FMS-1655M

LIT-12013119

16

The set brightness option on the 

Display 

Setup

 menu allows the intensity of the 

display backlighting to be adjusted from 

very dim to very bright. The brightness 

settings are saved in nonvolatile memory 

and remain in effect through a power 

cycle.

Adding password security 

Access to the FMS-1655M Monitor 

menu system can be protected from 

unauthorized tampering through the 

multi-level security passwords. Up to ten 

individual passwords may be entered in 

the system, each with a specific access 

level. A password entry may be created 

by selecting the 

Passwords Setup

 option 

from the 

System Setup

 menu, and then 

selecting add password. The user is 

prompted to enter a minimum of four and 

up to eight numeric digits. 

Once a password has been specified, the 

user is prompted to specify one of four 

access levels: Unrestricted, Standard, 

Basic, and Restricted. All password 

entries are saved to non-volatile memory, 

and remain in effect through a power 

failure. In the event that a password has 

been forgotten, there is a factory-default 

“back door” password that will provide 

unrestricted access to the user menu 

system. Please consult with the factory for 

more information regarding this password.

Note: An unrestricted password must 

be created first before any restricted 

passwords can be set. 

Resetting Sensor Zero Offset

The FMS-1655M Monitor’s remote sensor 

can have its zero offset reset to the 

factory calibrated default in the event the 

monitored pressure does not approach 

zero when the door to the monitored 

room is opened. Select the 

Reset Zero 

Offset 

option on the 

Diagnostics

 menu 

to begin the procedure.  once the reading 

stabilizes, click the OK button to proceed. 

Exit to the main display and verify that the 

reading goes to zero. If not, repeat the 

above procedure. 

Remote monitoring the FMS-1655M 

Monitor 

The FMS-1655M Monitor  provides native 

support for BACnet® MS/TP protocol over 

a RS-485 serial port located on the FMS-

1655M Monitor user interface display at 

CN7, a 3 pin pluggable terminal block at 

back of display (see page 19). The FMS-

1655M Monitor is able to communicate 

11 points of information to the building 

management system. See page 18 for list 

of BACnet® points. The network settings 

are easily configured by selecting the

Network Setup

 option from the 

Unit 

Setup 

menu. As an alternate means 

of remote monitoring, a 4-20mA signal 

representing the room DP is available 

for connecting to a third party controller 

on the BMS. It is located at the green 

terminal block on the remote sensor

and labeled as “Io.”

PID output setup

The FMS-1655M Monitor has an analog 

output which can be used to control a 

damper actuator for closed loop control of 

the room differential pressure. This analog 

output is present at the 9 pin connector 

on remote sensor and can be configured 

for a 0-10Vdc or 2-10Vdc output through 

the touchscreen display menu. Go to 

PID 

Output

 option in 

Room Setup

 of 

Unit 

Setup

 menu. Select PID Output Setup, 

set operating mode, and output range.

Touch Finish to save settings and exit 

back to PID Output Setup menu. If 

necessary the PID loop parameters can 

be changed by selecting the PID Loop 

Setup option where the Proportional, 

Integral, & Derivative values can be tuned 

for the optimum control loop response. 

For most typical applications, PID factory 

settings work well.

Editing setpoints

When the FMS-1655M Monitor is used 

as a controller, the target differential 

pressure setpoints can be set by selecting 

the 

Room Setup

 option in the 

Unit Setup

 

menu. There the 

Edit Setpoint

 option can 

be selected and the setpoints for Positive, 

Negative, and Neutral isolation can be set 

as well as a deadband.

Diagnostic menu

The FMS-1655M monitor incorporates 

several troubleshooting tools. The 

Override PID Output 

option allows the 

analog output to be overridden and 

locked while test and balance makes 

adjustments to the Supply and Exhaust 

dampers. While in the overridden state, 

the analog output is “disconnected” from 

the PID control loop, if enabled. The 

Real-Time View

 option allows the user to 

see in real time the actual values for the 

Pressure, Setpoint, PID Output, and Door 

Status. A software reset can be invoked 

through the 

Reset Monitor 

option. It is 

recommended to perform this function 

after installation to insure that all user 

settings are properly stored to nonvolatile 

memory. 

Содержание FMS-1655M

Страница 1: ...l apparatus meets all the requirements of the Canadian Interference Causing Equipment Regulations Cet appareil numérique de la Classe A respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada IMPORTANT The FMS 1655M Room Pressure Monitor must be wired to 24 VAC only Wiring the unit to 110 VAC will cause serious damange and void the warranty Risk of Property Damage Ensure th...

Страница 2: ...rning Setpoint Positive Isolation Low Alarm Setpoint Negative Isolation High Alarm Setpoint Negative Isolation High Warning Setpoint Negative Isolation Low Warning Setpoint Negative Isolation Low Alarm Setpoint Audible Alert Operating Mode audible or slient Delay Time Base seconds or minutes Delay Setting 0 60 Alarm Quiet Period Starting Hour 0 23 Alarm Quiet Period Ending Hour 0 23 Engineering Un...

Страница 3: ... Display mounting procedure surface mount 10 Flush thin mount mounting procedure 11 Installation detail view 12 Basic programming 14 Main display screen 14 Configuring Room Pressure Monitor 14 Setting up alarm limits 14 Selecting displayed units 15 Configuring display options 15 Adding password security 16 Cleaning the display 17 Alarm setpoints 18 Setup menu tree 19 ...

Страница 4: ...r Depth 18 bit or 262K colors Backlight Color White Luminous Intensity min 2500 cd m2 FMS 1655M Monitor Surface Mount Enclosure 3 W x 5 H x 1 13 D FMS 1655M Monitor Thin Mount Enclosure 5 W x 8 H x 0 75 D External Remote Sensor Housing 2 3 W x 4 H x 2 7 D Stainless Steel Cover Plate for Flow Tube 2 7 W x 4 5 H x 0 2 D Stainless Steel Cover Plate for Remote Sensor 2 7 W x 4 5 H x 0 2 D Surface Moun...

Страница 5: ...655M LIT 12013119 5 Part Number Guide UNIT FMS Flow Monitor Station FMS 01 Standard remote sensor REMOTE SENSOR S Surface mount T Thin flush mount STYLE SERIES BRAND LB Johnson Controls 1655M BACnet Monitor ...

Страница 6: ...ansformer be split between actuator and controller Doing so will damage the actuator the transformer the controller or all units A single 120 24V 30Va transformer is required for the controller and a separate 120 24V 20Va transformer is required for the actuator This equipment contains electrostatic sensitive components To prevent possible damage take precautions to prevent electrostatic discharge...

Страница 7: ...g in this compartment Note This product should be installed with the manufacturer provided isolated power supply and connected to an electrical circuit protected by a minimum 20A circuit breaker This circuit breaker should be mounted in an approved electrical enclosure located separately but in close proximity to this product 240 VAC 50 60 Hz Blue 1 Amp Slow Blow Fuse Transformer 50 60 Hz ...

Страница 8: ...MS 1655M Monitor provides a single digital input that may be used for monitoring a door switch The configuration of the door switch input is configured for normally closed operation and is active high triggered A SPDT magnetic door switch type is recommended for use with function The user may set up multiple multi level passwords to prevent unauthorized or casual access to the FMS 1655M Monitor co...

Страница 9: ... respectively Route the end of the interface cable with the 3 and 4 pin connector down the wall to the anticipated location of the touchscreen display module 4 Using a suitable length of 2 conductor 20 AWG cable connect the output of the universal isolated power supply module to the power input at the remote sensor module The output of this power supply module is non polarized so the two red wire ...

Страница 10: ...m all 4 conductors of the interface cable are securely attached at the terminal plugs Re connect gray harness between backplate and display module 6 Reconnect the gray harness to the backplate circuit board and attach the display enclosure to the backplate by inserting the tabs at the top of the display into the corresponding slots at the top of the backplate Secure the display enclosure to the ba...

Страница 11: ...wall and discard Be sure to brush off any drywall dust or remnants from the inside surface of the opening to ensure proper adhesion of the retrofit mounting plate 4 Remove the paper backing from the two adhesive strips on the retrofit mounting plate and insert it into the cut opening of the drywall The retrofit plate should be oriented such that the corner notch is located at the lower left corner...

Страница 12: ...all to seal unit penetration Flow Tube When Flow Tube mounting plate is located directly opposite the sensor flow tubing must be cut as short as possible to prevent kinks To Johnson Controls isolation transformer Optional Analog Output Damper Control To optional door switch Wall Section cutaway view Terminal For connection of transmitter to FMS 1655M Monitor Orange wall bracket to be installed fir...

Страница 13: ...ss steel plate and wall to seal unit penetration Terminal For connection of transmitter to FMS 1655M Monitor Flow Tube When Flow Tube mounting plate is located directly opposite the sensor flow tubing must be cut as short as possible to prevent kinks To FMS 1655M Monitor monitor Wall Section cutaway view Rotating clamps secure assembly to wall board Optional Analog Output Damper Control To Johnson...

Страница 14: ...open if door switch is enabled or 2 current differential pressure has drifted outside of the allowable limits of the desired setpoint and are in the caution range A red background indicates that the current differential pressure has reached a critical condition and is outside of the allowable limits of the desired setpoint The FMS 1655M Monitor incorporates a full color touchscreen and includes an...

Страница 15: ...the audible alerts to be suppressed between the specified hours every day thereby eliminating the potential for nuisance alarms Hospitals may take advantage of this feature to minimize nuisance alarms during non visiting hours in patient rooms Selecting displayed units The FMS 1655M Monitor displays differential pressure readings in one of two units inches of water column in WC or Pascals Pa Touch...

Страница 16: ...e FMS 1655M Monitor is able to communicate 11 points of information to the building management system See page 18 for list of BACnet points The network settings are easily configured by selecting the Network Setup option from the Unit Setup menu As an alternate means of remote monitoring a 4 20mA signal representing the room DP is available for connecting to a third party controller on the BMS It ...

Страница 17: ...pping the current room name text brings up an alphanumeric keyboard to quickly change the name of the monitored room Tap anywhere else on the screen enters the Main Setup Menu if no password is stored Otherwise a password must be entered before the Main Setup Menu can be accessed Tapping the units brings up engineering units selection popup to quickly change pressure measurement units Tapping Time...

Страница 18: ...FMS 1655M LIT 12013119 18 Alarm setpoints ...

Страница 19: ...FMS 1655M LIT 12013119 19 Setup menu tree ...

Страница 20: ...FMS 1655M LIT 12013119 20 ...

Страница 21: ...scription Read or Write Analog Inputs AI 1 Analog Input 1 default Differential Pressure Read Only Binary Inputs BI 1 Digital Input 1 Door Switch Read Only Analog Outputs AO 1 Analog Output PID 1 OUT Read Only Analog Values AV 1 Setpoint Differential Pressure Setpoint Read Write AV 2 Low Pressure Alarm Setpoint Read Write AV 3 Low Pressure Warning Setpoint Read Write AV 4 High Pressure Warning Setp...

Страница 22: ...FMS 1655M LIT 12013119 22 FMS 1655M Monitor wiring guide ...

Страница 23: ...respective owners Copyright 2019 Johnson Controls All rights reserved Any unauthorized use or copying is strictly prohibited European Single Point of Contact JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY NA SA Single Point of Contact JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA APAC Single Point of Contact JOHNSON CONTROLS C O CONTROLS PRODUCT MANAGEMENT NO 22 BLOCK D NEW DISTRICT...

Отзывы: