Table 9: Fault list
Error code
Description
Solutions
ER:05
ERROR_REMOTE_SENSOR_OPEN
•
Verify if the remote temperature sensor is
disconnected from the thermostat terminals
RS and SC. If yes, re-wire the remote
sensor correctly and then power cycle the
thermostat.
•
Verify if the remote sensor is malfunctioned
or damaged.
•
Contact technical support.
ER:06
ERROR_REMOTE_SENSOR_SHORT
•
Verify the remote temperature sensor
wiring and check if thermostat terminals
RS and SC are shorted. If yes, re-wire the
remote sensor correctly and then power
cycle the thermostat.
•
Verify if the remote sensor is malfunctioned
or damaged.
•
Contact technical support.
ER:07
ERROR_REMOTE_SENSOR_HI
Remote sensor detected a too high temperature.
•
Check if the thermostat wiring is connected
correctly to the FCU or PTAC.
•
Verify if the remote sensor is installed
correctly in the room or duct.
•
Contact technical support.
ER:08
ERROR_REMOTE_SENSOR_LO
Remote sensor detected a too low temperature.
•
Check if the thermostat wiring is connected
correctly to the FCU or PTAC.
•
Verify if the remote sensor is installed
correctly in the room or duct.
•
Contact technical support.
ER:09
ERROR_PIPE_SENSOR_OPEN
•
Check if the pipe temperature sensor
wiring is disconnected from thermostat
terminals PS and SC. If yes, re-wire the pipe
sensor correctly and then power cycle the
thermostat.
•
Verify if the pipe sensor is malfunctioned or
damaged.
•
Contact technical support.
ER:10
ERROR_PIPE_SENSOR_SHORT
•
Verify the pipe temperature sensor wiring
and check if thermostat terminals PS and
SC are shorted. If yes, re-wire the pipe
sensor correctly and then power cycle the
thermostat.
•
Verify if the pipe sensor is malfunctioned or
damaged.
•
Contact technical support.
ER:11
ERROR_PIPE_SENSOR_HI
Pipe sensor detected a too high temperature.
•
Verify if the pipe sensor is installed correctly
in the pipe.
•
Contact technical support.
ER:12
ERROR_PIPE_SENSOR_LO
Pipe sensor detected a too low temperature.
•
Verify if the pipe sensor is installed correctly
in the pipe.
•
Contact technical support.
25