QUANTUM™ 4 CONTROLLER BOARD 

 

INTRODUCTION 
 

Frick

®

 Controls strives to remain on the cutting edge 

of microprocessor technology and development. 
Because of the ever-increasing speed, memory 
features, and power of microprocessors, Frick

® 

will 

continue to introduce the latest advancement in 
microprocessor control technology. 

 

 

 
Quantum™ 4 

 

TROUBLESHOOTING THE QUANTUM™ CONTROL 
PANEL 

 

This section contains information on troubleshooting 
and making corrections to the boards and control 
circuits of the Quantum™ 4. Refer to the drawings at 
the end of this manual. 

 

GENERAL INFORMATION 
 

The components within the control panel can be 
inadvertently damaged by static electricity or 
mishandling. Only qualified technicians should 
directly handle these components. 

 

1.

 

DO NOT attempt to make corrections to the 
power supply without shutting off the power 
to the control panel. Accidental shorts can 
irreparably damage the processor boards or 
the display screen. 

 
2.

 

DO NOT HANDLE the panel boards when 
their cables are disconnected without first 
attaching a properly grounded wrist ground 
strap to prevent static electrical discharge 
from your body. 

 

Most problems encountered with the microprocessor 
and control circuits will be the result of a wiring fault, a 
blown fuse, faulty I/O module or failure of a peripheral 
control such as a solenoid coil or a pressure 
transducer. Faults in the computer, while possible, are 
unlikely. If a fault develops in the computer, the 
probability is that all functions will cease. The control 
system of the compressor consists of an AC (high 
voltage) side, which can be either 120 volts, or 230 
volts, and a DC (low voltage) side. The AC side 
actuates solenoids, relays, alarms, and other 
electromechanical functions. The DC side operates 
the computer and it's various sensors. 

 

When working within the panel, the AC high 
voltage side, which can be either nominal 120 
VAC or nominal 230 VAC, CAN CAUSE INJURY 
OR DEATH. 

 
To troubleshoot the low-voltage side of the control 
circuits, it is necessary to have the following tools: 

 

1.

 

Accurate digital multi-meter (capable of 
reading DC/AC mA to the hundreds place) 

 
2.

 

Small wire stripper 

 
3.

 

Small screwdriver (with insulated shaft) 

 
4.

 

Small snip nose pliers 

 
5.

 

Wrist Grounding strap 

 
6.

 

Static free grounded work surface 

 

Note: Proper panel voltage refers to the AC (high 
volt-age) that has been supplied to the panel, 
which could be either nominal 120 VAC or 
nominal 230 VAC (Reference the Control Panel 
Power Specifications). 
 

Some problems that are encountered involve 
troubleshooting the panels digital inputs and outputs. 
The Digital I/O (Input/Output) boards have six Digital 
I/O (DIO) board connectors labeled P1 through P6. 
The input and output modules are wired into a DIO 
connector plug. Position 3 provides power and 
position 4 is a neutral on the DIO connectors. 

 
WHAT TO DO BEFORE CALLING THE FACTORY 

 

Many times when a suspected Quantum™ problem is 
called in to the factory, not enough information is 
provided for the service personnel to assist in solving 
the problem. This is because the caller most likely is 
not aware of the type of information that would be 
useful to factory personnel in helping to identify and 
correct the problem. An example of this is the 
statement that the Quantum™ is not booting (the 
main processor board is not starting). Unfortunately, 
this description is usually vague and only means that 
nothing is showing on the web browser or the optional  

Содержание FRICK QUANTUM LX AcuAir

Страница 1: ...cuAir CONTROL PANEL Version 3 0x Form 090 510 M OCT 2010 MAINTENANCE File SERVICE MANUAL Section 90 Replaces S90 510 M MAR 2008 Dist 3 3a 3b 3c Please check www johnsoncontrols com frick for the lates...

Страница 2: ...ions To The Quantum 13 Logic Voltage Power LED 13 Active LED 14 Digital Inputs 14 Digital Outputs 14 Checking The Digital Inputs And Outputs 14 Fuse Testing And Replacement 15 Input And Output Module...

Страница 3: ...ontrol Panel Communications Setup setup and wiring for data communication using available protocols S90 510 M Frick Quantum LX AcuAir Control Panel Maintenance repair and troubleshooting S90 512 O Fri...

Страница 4: ...world can be achieved through industry standard communications protocols The combination of the Quantum 4 control board and the specific software program that it runs is known as the Quantum LX Additi...

Страница 5: ...Digital and Analog control Fuses and circuit breakers Pressure switches An auxiliary 120 volt plug to be used for maintenance purposes Control Relays The next drawing shows the inside of the door for...

Страница 6: ...of the Digital Board that failed An shutdown message stating Analog Board x Comm Fail Shutdown where x is replaced by the number of the Analog Board that failed Numerous sensor fault shutdown messages...

Страница 7: ...the supply itself may need replaced The 12 Vdc may be measured the same as the other voltages however this voltage is not adjustable on any supply so if the harness is not the culprit the supply may n...

Страница 8: ...N 5 AC LINE PIN 3 OUTPUT 1 5 1V PIN 4 COMMON MATING CONNECTORS MOLEX HOUSING CONTACT INPUT 26 03 4050 08 52 0113 OUTPUT 26 03 4131 08 52 0113 PIN 5 COMMON PIN 6 COMMON PIN 7 COMMON PIN 8 OUTPUT 2 24V...

Страница 9: ...hich can be either 120 volts or 230 volts and a DC low voltage side The AC side actuates solenoids relays alarms and other electromechanical functions The DC side operates the computer and it s variou...

Страница 10: ...urface 3 Ensure that the jumpers on the new board are set the same as those on the old board 4 Install the flash card from the old board to the replacement board 5 Install the modified replacement boa...

Страница 11: ...RS 422 RS 485 LK 4 LK 3 LK 6 LK 5 D1 D8 LK17 RS 422 RS 485 LK 8 LK 7 LK 10 LK 9 D6 D2 LK11 B A PL1 COM1 RX COM2 RX KB 3 LK1 Com 3 RS 232 Connector USB Connector Depending on board version USB could b...

Страница 12: ...S 485 Not Terminated LK10 in out RS 422 Terminated RS 422 Not Terminated LK11 in out Bit 1 of 259H Logic 1 User Application Link Bit 1 of 259H Logic 0 User Application Link LK12 in out Bit 2 of 259H L...

Страница 13: ...end that plugs into the Quantum Another connector plugs into the power supply The remaining three connectors 16 pin will plug into each of the Digital and Analog Boards in the system up to three total...

Страница 14: ...an associated Output channel The following pictorial shows a side view of the 120 VAC Input module The color of an Input module is yellow Never plug a 120 Volt Input module into a 240 Volt system and...

Страница 15: ...he terminal strip 5 If the voltage is OK check the wiring external to the panel 6 If voltage is not OK check the fuse 7 If the fuse is OK then check the module 8 If the module is OK check for proper p...

Страница 16: ...F9 F8 F7 F6 F5 F4 F3 F2 F1 F24 F16 F15 F14 F23 F22 F21 1 P5 1 M7 D7 M6 D6 M5 D5 M4 D4 M3 D3 M2 D2 M1 D1 Channel 9 Channel 10 HOT NEUTRAL Channel 11 Channel 12 Channel 13 Channel 14 HOT NEUTRAL Channel...

Страница 17: ...in out RS 422 transmit pull up for long communications lines No pull up J9 in out RS 422 485 receive pull down for long communications lines No pull down J10 in out RS 422 receive pull down for long...

Страница 18: ...as to the function of each channel Communications LED s The Quantum controller is in constant communication with the Analog and Digital Board s You will notice on each Analog and Digital board that t...

Страница 19: ...the DVM and carefully insert the end into the 5V lead and the black negative probe end into the RET Return or Common lead as shown below Set the DVM to read DC and set the proper range The voltage re...

Страница 20: ...his can show up as a whole assortment of problem channels The easiest way to find a short to earth problem is to disconnect all the sensor plugs and ohm out each plug screw terminal to earth for open...

Страница 21: ...H2 P4B Inputs CH3 CH4 P5A Inputs CH5 CH6 P5B Inputs CH7 CH8 P6A Inputs CH9 CH10 P6B Inputs CH11 CH12 P7A Inputs CH13 CH14 P7B Inputs CH15 CH16 P9A Inputs CH17 CH18 P9B Inputs CH19 CH20 P10A Inputs CH2...

Страница 22: ...ermination No termination default setting Miscellaneous LK2 In Out Not Used LK3 In Out Not Used LK4 In Out Not Used default setting NOTE Although LK2 3 and 4 are not used they must still be set for th...

Страница 23: ...Digital Board Inputs and Outputs SCREEN NAME Digital I O ACCESSING DESCRIPTION This Digital Service Screen has been provided to view the raw data from a Digital Board All Digital boards that have been...

Страница 24: ...ENANCE Analog Board Inputs and Outputs SCREEN NAME Analog I O ACCESSING DESCRIPTION The Analog Service Screen has been provided to view the raw data from an Analog Board Analog values are converted fr...

Страница 25: ...CONTROL PANEL 090 510 M OCT 10 MAINTENANCE Page 25 Diagnostics SCREEN NAME Analog I O ACCESSING DESCRIPTION The Diagnostics screen has been provided as a way for the user to test the Ethernet connect...

Страница 26: ...ts or custom text that may have previously been setup Ensure that a USB Adapter flash card reader and flash card have been installed prior to accessing this screen Ensure that all setpoint values have...

Страница 27: ...be issued All outputs are turned off on a Digital Board that has lost communications All inputs will get set to their minimum value range on an Analog Board that has lost communications A loss of comm...

Страница 28: ...ings that can occur that would cause an I O board to stop communicating with the Quantum LX and would require that you Redetect I O Comms A board has been removed and power was turned on with the boar...

Страница 29: ...s are properly grounded The two types of transducers you may have are as follows an older type has an 8 to 10 inch 3 conductor pigtail coming out of the transducer This type will have the attaching ca...

Страница 30: ...w go into the user interface and modify the IP address for the unit in question to the number that they need it to be or they may leave it alone If the above steps fail to bring the unit back into the...

Страница 31: ...stomer Remote Computer DCS System RX TX RX TX BLK CLR AIR HANDLER 2 1 2 3 4 BLK CLR QUANTUM 3 OR 4 COM 2 TB2 QUANTUM 3 OR 4 COM 2 TB2 AIR HANDLER 3 BLK CLR 1 2 3 4 QUANTUM 3 OR 4 COM 2 TB2 5 6 7 8 5 6...

Страница 32: ...24VDC Relay 639A0185H10 2 Pos Selector Switch Control Power 639A0185H30 Latch 3 Across Attaches contact block to switch mechanism 639A0185H36 Normally Open Contact Block for Control Power Switch Digit...

Страница 33: ...age 13 18 19 Daisy Chain 13 14 19 DC 13 DCS 31 Digital Board 4 13 15 17 19 23 24 27 Digital Board Description 13 Digital I O 9 10 13 14 15 Digital Inputs 14 Digital Outputs 14 Digital Volt Meter 6 13...

Страница 34: ...Parts 32 Return 13 19 RS 232 12 29 RS 422 12 17 29 31 RS 485 12 29 31 RX Receive 13 19 S Screen 9 10 13 15 17 18 20 23 24 27 28 Sensor 20 27 29 Sensor Fault 20 27 Service Screen 15 23 24 25 26 28 Sho...

Страница 35: ...FRICK QUANTUM LX AcuAir CONTROL PANEL 090 510 M OCT 10 MAINTENANCE Page 35...

Страница 36: ...512 M 2010 10 Supersedes S90 512 M 2008 03 Subject to change without notice Published In USA GUI 1C 2010 Johnson Controls Inc ALL RIGHTS RESERVED JOHNSON CONTROLS 100 CV Avenue P O Box 997 Waynesboro...

Отзывы: