6 EDA-8000 Product/Technical Bulletin
W
iring
!
CAUTION: Disconnect all power before
wiring the actuator to avoid
electrical shock or damaging the
equipment.
Note:
Connections should be made using flexible
conduit or cable to allow for actuator lateral
motion.
1.
If the cover was replaced after installation, insert a
screwdriver under the edge of the plastic cover
and carefully pry off the cover as shown in
Figure 4.
Conduit
Opening
Covers
Conduit Opening
Figure 8: Conduit Openings
2.
Insert the conduit and wires from the controller
through one of the three conduit openings.
3.
Install the black plugs in the other two openings.
See Figure 8.
K 1
K 2
C W
C C W
C O M
T B1
F T1
From Controller
Clockwise 24 VAC
Counterclockwise 24 VAC
Common
Figure 9: Wiring Connections
4.
Connect the leads to Terminal Block 1 (TB1) as
shown in Figure 9.
C
heckout Procedure
Follow these steps to verify operation after all wiring
connections have been completed:
1.
Apply power to the unit.
2.
Refer to the controller’s manual for directions on
checking out a newly installed device.
3.
Use the controller to drive the actuator fully
clockwise and counterclockwise.
4.
Verify that the damper blades fully open and close.
5.
Install the plastic cover and checkout is completed.