FCP-NA-701, FCP-PA-701
24-11482-00006 Rev. —
7
Menu item
Description
Setting options
Default
01
Temperature scale
F: Fahrenheit
C: Celsius
F
02
User temperature calibration
Temperature with calibration value. Offset: +/- 5.4°F (+/-
3.0°C)
0.0°F (0.0°C)
03
Temperature calibration – remote
sensor
Temperature with calibration value. Offset: +/- 5.4°F (+/-
3.0°C)
0.0°F (0.0°C)
04
Temperature calibration – pipe
sensor
Temperature with calibration value. Offset: +/- 5.4°F (+/-
3.0°C)
0.0°F (0.0°C)
05
Backlight on duration
10 seconds, 30 seconds, always ON
10 seconds
06
Backlight brightness level
20, 40, 60, 80, 100
80
07
Display content
0: ambient tempe set temperature
1: set temperature only
2: ambient temperature only
0
08
Clock format
(available only on FCP-PA-701)
12: 12 hour
24: 24 hour
12
09
Auto Daylight Savings
(available only on FCP-PA-701)
ON: Auto DST on
OFF: Auto DST off
ON
10
Programming mode
(available only on FCP-PA-701)
ON: programmable
OFF: manual
OFF
11
Periods per day
(available only on FCP-PA-701)
1, 2, 3, 4, 5, 6
2
12
Use default temperatures after
mode change
ON: uses default temperatures
OFF: uses last temperature for each mode
ON
13
Default heat mode set temperature
60°F (15.5°C) - Max Heat Set Temp
70°F (21°C)
14
Default cool mode set temperature
Min Cool Set Temp - 80°F (27°C)
74°F (23.5°C)
Table 5: User preference settings
Menu item
Description
Setting options
Default
21
System type
2FCU: 2-pipe fan coil unit
4FCU: 4-pipe fan coil unit
HP: heat pump
H-C: conventional (furnace elect)
4FCU
22
2-pipe FCU with aux heat available
(available only if system type = 2FCU)
Yes
No
No
23
Available modes
2FCU without aux heat:
04: heat and cool without auto
2FCU without aux: 04
2FCU with aux: 03
4FCU, HP, or H-C: 03
2FCU with aux heat:
03: heat and cool with auto
04: heat and cool without auto
4FCU, HP, or H-C:
01: heat only
02: cool only
03: heat and cool with auto
04 : heat and cool without auto
24
HP valve type
(unavailable if system type = HP)
B: B valve
O: O valve
B
25
Remote sensor location
0: in room
1: in duct
0
26
Remote sensor type
0: type II
1: type III
0
27
Pipe sensor type
0: type II
1: type III
0
Table 6:
System configuration settings (part 1 of 2)