2   EDA-8000 Product/Technical Bulletin

A

pplication

The EDA-8000 is designed to regulate control air
dampers in HVAC systems.  Typical applications
include:

positioning of D-1300 Series Dampers

return air, or exhaust dampers

face and bypass control

blade positioning for variable volume fans

Refer to damper manufacturer’s information to properly
size the damper and actuator.  Return to normal
actuators are recommended for use with outdoor air
dampers.

O

peration

The EDA-8000 Electric Damper Actuator provides a
stall torque output of 100 in·lb with incremental control
of dampers.  It can also be used in a variety of other
applications at 80 in·lb continuous load.

The EDA-8000 is used on dampers having externally
accessible 10 to 12 mm (0.394 to 0.472 inch) square
or 7/16 to 1/2 inch (11 to 12.5 mm) round shafts.

It is compatible with Johnson Controls D-1300
Dampers as a direct mount actuator.  The EDA-8000
housing has additional mounting slots to aid adaptation
to unusual applications.  Several kits are available to
solve virtually any mounting situation.

The EDA-8000 non-spring return actuator will drive the
damper through a full stroke cycle of 90° in
60 seconds.

In typical incremental operation, a controller provides
24 VAC to the Clockwise (CW) or Counterclockwise
(CCW) terminal on the actuator depending on the
desired movement of the damper.  This signal causes
the motor to rotate in the proper direction and moves
the damper blades open or closed.  When no control
signal is present, the actuator holds its position.

The actuator is energized as long as the 24 VAC signal
is present.  Therefore, it is more efficient to pulse the
signal to the actuator, which will prevent excessive
drive time of the motor.  The use of a controller and/or
software that provides a time out to remove the signal
at the end of rotation is preferred to leaving the signal
applied to the actuator at all times.

Содержание EDA-8000

Страница 1: ...turn Figure 1 EDA 8000 Actuator Features and Benefits Direct Mount Simplifies installation Over Torque Protection Patent Pending Eliminates need for setup or maintenance of limit switches Extends life of the actuator Up to 90 Degree Clockwise or Counterclockwise Rotation Increases application versatility Precise Positioning Based on 24 VAC Incremental Input Signals Assures compatibility with most ...

Страница 2: ...ntrols D 1300 Dampers as a direct mount actuator The EDA 8000 housing has additional mounting slots to aid adaptation to unusual applications Several kits are available to solve virtually any mounting situation The EDA 8000 non spring return actuator will drive the damper through a full stroke cycle of 90 in 60 seconds In typical incremental operation a controller provides 24 VAC to the Clockwise ...

Страница 3: ... for spanning channels or objects Dimension Note The actuator requires a minimum damper shaft length of four inches from the mounting surface When determining shaft length consideration has to be given to channel depth insulation etc Refer to the following dimensional drawings Before starting the job obtain the damper installation information to use as a reference when mounting the actuator 6 inch...

Страница 4: ...rangement when using shafts 10 mm 0 472 inch square or 7 16 inch 11 mm round or larger If the duct or wall is less than 16 gauge 0 06 inch or 1 5 mm use the Universal Mounting Bracket D 3153 105 When using the blade pin extension and or the universal mounting bracket follow installation procedures packaged with the product Direction Of Rotation 1 Firmly grasp the drive pin extension with a pliers ...

Страница 5: ...use the Universal Mounting Bracket D 3153 105 Note Because of eccentric motion of the actuator that occurs when using shafts smaller than 10 mm 0 394 inch square or 1 2 inch 12 5 mm round use the isolation grommet only in the bottom center mounting slot 3 Mark the location of the actuator s top and bottom mounting slots on the duct or wall 4 Remove the actuator and coupler and set aside 5 Drill tw...

Страница 6: ...he controller through one of the three conduit openings 3 Install the black plugs in the other two openings See Figure 8 K1 K2 CW CCW C OM TB1 FT1 From Controller Clockwise 24 VAC Counterclockwise 24 VAC Common Figure 9 Wiring Connections 4 Connect the leads to Terminal Block 1 TB1 as shown in Figure 9 Checkout Procedure Follow these steps to verify operation after all wiring connections have been...

Страница 7: ...er Description EDA 8000 1100 Electric Damper Actuator incremental with 60 second travel time for 90 degrees no spring return Unit Replacement The EDA 8000 is not field repairable For a replacement contact the nearest Johnson Controls branch office or your wholesale distributor ...

Страница 8: ...rage Conditions 20 to 150 F 29 to 65 C 90 RH maximum non condensing Dimensions H x W x D 9 25 in x 4 5 in x 4 375 in 235 mm x 114 mm x 111 mm Shipping Weight 8 5 lbs 3 86 kg Agency Compliance UL 916 CSA Agency Listings UL Listed as part of the Metasys Network Accessories Order Separately 3 4 inch coupler kit Product Code Number 8000 100 Drive pin extension for JCI D 1300 Dampers D 9999 142 Univers...

Отзывы: