background image

FCP-NA-701, FCP-PA-701

24-11482-00006 Rev. —

8

Menu item

Description

Setting options

Default

28

Pipe state – calendar

ON
OFF

OFF

29

Heat to cool day
(unavailable if pipe state – calendar = OFF)

1-Mar to 31-May

15-Apr

30

Cool to heat day 
(unavailable if pipe state – calendar = OFF)

1-Sep to 30-Nov

15-Oct

31

Pipe state 

(unavailable if system type ≠ 2FCU or if pipe 

sensor = true or if pipe state – calendar = ON)

0: heat  
1: cool

0

32

Heat to cool threshold 

(unavailable if system type ≠ 2FCU or if pipe 

sensor = false)

50°F - 72°F (10°C - 22°C)

60°F (16°C)

33

Cool to heat threshold 

(unavailable if system type ≠ 2FC or if pipe sensor 

= false)

55°F - 90°F (13°C - 32°C)

80°F (27°C)

34

Purge frequency 

(unavailable if system type ≠ 2FC or if pipe sensor 

= false)

0: Never 
1: 2 hours 
2: 24 hours

With pipe sensor: 1 
Without pipe sensor: 0

Programmable mode (FCP-PA-701 only)

The programmable mode is available only on the FCP-PA-701 model. In the programmable mode menu you can adjust time of day, 

date, schedule for heat, and schedule for cool. 

To enable the programmable mode, complete the following steps:

1.  Press 

Mode

 to set the thermostat to OFF mode.

2.  Press and hold 

Mode

 and 

Fan

 for 5 seconds to access the advanced settings menu. 

3.  Press 

Up

 to navigate to User Preference Settings, then press 

Mode

 to enter the menu. 

4.  Press 

Mode

 to navigate to 10.

5.  Use the 

Up

 and 

Down

 buttons to set the programmable mode to ON and press 

Mode

 to confirm the change. 

To access the programmable mode, press 

Mode

 to set the thermostat to OFF mode, then press and hold 

Mode

 and 

Up

 for 5 seconds. 

Setting the time and date

To set the time and date, complete the following steps:

1.  In the progrmmable mode, press 

Mode

 to access the Set Time menu.

2.  In the Set Time menu, press 

Mode

 to scroll through the menu and press 

Up

 or 

Down

 to change the options. 

3.  After each change, press 

Mode

 to confirm the change. 

4.  After you set all the options in the Set Clock menu, press 

Mode

 to continue to set the schedule, or press 

Fan

 to exit the menu and 

retun to the home screen.

Setting the heat and cool schedule

You can program a schedule for up to seven consecutive days. Each day can consist of a maximum of six periods. You can change the 

start times for each period by increments of 15 minutes.

To set the heat and cool schedule, complete the following steps:

1.  In the programmable mode, press 

Up

 or 

Down

 to navigate to the heat icon, then press 

Mode

 to access the menu.

2.  Press 

Up

 or 

Down

 to select the day of the week you want to schedule, then press 

Mode

 to confirm the selection.

3.  Press 

Mode

 to navigate to the following setting and press 

Up

 or 

Down

 to set the required period and temperature. Repeat this step 

until you set all the schedule settings. 

4.  Press 

Mode

 to save the settings and return to Set Sche menu. 

5.  Press 

Up

 or 

Down

 to navigate to the cool icon and press 

Mode

 to access the menu.

6.  Repeat Step 3 and Step 4 until you set all the schedule settings. 

Remote sensor

The system configuration summary indicates if a remote sensor is installed. Access the advanced settings menu to see your system 

configuration summary. 

You can adjust the values of the temperature offset to calibrate the remote sensor temperature.

Table 6: System configuration settings (part 2 of 2)

Содержание FCP-NA-701

Страница 1: ...and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the...

Страница 2: ...in to 0 12 in 2 mm to 3 mm 3 Place the top screw hole of the trim plate over the partly inserted screw in the junction box then pull the wires through the trim plate opening 4 Slide the trim plate down to hook the plate onto the screw See Figure 4 5 Place the back housing in the trim plate opening 6 Use the included screws to attach the back housing to the trim plate The bottom screw joins with th...

Страница 3: ... Rev 3 Wiring Figure 5 Attaching the back housing to the trim plate Figure 4 Attaching the trim plate to the junction box Figure 7 2 Pipe fan coil unit Figure 8 4 Pipe fan coil unit Figure 6 Attaching the front housing to the back housing ...

Страница 4: ...tem type remote sensor and pipe sensor The thermostat screen shows the preset configuration menu on the first power up or after a factory reset To select a configuration profile use the Up or Down buttons to scroll through the configuration profiles then press Mode to confirm your selection Table 2 lists the preset configuration profiles Setup and adjustments Figure 9 Conventional PTAC Figure 10 H...

Страница 5: ...e FCU No 4 Off 1 3 15 Yes No 4 pipe FCU 3 0 3 16 Yes No 4 pipe FCU 3 1 3 17 No No 4 pipe FCU 3 3 18 No No HP 3 O 2 19 No No HP 3 B 2 20 No No H C 3 2 Table 2 Preset configuration profiles Button combinations The following table describes the button combinations that you can use to access menus or functions The table also indicates the modes in which these button combinations are applicable Menu or...

Страница 6: ... used with heating or cooling is always set to low You can set the smart auto fan option through the installer configuration setting Fan mode reset When you enable the fan mode reset time the fan mode resets to Auto when the set time elapses You can enable and configure the fan mode reset through the installer configuration setting Setting the temperature To change the temperature when the thermos...

Страница 7: ...e only on FCP PA 701 1 2 3 4 5 6 2 12 Use default temperatures after mode change ON uses default temperatures OFF uses last temperature for each mode ON 13 Default heat mode set temperature 60 F 15 5 C Max Heat Set Temp 70 F 21 C 14 Default cool mode set temperature Min Cool Set Temp 80 F 27 C 74 F 23 5 C Table 5 User preference settings Menu item Description Setting options Default 21 System type...

Страница 8: ...ode and Up for 5 seconds Setting the time and date To set the time and date complete the following steps 1 In the progrmmable mode press Mode to access the Set Time menu 2 In the Set Time menu press Mode to scroll through the menu and press Up or Down to change the options 3 After each change press Mode to confirm the change 4 After you set all the options in the Set Clock menu press Mode to conti...

Страница 9: ...RROR_AIR_ SENSOR_LO Built in temperature sensor detected a too low temperature Check if the thermostat wiring is connected correctly to the FCU or PTAC Contact technical support ER 05 ERROR_REMOTE_ SENSOR_OPEN Verify if the remote temperature sensor is disconnected from the thermostat terminals RS and SC If yes re wire the remote sensor correctly and then power cycle the thermostat Verify if the r...

Страница 10: ...sensor accurate to 1 F 0 6 C at 77 F 25 C Remote temperature sensor type NTC temperature sensor accurate to 2 F 1 2 C at 70 F 21 C Wire size 18 AWG 100 ft 30 5 m maximum to 24 AWG 36 ft 11 m maximum Temperature adjustment range Heat mode 45 F to 90 F 7 C to 32 C Cool mode 60 F to 95 F 15 C to 35 C Accuracy Local temperature sensor 1 F 0 6 C Remote temperature sensor 2 F 1 2 C at 70 F 21 C Remote p...