница 31: ...VYPER VARIABLE SPEED DRIVE INSTALLATION 100 200 IOM SEP 13 Page 31 ANALOG BOARD WIRING Figure 25 Analog Board Wiring...

Страница 32: ...blower fans if present Mounting a Verify that the Vyper Drive is properly mounted to the floor or wall for remote mounts or to the package for package mounted units b Verify that the Vyper power lead...

Страница 33: ...drive operation THREE INSTALLATION STEPS Installation of the Vyper can be done in a few easy steps Before beginning the Setup Procedures be sure that the cabinet has the proper electrical connections...

Страница 34: ...il the fluid level re mains constant about one inch form the top of the manifold See Figure 34 Step 7 Replace and tighten the plug on the top of the mani fold using an adjustable wrench See Figure 35...

Страница 35: ...ential pressure the motor speed will increase to meet the capacity requirement When the slide valve reaches the Capacity Control Slide Valve setpoint the motor speed can increase At this point the sli...

Страница 36: ...r can select either the Vyper or the Har monic Filter setup screens See Figure 39 The flydown menu allows the user to select either the Vyper Drive setup or if the Harmonic Filter is installed the dis...

Страница 37: ...ring the VSD memory and resetting the kWh record Standby Time The VSD enters Standby mode when there is no load on the VSD The VSD capacitor banks remain charged and the compressor output is 0 Hz Stan...

Страница 38: ...indicate the status of the field They are displayed as the following 0 no off 1 yes on VSD Operating Mode Harmonic Filter Present Harmonic Filter Operating Mode Water Pump Energized Precharge Relay E...

Страница 39: ...ompressors via the SFS 229 Frick Interface Board This is accomplished through the reception of a Speed Command value in rotations per minute and a Run Command signal from the Quantum LX control panel...

Страница 40: ...on The screen shown in Figure 43 will appear Type 2 into the User Level field Enter Level 2 password Return to the menu and the Home screen The home screen will now provide additional information as s...

Страница 41: ...pacity Regulations and Package spe cific information Verify that Screw Compressor with Vyper is selected under the package Drive field This will allow the Vyper specific screens to be displayed See Fi...

Страница 42: ...set to PID Channel 5 Use the table below to program the proper settings Parameter Value Name Drive Cooling Control Running Action Forward Control Point Vyper Coolant Device Source Analog Board 2 Devi...

Страница 43: ...ng the motor and the drive from high currents High Motor Amps Load Inhibit Force Unload Delay Warning 5 SEC Shutdown 5 SEC Applied Motor FLA Calculation IF USE Mtr Nameplate SF 1 0 Mtr Nameplate FLA 1...

Страница 44: ...Inhibit Applied Motor FLA x 1 1 374 A Force Unload Applied Motor FLA x 1 12 380 A Warning Applied Motor FLA x 1 13 384 A Shutdown Applied Mtr FLA x 1 15 391 A High Motor Amps Load Inhibit 357 Force U...

Страница 45: ...A Shutdown Applied Mtr FLA x 1 15 339 A High Motor Amps Load Inhibit 310 Force Unload 324 Delay Warning 330 5 SEC Shutdown 337 5 SEC Example 4 What are the High Motor Amp setpoints if a 437 HP Vyper...

Страница 46: ...r The Rate of Decrease setting works in conjunction with the Cycle Time setting to provide variability in the desired speed change step rate The Vyper has an internally set rate of deceleration of 6 0...

Страница 47: ...ating compressors for the base load This allows the required quick response and also prevents the rapid cycling on and off of the other compressors in the system Some additional Vyper features require...

Страница 48: ...advance to the Compressor Safeties Screen Figure 51 Compressor Safeties Screen 1 2 Figure 52 2 1 Turndown Suggested Control Strategy Step 2 Refer to Figure 51 Use the cursor arrow and Tab keys to navi...

Страница 49: ...for the operation shown in Figure 52 VFD Proportional Band This is the value above the Capac ity Control setpoint for forward action at which the output to the drive will match the maximum output set...

Страница 50: ...com munication address with the Quantum LX Panel To config ure the switches for proper communication set switches 1 through 6 to the OFF position Place switch 7 in the ON position The resulting MODBU...

Страница 51: ...e trim pot control until the desired Job FLA setting is achieved The Quantum LX screen will provide feedback to the operator as the adjust ment is made Close the Vyper cabinet and secure with the door...

Страница 52: ...to operate properly The switches should be set at the factory but it is good practice to verify the settings before starting the Vyper The switches should be set as shown in Figure 62 Figure 61 Frick...

Страница 53: ...ndicators RX TX Logic Board to Quantum LX 8 J16 Communications Cable Logic Board to Quantum LX 9 Communications Indicators RX TX Logic Board to Filter Board 10 J15 Communications Cable Logic Board to...

Страница 54: ...e tubing has a milky white coating this indicates that the coolant is corroding the inside of the cooling system and oxidizing the aluminum If any of these conditions exist the coolant may have bacter...

Страница 55: ...A The input current to the Vyper may be considerably lower compared to the output current This is due to the power factor at the input to the Vyper being greater than 0 95 and nearly unity when the Ha...

Страница 56: ...oftware generates for the basic compressor package there are warnings and shutdowns that are associated with the Vyper drive operation These can be initiated by the Quantum LX panel or the Vyper drive...

Страница 57: ...C Baseplate Temperature Occurs when the Phase C baseplate temperature reaches 165 F and this will unload the Slide Valve FRICK VYPER FAULT CODES Quantum LX Failure Code Quantum LX Failure Message 1 V...

Страница 58: ...r each board and they must be correctly installed There are a total of seven 7 EPROMs in each Vyper system These EPROMs are cre ated as a set and cannot be intermixed All pins must be properly inserte...

Страница 59: ...pt applying to Phase C Inverter Baseplate Temperature Fault 13 Low Phase B Inverter Baseplate Temperature Message Quantum Fault 13 Quantum LX Low Phase B Inverter Baseplate Temperature The phase bank...

Страница 60: ...r board and relayed to the Vyper Logic board to initiate a system shut down The single phase control uses circuitry to detect the loss of any one of the three input phases The trigger board will detec...

Страница 61: ...these conditions connect a 12 VDC source such as a battery charger used to charge automobile batteries and apply 12 VDC between the positive bus and negative bus plates on power unit while measuring...

Страница 62: ...is generated when communications between the Quantum LX Panel and the Frick Interface board or the Frick Interface board and Vyper Logic board is disrupted for a least 22 seconds Check the shielded c...

Страница 63: ...board Fault 50 Harmonic Filter High DC Bus Voltage Message Quantum Fault 50 Quantum LX Harmonic Filter High DC Bus Voltage Fault The harmonic filter s DC link voltage is continuously moni tored and if...

Страница 64: ...be equal to or greater than 50 VDC 41 VDC for 50 HZ 1 10 second after the filter precharge relay is energized Also the filter s DC bus voltage must be equal to or greater than 525 VDC 425 VDC for 50...

Страница 65: ...should be replaced If the voltages are not equal check the wiring between the bleeder resistors 12RES and 13RES and the filter power unit Also check the value of these resistors They should be 3000 oh...

Страница 66: ...the line frequency is within range RECOMMENDED SPARE PARTS 305 254 HP NOTE This list is based on one unit When stocking for more than one unit the quantity should be adjusted to meet your individual r...

Страница 67: ...ronic 1 ALL 025 40386 000 Board SCR Trigger 60 Hz 1 ALL 031 02060 001 Board SCR Trigger 50 Hz 1 ALL 031 02060 002 Kit VSD Power Module IGBT with Gate Driver Board 1 437 362 371 04164 001 437 362 HP OP...

Страница 68: ...transformer 13 multiple ground conductors 12 NEC code book 11 NEMA rating 14 Optical Isolation 15 parallel connect 14 plant supply transformer 13 point to point wiring 11 Quantum LX panel 15 refriger...

Страница 69: ...r 9 21 heat exchanger 21 32 33 56 horseshoe jumper 58 I IGBT 60 IGBT Module 61 IGBT module 56 IGBT transistor 61 impedance 8 input fuses 60 INSTALLATION 4 16 AC line choke 17 Analog Board Wiring 31 An...

Страница 70: ...verage Current 38 Baseplate Temperature 38 Capacity Regulations 41 Clear Standby Time 37 Clear VSD Memory 38 Comm 1 41 Converter Heatsink Temp 38 Current Phase 38 Current Value Timer 38 DC Bus Voltage...

Страница 71: ...T1 lug 55 temperature sensor 17 61 temperature sensors 32 test button 56 thermistors 28 thermistor sensor 61 Three Phase Inductor 19 timeout 66 Total Demand Distortion 59 Total Harmonic Distortion 8...

Страница 72: ...age 72 Johnson Controls 100 CV Avenue Waynesboro PA 17268 1206 USA Phone 717 762 2121 FAX 717 762 8624 www jci com frick Form 100 200 IOM 2013 09 Supersedes 100 200 IOM 2012 09 Subject to change witho...

Отзывы: