090.510-M (OCT 10) FRICK
QUANTUM™LX AcuAir
CONTROL PANEL
Page 30 MAINTENANCE
2.
Locate the processor board (located on the
inside of the top door).
3.
On the processor board (the larger of the two
boards), locate and temporarily remove
LK12.
4.
Power the unit up.
5.
Wait for one minute to allow the processor to
fully boot.
6.
Power the unit down.
7.
Replace LK12.
8.
Power back up. The IP address will be
automatically set to 192.168.0.105. This
address is know to work, and should solve
the problem. At this point, the unit should
show up at the web browser or Operator
Interface Panel. If the user wishes, they may
now go into the user interface and modify the
IP address for the unit in question to the
number that they need it to be, or they may
leave it alone.
If the above steps fail to bring the unit back into the
network, you will need to verify the Ethernet cables,
hub or switch, Quantum™ control board, etc.
Erasing the System Setpoints
In the event it becomes necessary to erase the
systems setpoints, use the following procedure:
1.
Ensure that the existing setpoints are
documented if possible.
2.
Power the controller down.
3.
Locate the processor board (located on the
inside of the top door).
4.
On the processor board (the larger of the two
boards), locate and temporarily remove
LK11.
5.
Power the unit up.
6.
Wait for one minute to allow the processor to
fully boot.
7.
Power the unit down.
8.
Replace LK11.
9.
Power back up.