The following table itemizes the list of points available for integration in a building management system (BMS). This table contains the objects for
open N2 integration.
Object
Functional Description
Read or Write
Analog Inputs
AI - 1
Analog Input 1 (default: Primary Pressure)
Read-Only
AI - 17
Analog Input 2
Read-Only
AI - 18
Analog Input 3
Read-Only
AI - 19
Analog Input 4
Read-Only
AI - 20
Thermistor Input 1
Read-Only
AI - 21
Thermistor Input 2
Read-Only
Analog Outputs
AO - 1
Analog Output 1 (default: Primary Damper Control)
Read-Only
AO - 11
Analog Output 2 (default: Supply/Exhaust Damper
Read-Only
AO - 12
Analog Output 3 (spare control output)
Read-Only
AO - 13
Analog Output 4 (spare control output)
Read-Only
Binary Inputs
BI - 3
Digital Input 1 (default: Primary Room Switch)
Read-Only
BI - 4
Digital Input 2 (default: Secondary Room Door Switch)
Read-Only
BI - 5
Digital Input 3 (spare digital input)
Read-Only
BI - 6
Digital Input 4 (spare digital input)
Read-Only
Binary Outputs
BO - 1
Relay Output 1 (default: Primary Alarm Relay Output)
Read-Only
BO - 2
Relay Output 2 (spare relay output)
Read-Only
BO - 3
Relay Output 3 (spare relay output)
Read-Only
BO - 4
Not user-selectable
Read-Only
Internal Float Values
ADF - 1
PID Control Loop 1 Setpoint (Primary Pressure)
Read/Write
ADF - 2
Primary Room Alarm Relay High Setpoint
Read/Write
ADF - 3
Primary Room Alarm Relay Low Setpoint
Read/Write
ADF - 4
Secondary Room Alarm Relay High Setpoint
Read/Write
Internal Float Values (continued)
ADF - 5
Secondary Room Alarm Relay Low Setpoint
Read/Write
ADF - 8
Primary Room Low Alarm Setpoint
Read/Write
ADF - 9
Primary Room Low Warning Setpoint
Read/Write
ADF - 10
Primary Room High Warning Setpoint
Read/Write
ADF - 11
Primary Room High Alarm Setpoint
Read/Write
ADF - 13
PID Control Loop 2 Setpoint
Read/Write
ADF - 14
PID Control Loop 3 Setpoint
Read/Write
ADF - 15
PID Control Loop 4 Setpoint
Read/Write
ADF - 16
Air Change Rate based on Flow Input at AI-1
Read-Only
ADF - 17
Air Change Rate based on Flow Input at AI-2
Read-Only
ADF - 18
Air Change Rate based on Flow Input at AI-3
Read-Only
ADF - 19
Air Change Rate based on Flow Input at AI-4
Read-Only
ADF - 20
Alarm Relay 3 High Setpoint
Read/Write
ADF - 21
Alarm Relay 3 Low Setpoint
Read/Write
ADF - 22
Not user-selectable
Read/Write
ADF - 23
Not user-selectable
Read/Write
ADF - 24
AI-2 Low Alarm Setpoint
Read/Write
ADF - 25
AI-2 Low Warning Setpoint
Read/Write
ADF - 26
AI-2 High Warning Setpoint
Read/Write
ADF - 27
AI-2 High Alarm Setpoint
Read/Write
ADF - 28
AI-3 Low Alarm Setpoint
Read/Write
ADF - 29
AI-3 Low Warning Setpoint
Read/Write
ADF - 30
AI-3 High Warning Setpoint
Read/Write
ADF - 31
AI-3 High Alarm Setpoint
Read/Write
ADF - 32
AI-4 Low Alarm Setpoint
Read/Write
ADF - 33
AI-4 Low Warning Setpoint
Read/Write
ADF - 34
AI-4 High Warning Setpoint
Read/Write
Содержание FMS-1655 Series
Страница 2: ...Notes ...
Страница 34: ...SUBHEAD 27 MOUNTING WIRING Notes ...
Страница 40: ...SUBHEAD 33 MOUNTING WIRING Power Step Down Isolation Transformer provided with FMS Controller ...
Страница 42: ...SUBHEAD 35 MOUNTING WIRING Notes ...
Страница 57: ... 50 Notes ...
Страница 60: ...Integrated Flush Mount Wiring Box Dimensions 53 ...
Страница 61: ...Flush Mount Bracket Dimensions 54 ...
Страница 62: ...Thin Mount Wiring Box Dimensions 55 ...
Страница 64: ...FLOW DIAGRAMS 57 Unit Setup Menu Tree JCI reserves the right to change product specifications without notice ...
Страница 67: ... 60 System Setup Menu Tree FLOW DIAGRAMS ...