EDA-8000 Product/Technical Bulletin     5

Standard Mounting

The EDA-8000 is not position sensitive and can be
mounted in any convenient orientation on a duct or wall
that is 16 gauge (0.06 inch or 1.5 mm) or thicker as
long as the drive shaft is perpendicular to the mounting
surface of the actuator.

Top Center 
Mounting Slot

Figure 7:  Actuator Against Duct

1.

Position the actuator onto the blade pin extension
so that the actuator sits against the duct as shown
in Figure 7.

Note:

The bottom center mounting hole looks the
same as the top mounting hole illustrated in
Figure 7.

2.

Use of the actuator’s center mounting slots with
the isolation grommets is the preferred  mounting
arrangement.  If the duct or wall is less than
16 gauge (0.06 inch or 1.5 mm), use the
Universal Mounting Bracket (D-3153-105).

Note:

Because of eccentric motion of the actuator
that occurs when using shafts smaller than
10 mm (0.394 inch) square or 1/2 inch
(12.5 mm) round, use the isolation grommet
only in the bottom center mounting slot.

3.

Mark the location of the actuator’s top and bottom
mounting slots on the duct or wall.

4.

Remove the actuator and coupler and set aside.

5.

Drill two 5/32 inch (4 mm) holes in the duct or wall
at the marked locations.

Note:

When using the universal mounting bracket,
drill two 11/64 inch holes.

6.

Slide the actuator and coupler onto the pin
extension.

7.

Secure the actuator to the wall or duct with the
screws and isolation grommets included in the kit.

8.

Tighten the two square-head screws on the
actuator coupler.

9.

Lift the manual release lever and hand turn the
coupler CW and CCW to check that the damper
blades fully open and close.

Note:

The cover should remain off until the wiring is
completed.

Содержание EDA-8000

Страница 1: ...turn Figure 1 EDA 8000 Actuator Features and Benefits Direct Mount Simplifies installation Over Torque Protection Patent Pending Eliminates need for setup or maintenance of limit switches Extends life of the actuator Up to 90 Degree Clockwise or Counterclockwise Rotation Increases application versatility Precise Positioning Based on 24 VAC Incremental Input Signals Assures compatibility with most ...

Страница 2: ...ntrols D 1300 Dampers as a direct mount actuator The EDA 8000 housing has additional mounting slots to aid adaptation to unusual applications Several kits are available to solve virtually any mounting situation The EDA 8000 non spring return actuator will drive the damper through a full stroke cycle of 90 in 60 seconds In typical incremental operation a controller provides 24 VAC to the Clockwise ...

Страница 3: ... for spanning channels or objects Dimension Note The actuator requires a minimum damper shaft length of four inches from the mounting surface When determining shaft length consideration has to be given to channel depth insulation etc Refer to the following dimensional drawings Before starting the job obtain the damper installation information to use as a reference when mounting the actuator 6 inch...

Страница 4: ...rangement when using shafts 10 mm 0 472 inch square or 7 16 inch 11 mm round or larger If the duct or wall is less than 16 gauge 0 06 inch or 1 5 mm use the Universal Mounting Bracket D 3153 105 When using the blade pin extension and or the universal mounting bracket follow installation procedures packaged with the product Direction Of Rotation 1 Firmly grasp the drive pin extension with a pliers ...

Страница 5: ...use the Universal Mounting Bracket D 3153 105 Note Because of eccentric motion of the actuator that occurs when using shafts smaller than 10 mm 0 394 inch square or 1 2 inch 12 5 mm round use the isolation grommet only in the bottom center mounting slot 3 Mark the location of the actuator s top and bottom mounting slots on the duct or wall 4 Remove the actuator and coupler and set aside 5 Drill tw...

Страница 6: ...he controller through one of the three conduit openings 3 Install the black plugs in the other two openings See Figure 8 K1 K2 CW CCW C OM TB1 FT1 From Controller Clockwise 24 VAC Counterclockwise 24 VAC Common Figure 9 Wiring Connections 4 Connect the leads to Terminal Block 1 TB1 as shown in Figure 9 Checkout Procedure Follow these steps to verify operation after all wiring connections have been...

Страница 7: ...er Description EDA 8000 1100 Electric Damper Actuator incremental with 60 second travel time for 90 degrees no spring return Unit Replacement The EDA 8000 is not field repairable For a replacement contact the nearest Johnson Controls branch office or your wholesale distributor ...

Страница 8: ...rage Conditions 20 to 150 F 29 to 65 C 90 RH maximum non condensing Dimensions H x W x D 9 25 in x 4 5 in x 4 375 in 235 mm x 114 mm x 111 mm Shipping Weight 8 5 lbs 3 86 kg Agency Compliance UL 916 CSA Agency Listings UL Listed as part of the Metasys Network Accessories Order Separately 3 4 inch coupler kit Product Code Number 8000 100 Drive pin extension for JCI D 1300 Dampers D 9999 142 Univers...

Отзывы: